![Festo CPX-AP-I-4IOL-M12 Скачать руководство пользователя страница 20](http://html1.mh-extra.com/html/festo/cpx-ap-i-4iol-m12/cpx-ap-i-4iol-m12_instructions-manual_2283157020.webp)
IO-Link master event codes
IO-Link
event
code hex
Diagnostics ID
hex
Message
Description
No IO-Link device connected
Remedy
–
Check whether an IO-Link
device is connected.
1800h
08
|
0A
|
01A9
No device connected
Diagnost-
ic status
Error
The recognized IO-Link device does not match
the configured VendorID.
Remedy
–
Check whether the correct IO-
Link device is connected.
1802h
08
|
0A
|
016B
Incorrect VendorID;
deviation of the
Inspection Level
Diagnost-
ic status
Error
The recognized IO-Link device does not match
the configured Device ID.
Remedy
–
Check whether the correct IO-
Link device is connected.
1803h
08
|
0A
|
01A8
Incorrect Device ID;
deviation of the
Inspection Level
Diagnost-
ic status
Error
IO-Link Backup/Restorefailed
–
memory out of
range (2048 octets)
Remedy
–
1809h
08
|
0A
|
0183
BackupInconsistency;
memory out of range
(2048 octets)
Diagnost-
ic status
Error
IO-Link Backup/Restore failed.
DataStorageIndex not available
Remedy
–
180Ah
08
|
0A
|
0184
BackupInconsistency;
DataStorageIndex not
available
Diagnost-
ic status
Error
IO-Link Backup/Restore failed. Unspecific
error in data memory
Remedy
–
180Bh
08
|
0A
|
0185
Backup inconsist-
ency; non-specific
error during data stor-
age
Diagnost-
ic status
Error
Diagnostics and fault clearance
20
Festo — CPX-AP-I-4IOL-M12 — 2020-03