ID hex (dec)
Message
Description
The connected sensor is defective or generates too much
load on its channel.
Remedy
–
Check sensor for correct function, in par-
ticular for current consumption.
–
Check sensor cabling.
01
|
01
|
010B
(16843019)
Short circuit/overload
in sensor supply
Diagnost-
ic status
Error
Undervoltage of the logic supply PS 24 V DC was detec-
ted.
Remedy
–
Check logic supply PS.
02
|
01
|
0016
(33619990)
Undervoltage in logic
supply PS 24 V DC
Diagnost-
ic status
Warning
Error
Undervoltage in the load supply PL 24 V DC was detected.
Remedy
–
Check load supply PL.
02
|
01
|
0105
(33620229)
Undervoltage in load
supply PL 24 V DC
Diagnost-
ic status
Error
A switch-off of the load supply PL was detected. The cause
can be a deliberate shutdown by the emergency stop.
Remedy
–
Check if the emergency stop was activ-
ated.
–
Check load supply PL.
02
|
01
|
0106
(33620230)
Switch-off load supply
PL 24 V DC
Diagnost-
ic status
Information
Overvoltage load supply PL 24 V DC
Remedy
–
Check load supply PL.
02
|
01
|
013F
(33620287)
Overvoltage load sup-
ply PL 24 V DC
Diagnost-
ic status
Error
Device undertemperature
Remedy
–
Check ambient conditions.
03
|
01
|
002D
(50397229)
Undertemperature
Device
Diagnost-
ic status
Error
Output process data watchdog of the AP module expired
08
|
01
|
0130
(134283568)
Output process data
watchdog of the AP
module expired
Remedy
–
Restart AP system.
–
Check the cable.
Diagnostics and fault clearance