Festo CPV10/14-ASI-8E6A 2018-11b English
14
Type CPV...-GE-ASI-8E6A-Z M8
AS-Interface bus connection
– Voltage range (protected against incorrect
polarity)
– Residual ripple
– Max. current consumption
– all inputs 0-status
– all inputs 1-status, no current
consumption by sensors (e.g. switches)
– all inputs in 1-status, max. current
consumption by sensors
1)
26.5 ... 31.6 V DC
≤ 20 mVpp
CPV10-... CPV14-...
40 mA
40 mA
96 mA
96 mA
278 mA
278 mA
Load voltage connection
– Rated value (protected against incorrect
polarity)
– Residual ripple
– Current consumption for 8 valves
– when switched on (26.4 V)
2
)
– when switched on (20.4 V)
2
)
– after current reduction (stationary; 26.4 V)
– after current reduction (stationary; 20.4 V)
21.6 ... 26.4 V DC
4 Vpp
CPV10-... CPV14-...
150 mA
233 mA
120 mA
158 mA
53 mA
75 mA
68 mA
90 mA
Valves (see Pneumatics manual)
Watchdog function
active after approx.
40 ... 100 ms (see
3.5)
Digital inputs
– Design
– Logic level
– Reference potential
– Response delay
8 digital inputs
based on IEC 1131-2
type 2
24 V DC, PNP,
Status display (LED)
ON: 11 ... 30 V
OFF: -30 ... 5 V
0 V
typ. 3 ms (at 24 V)
1)
e.g. per input 30 mA, incl. 7 mA for input circuit
2
) for max. 30 ms all valve coils switched simultaneously