CONTROL SYSTEM
Inputs and outputs
ID
Use
Description
Features
Available
for the user
Input
s
B9
B9
outdoor air temperature
temperature sensor NTC 1K
B91
B91
source heat exchanger inlet temperature
temperature sensor NTC 10K
B92
B92
source heat exchanger outlet temperature
temperature sensor NTC 10K
B71
B71
plant heat exchanger inlet temperature
temperature sensor NTC 10K
B21
B21
plant heat exchanger outlet temperature
temperature sensor NTC 10K
B3
B3
domestic hot water buffer temperature
temperature sensor NTC 10K
B1
B1
heating circuit 1 flow temperature
temperature sensor NTC 10K
BX1
B4
plant buffer temperature
temperature sensor NTC 10K
x
BX2
B41
plant buffer temperature - bottom
temperature sensor NTC 10K
x
BX3
B31
domestic hot water buffer temperature - bottom
temperature sensor NTC 10K
x (1)
BX4
B38
instantaneous domestic hot water flow temperature
temperature sensor NTC 10K
x (1)
BX5
B6
solar collector temperature
temperature sensor NTC 10K
x
H1
H1
instantaneous domestic hot water flow switch
voltage free digital input
H3
H3
room humidity sensor
voltage free digital input
0-10 Vdc input
x
E9
E9
Low pressure switch
230 Vac digital input
E10
E10
High pressure switch
230 Vac digital input
EX1
E15
Source flow switch
230 Vac digital input
EX2
E24
Plant flow switch
230 Vac digital input
EX3
E5
Low tariff
230 Vac digital input
x
EX4
E6
Electrical power supply lock
230 Vac digital input
x
EX5
-
-
230 Vac digital input
x
EX6
-
-
230 Vac digital input
x
EX7
-
-
230 Vac digital input
x
Output
s
K1
K1
Compressor
2 A - 230 Vac
Q2
Q2
Heating circuit 1 pump
2 A - 230 Vac
Q3
Q3
Domestic hot water 3 way valve
2 A - 230 Vac
Q8
Q8
Source pump
Source 2 way valve
2 A - 230 Vac
Q9
Q9
Plant pump
2 A - 230 Vac
QX1
K25
Integrative electrical heaters - step 1
2 A - 230 Vac
x (2)
QX2
K26
Integrative electrical heaters - step 2
2 A - 230 Vac
x (2)
QX3
Y28
Passive cooling 3 way valve
2 A - 230 Vac
x (3)
QX4
Q33
Q34
Domestic hot water pump
Instantaneous domestic hot water pump
2 A - 230 Vac
x (1)
QX5
Y22
Reversing cycle valve
2 A - 230 Vac
x (4)
QX6
Q20
Q5
Heating circuit P pump
Solar collector pump
2 A - 230 Vac
x
Y1/Y2
Y1/Y2
Heating circuit 1 3 way mixing valve
2 A - 230 Vac
x
UX
-
-
0-10 Vdc
x
(1)
Available for the user only if as “Domestic hot water production” option has not been chosen “3 way valve with primary heat exchanger”
or “3 way valve with secondary heat exchanger”.
(2)
Available for the user only if the “Integrative electrical heaters” option has not been chosen.
(3)
Available for the user only if the “Passive cooling” option has not been chosen.
(4)
Available for the user only for not reversible heat pumps (IH).
The following table shows the list of the inputs and outputs available on the controller of the heat pump along with the expected
use. Some inputs and outputs can be configured in a different way by the user in order to manage other plant components which
are not contained inside the heat pump.