CONTROL SYSTEM
38
Remote thermostat programming
The configuration parameters of the remote ther-
mostat must be set on the device itself.
A long press (longer than 3 seconds) on the
OCCUPANCY button allows to enter the
Programming menu from which is possible to
modify the parameters listed in the table.
When a parameter is selected the current value
blinks. Use the knob to adjust the value of the
parameter. Press briefly the OCCUPANCY button
to select the following parameter.
Press the HEATING button to escape from the
Programming menu.
Remote control (wired o wireless) programming
The configuration parameters of the remote control must be set on the device itself. Entering the “Operator section” menu it is
possible to adjust the parameters listed in the table.
Menu
Level
Parameter Function
Operator section
E
20
Language
F
22
Informations
F
26
Operation lock
F
27
Programming lock
I
28
Save settings
I
40
Renote control use
I
42
Heating circuits assignment
I
46
Operation heating circuit P
I
48
Action OCCUPANCY button
F
54
Room temperature sensor offset
Parameter Function
ru
Remote thermostat use
ru
= 1 management heating circuit 1
ru
= 3 management heating circuit P
P1
Save settings
P1
= 1 save pressing HEATING button or without confirmation
(for timeout)
P1
= 2 save pressing HEATING button
P2
Operation lock
P2
= 0 lock disabled
P2
= 1 all the buttons are locked (access to Programming
menu granted)
For details on the settings of parameters 40, 42, 44 and 46 see paragraph “Heating and cooling circuits”.
The room temperature sensor contained inside the remote control can be calibrated adding an offset (parmeter 54) to the value
read.
Functions available for the user
Heat pump type setting
It is possible to set the type of heat pump (water-water or brine-water) modifying the parameter 5800.
Hour, date and language setting
In order to set hour and date enter the “Hour and date” menu and modify the parameters 1, 2 and 3. It is possible to select the
desired language for the user interface and for each remote control through the “Operator section” menu (parameter 20).
Time tables setting
When the selected operating mode is “Automatic”, the circuits are activated according to the set time tables.
It is possible to set the time table independently for each circuit (heating circuit 1, heating circuit P, domestic hot water circuit,
cooling circuit 1).
For the cooling circuit 1 it is possible to select, through the parameter 907, whether :
- keep the circuit always activated (24 hour per day)
- activate the circuit according to time table 5
- activate the circuit according to heating circuit 1 time table
For each time table it is possible to specify the program to use in the different days of the week :
- daily (a different program for each day of the week)
- weekly (same program for all the days of the week)
- week end (a program from Monday to Friday and another program from Saturday to Sunday)
For each program it is possible to specify 3 different operating phases per day (6 switch on or switch off events per day).
All the programs can be restored to the dafault values.