10
TECHNICAL DATA AND PERFORMANCE
Technical data
Efficiency capacity in heating mode - Average climate
Model
5
7
10
14
14T
Efficiency capacity - medium temperature (water 55°C)
Efficiency season - medium temperature (water 55°C)
126
126
129
129
128
Efficiency capacity - low temperature (water 35°C)
Efficiency season - low temperature (water 35°C)
176
178
162
173
168
NOTA:
Declared according to
European regulation 811/2013
. The values are referred to units without options and accessories.
The values are referred to units without options and accessories.
Data declared according to
EN 14511
:
EER
(Energy Efficiency Ratio) = ratio of the total cooling capacity to the effective
power input of the unit
COP
(Coefficient Of Performance) = ratio of the total heating capacity to the effective
power input of the unit
A35W7
= source : air in 35°C d.b. / plant : water in 12°C out 7°C
A35W18
= source : air in 35°C d.b. / plant : water in 23°C out 18°C
A7W45
= source : air in 7°C d.b. 6°C w.b. / plant : water in 40°C out 45°C
A7W35
= source : air in 7°C d.b. 6°C w.b. / plant : water in 30°C out 35°C
General data
Modelli
5
7
10
14
14T
Power supply
220-240V~ 50Hz, 1Ph
380-415V~ 50Hz,
3Ph+N
V-ph-Hz
Compressor type
Twin Rotary DC
-
N° compressors / N° refrigerant circuits
1 / 1
n°
Plant side heat exchanger type
stainless steel brazed plates
-
Source side heat exchanger type
finned coil
-
Fans type
DC axial
-
N° fans
1
2
n°
Expansion tank volume
2
5
l
Water safety valve set
3
bar
Hydraulic fittings
1" M
1-1/4" M
“
Minimum water content onf the system
20
l
DHW boiler - minimum surface of the coil
1,4
1,7
m
2
Refrigerant type
R410A
-
Refrigerant charge
2,40
3,60
kg
Control type
Remote wired
-
SWL - Sound power level*
61
65
66
71
71
dB(A)
SPL - Sound pressure level at 1mt **
46
50
51
56
56
dB(A)
Maximum current input
16
16
32
32
16
A
* SWL = Sound power levels, with reference to 1x10
-12
W.
The Total sound power level in dB(A) measured in compliance with ISO 9614 stan-
dards. The Total Sound Power in db(A) the only binding acoustic specification.
** SPL = Sound pressure levels, with reference to 2x10
-5
Pa.
The sound pressure levels are values calculated by applying the ISO-3744 relation.
Performances data
- Models
5
7
10
14
14T
A7W35
Heating capacity
nom
4580
6550
10430
14760
14100
W
min-max
1566 - 8884
2050 - 10910
3586 - 13395
5207 - 16595
4715 - 16763
W
Power input
nom
970
1450
2280
3400
3260
W
min-max
327 - 2226
448 - 2734
771 - 3848
1178 - 4768
1077 - 4816
W
COP
4,72
4,52
4,57
4,34
4,33
W/W
Water flow rate
788
1127
1794
2539
2425
l/h
A7W45
Heating capacity
nom
4670
6690
10170
14080
14110
W
min-max
1581 - 6238
2047 - 7661
3429 - 12207
4870 - 15123
4626 - 15276
W
Power input
nom
1430
2050
3080
4470
4460
W
min-max
478 - 1944
623 - 2387
1025 - 3948
1525 - 4892
1451 - 4941
W
COP
3,27
3,26
3,30
3,15
3,16
W/W
Water flow rate
803
1151
1749
2422
2427
l/h
A35W1
8
Cooling capacity
nom
4550
6450
10250
14610
14030
W
min-max
2255 - 8818
2788 - 10829
5037 - 14203
6423 - 17596
5873 - 17774
W
Power input
nom
1000
1470
2060
3320
3260
W
min-max
448 - 2447
581 - 3022
931 - 3867
1314 - 4791
1269 - 4839
W
EER
4,55
4,39
4,98
4,40
4,30
W/W
Water flow rate
783
1109
1763
2513
2413
l/h
A35W7
Cooling capacity
nom
4550
6710
10440
12950
13800
W
min-max
1454 - 5524
1850 - 7136
3485 - 11364
4435 - 13629
4480 - 14566
W
Power input
nom
1550
2570
3280
4530
5140
W
min-max
483 - 2097
687 - 3029
1077 - 4249
1520 - 5500
1649 - 6288
W
EER
2,94
2,61
3,18
2,86
2,68
W/W
Water flow rate
783
1154
1796
2227
2374
l/h
A++
A++
A++
A++
A++
A++
A++
A++
A++
A++
Содержание RVL-I PLUS
Страница 31: ...31 SETUP OF THE SYSTEM...
Страница 32: ...32 SETUP OF THE SYSTEM...
Страница 33: ...33 SETUP OF THE SYSTEM...
Страница 34: ...34 SETUP OF THE SYSTEM FOR SEVICEMAN menu english language...
Страница 35: ...35 SETUP OF THE SYSTEM...
Страница 36: ...36 SETUP OF THE SYSTEM...
Страница 37: ...37 SETUP OF THE SYSTEM...
Страница 91: ...91...