6

3.2 Assigning the AS-Interface addresses

Please note

Addressing valve terminal type CPV..-GE-ASI-8E6A-Z is
only permitted with addressers as per specification 2.1.
Other addressers do not permit clear access to the
slaves and in some cases overwrite the ID1 codes.

Recommendation: Use the Festo addresser type ASI-PRG-
ADR with adapter cable type KASI-ADR.

Factory setting:

Slave 1: address #1, A slave
Slave 2: address #1, B slave

The addressing device scans the existing slaves in the
AS-Interface network.

S

Assign the desired addresses to the two slaves one
after the other.

Operation with AS-Interface masters < Spec. 2.1

Operation with AS-Interface masters < Spec. 2.1 is possible
but both slaves must be programmed as A slave.

Recommendation: For operation with AS-Interface masters
< Spec. 2.1 use valve terminal type CPV..-GE-ASI-8E

8

A-Z

instead of CPV..-GE-ASI-8E

6

A-Z.

Содержание CPV-GE-ASI-8E6A-Z M8 Series

Страница 1: ...Brief description CPV valve terminal with AS Interface type CPV10 14 ASI 8 E6A English 8101710 2018 11b 8101712 Compact performance...

Страница 2: ...Ruiter Stra e 82 73734 Esslingen Germany Internet http www festo com E Mail service_international festo com Reproduction distribution or sale of this document or communication of its contents to other...

Страница 3: ...stems and valve terminals may only be installed by personnel especially trained for this purpose Detailed information on the design and addressing of your bus system can be found in the manual for you...

Страница 4: ...ption fields for addresses 8 LED status display for valves yellow 9 Valve plates slave 2 aJ Valve plates slave 1 aA Load voltage connec tion for valves aB PWR LED power green Fault LED fault red PWR L...

Страница 5: ...f the inputs and outputs valves Slave 1 Inputs I0 I3 outputs O0 O2 Slave 2 Inputs I4 I7 outputs O4 O6 Automatic addressing with the function Automatic address assignment of the master is not possible...

Страница 6: ...ype ASI PRG ADR with adapter cable type KASI ADR Factory setting Slave 1 address 1 A slave Slave 2 address 1 B slave The addressing device scans the existing slaves in the AS Interface network S Assig...

Страница 7: ...ess selector LED will light up to indicate that slave 1 has been disconnected from the AS Interface Please note The red address selector LED must not light up when the valve terminal is operated If th...

Страница 8: ...FF 3 OFF 4 ON J 2 Addresses of the solenoid coils for AS Interface address n m 3 Addresses or LEDs of the solenoid coils 14 4 Addresses or LEDs of the solenoid coils 12 5 Valve plates with 2 valve sol...

Страница 9: ...nections with the protective caps type ISK M8 Only in this way can you comply with protection class IP65 Please note The inputs are resistant to short circuits If a short cir cuit occurs the slave wil...

Страница 10: ...e AS Interface has an integrated watchdog function which resets the outputs if there is a bus communica tion failure Warning Use power supplies which guarantee reliable electrical isolation of the ope...

Страница 11: ...Pin assignment 24 V DC black cable 3 Pin 2 24 V brown 4 Pin 1 0 V blue 0 1 1 2 3 4 For connecting the valve terminal use the Festo cable sockets type ASI SD FK You will then comply with protection cla...

Страница 12: ...can be fitted with double solenoid and or single solenoid valves During conversion the new valve terminal configuration must be set on the DIP switches on the bottom of the electric sub base 1 DIP swi...

Страница 13: ...inserted or provided with protective cap IP65 Relative humidity 95 non condensing Electromagnetic compatibility EMC interference emission EMC resistance to interference See declaration of conformity w...

Страница 14: ...correct polarity Residual ripple Current consumption for 8 valves when switched on 26 4 V 2 when switched on 20 4 V 2 after current reduction stationary 26 4 V after current reduction stationary 20 4...

Отзывы: