CONTROL SYSTEM
41
Alarms activation and reset
The controller is able to perform a complete diagnosis of the
unit detecting all the operating faults and notifying different
alarms.
The activation of an alarm implies :
- involved consumers locked
- alarm icon shown on the display
- event recorded in the alarm history
To show the details about the active alarm press the INFO but-
ton.
Alarms that can damage the unit or the plant require a
manual
reset
that implies that the operator has to reset manually the
controller. It is advisable to verify accurately the cause that ori-
ginated the alarm and to make sure that the problem has been
solved before restarting the unit. In any case the unit will
restart only if the cause of the alarm has disappeared.
For the manual reset alarms, pressing the INFO button, along
with the details about the alarm, also the message “Reset ?”
will appear. Press the OK button. When the message “Yes”
blinks press again the OK button to confirm the alarm reset.
The less critical alarms have an
automatic reset
. As soon as
the minimum compressor switch off time has elapsed the con-
troller tries to reset the alarm. If the cause that originated the
alarm has disappeared, the unit starts working again and the
alarm icon is no more shown on the display. Some of these
alarms become manual reset alarms if the number of events
in an hour exceeds a fixed threshold.
It is possible to reset the active alarms also through the
RESET button. In that case the scheduled delays at the unit
switch on are ignored avoiding undesired waiting times during
commissioning or fault tracing. This function should NOT be
used in normal operation.
Alarm history
The controller allows to save the last 10 alarms occured
during the unit operation. For each event the following details
are recorded :
- alarm code
- hour
- date
Such details can be displayed entering the “Errors” menu
(parameters from 6800 to 6819).
When the number of saved events is higher than 10 the follo-
wing events are saved deleting the oldest alarms.
Alarms
Note:
(1) A = automatic reset , M = manual reset , A / M = manual reset only if the number of events in an hour is higher than 3.
(2) Only for brine-water units
(3) Only for water-water units
Alarms table
Code
Alarm
Reset
(1)
Input
Heat pump
lock
10
Outdoor air temperature sensor
A
B9
No
33
Plant side flow temperature sensor
A
B21
No
35
Source side return temperature sensor
A
B91
Yes
(2)
44
Plant side return temperature sensor
A
B71
No
45
Source side flow temperature sensor
A
B92
Yes
(3)
106
Sorce side temperature too low
M
-
Yes
201
Plant side frost protection alarm
A
B21
Yes
222
High pressure during heat pump operating
A / M
E10
Yes
223
High pressure during heating circuit start
M
E10
Yes
224
High pressure during domestic hot water circuit start
M
E10
Yes
225
Low pressure
A / M
E9
Yes
228
Source side flow switch
A / M
E15
Yes
355
Phase sequence controller
A / M
E21 - E23
Yes
356
Plant side flow switch
A / M
E24
Yes
The controller diagnostic takes into account, besides the alarms reported in the table, many other alarm codes the meaning of
which is indicated on the unit display when the corresponding alarm becomes active. Such alarms are not critical and don’t lock
the heat pump operation.
Содержание HSW 11.1
Страница 47: ...47...