13
CX SERIES Installation, Operating & Maintenance Manual
INST
ALLER
Model
kW
Room
Volume (FT3)
Volts
Phase
Amps
Wire size (AWG)
for 25°C
1
44
6
3
25
8
1
38
8
3
22
10
480
3
11
14
1
58
4
3
34
8
1
50
6
3
29
8
480
3
14
12
1
73
4
3
42
8
1
63
4
3
37
8
480
3
19
10
1
97
1
3
56
4
1
84
3
3
48
6
480
3
24
8
1
116
1/0
3
67
4
1
100
1
3
58
6
480
3
29
8
1
145
3/0
3
84
2
1
125
2/0
3
73
3
480
3
36
8
208
3
112 (2X 56)
2X 4
240
3
96 (2X 48)
2X 6
480
3
48 (2X 24)
2X 8
208
3
134 (2X 67)
2X 4
240
3
116 (2X 58)
2X 6
480
3
58 (2X 29)
2X 8
208
3
168 (2X 84)
2X 2
240
3
146 (2X73)
2X 3
480
3
72 (2X 36)
2X 8
208
3
201 (3X 67)
3X 4
240
3
174 (3X 58)
3X 6
480
3
87 (3X 29)
3X 8
208
3
336 (4X 84)
4X 2
240
3
292 (4X73)
4X 3
480
3
144 (4X 36)
4X 8
2501 - 3000
3001 - 5000
CX0600
15
501 - 600
801 - 1000
1001 - 1250
1251 - 1600
1601 - 2000
2001 - 2500
30
CX0500
9
CX1250
208
240
208
240
208
240
208
240
208
240
208
240
Up to 360
361 - 500
601 - 800
CX0800
CX1000
CX0360
12
20
24
CX3000*
72 (3X 24)
CX5000*
120 (4X 30)
CX1600*
40
(2X 20)
CX2000*
48 (2X 24)
CX2500*
60 (2X 30)
Never use damaged
equipment, doing so may result in an
inoperative or hazardous installation.
All electrical wiring
installation to be performed by a
qualified licensed electrician in
accordance with National Electrical
Code and Local Electrical Code.
Connect electrical
power supply to the power block only.
Do not connect power supply directly
to elements. Connecting power
directly to the elements may result in a
dry fire and result in elevated
temperatures and a fire hazard.
For 208V units do
not apply more than 218V service.
Use minimum 90°
rated insulated copper conductors
only, sized in accordance with
National Electrical Code and Local
Electrical Code for the current in
Ampere Chart. If allowed by codes,
NM cable may require a larger wire
size than as listed on the chart.
Connect suitably
sized equipment grounding wire to
ground terminal provided. Neutral
(white) wire is not required for 208V
and 240V units.
Provide suitable
over-current protection (fuses or
circuit breaker).
Provide a power
supply disconnect within sight of
the steam generator or one that is
capable of being locked in the
open position as required by code.
Wire size (AWG) is
based on minimum 90° C rated
THHN copper conductors. Refer to
the National Electric Code for other
types of conductors.
Electrical Chart
* Models CX1600 - CX2500 are made of two discrete generators, model CX3000 is
made of three and model CX5000 CX5000 is made of 4 units
.