Fieldbus startup parameters
ID
Parameter
Instance-
s
Data
type
Access
1)
Arraysize
20022
Configuration of voltage monitoring load
supply PL
–
0: load voltage monitoring inactive
–
1: load voltage monitoring active, with
suppression of diagnostics at switch-
off (factory setting)
–
2: load voltage monitoring active
1
UINT8
rw
–
20049
Setpoint cycle time [ms]
2)
–
0: as fast as possible (factory setting)
–
16: 1.6 ms
–
32: 3.2 ms
–
48: 4.8 ms
–
68: 8.0 ms
–
73: 10.0 ms
–
78: 12.0 ms
–
88: 16.0 ms
–
98: 20.0 ms
–
133: 40.0 ms
–
158: 80.0 ms
–
183: 120.0 ms
4
UINT8
rw
–
20050
Activation of diagnostics for IO-Link device
lost (factory setting TRUE)
4
BOOL
rw
–
20071
Port mode
–
0: DEACTIVATED (factory setting)
–
1: IOL_MANUAL
–
2: IOL_AUTOSTART
–
3: DI_CQ
–
97: PREOPERATE
3)
4
UINT8
rw
–
20072
Review and backup
2)
–
0: no test (factory setting)
–
1: device compatible V1.0
–
2: device compatible V1.1
–
3: device compatible V1.1
Data storage Restore
–
4: device compatible V1.1
Data storage Restore
4
UINT8
rw
–
20073
Target vendor ID
2)
4
UINT16
rw
–
Parameterisation
11
Festo — CPX-AP-I-4IOL-M12 — 2020-03