LEVEL 5 Voltage Threshold

Always leave the
Slide Switch OFF
while
reconfiguring.

Level 5 - Voltage Threshold is where you con-
figure  three  voltage  thresholds  used  by  the
load manager.

SAVE

Save LEVEL 5 - Voltage Threshold settings
and return to Level 5, Load Management, page
16.

CAUTION

The two sets of default voltage thresholds are
set at: 11.8 V, 12.8 V, and 13.8 V; and 11.0V,
11.8V, and 12.8V. DO NOT change the volt-
ages  if  not  necessary.  If  the  thresholds  are
changed, the initial defaults are lost and the
new settings replace the default values. The
system does NOT reset to the factory voltage
threshold  defaults  even  when  the  “Default
Configuration” is selected in Level 1 (see page
7).

Voltage Thresholds

Higher Voltage

The  higher  voltage  threshold  programming
can be performed only when key 15 is pressed
and the key 15 LED turns on. Press key 15 to
enable  higher  voltage  threshold  program-
ming.

To  perform  the  voltage  threshold  program-
ming, obtain an adjustable DC power supply
(2A min.) and a voltmeter. Use the power sup-
ply to power the system. Leave all switches
off and adjust the DC power supply output to
14  volts.  Enter  the  programming  mode,
LEVEL 5 - Voltage Threshold. Press key 15
to  enable  voltage  threshold  programming.
Adjust  the  DC  power  supply  output  to  the
High  Idle  off  voltage  (default:  13.8V)  and
press key 6. Adjust the DC power supply out-
put to the Load Shed Threshold  voltage (de-
fault: 12.8V) and press key 5. Adjust the DC
power  supply  output  to  the  Low  Voltage
Alarm Threshold voltage (default: 11.8V) and
press key 4.

The adjustable voltage threshold range is
11 - 15 volts.

The flow chart on page 19 illustrates how the
load manager works in conjunction with volt-
age thresholds.

Press key 9 to save after all voltage thresh-
olds are programmed and return to Level 5 -
Load Management, page 16

Lower Voltage

The  lower  voltage  threshold  programming
can be performed only when key 12 is pressed
and the key 12 LED turns on. Press key 12 to
enable lower voltage threshold programming.

To  perform  the  voltage  threshold  program-
ming, obtain an adjustable DC power supply
(2A min.) and a voltmeter. Use the power sup-
ply to power the system. Leave all switches
off and adjust the DC power supply output to
14  volts.  Enter  the  programming  mode,
LEVEL 5 - Voltage Threshold. Press key 15

to  enable  voltage  threshold  programming.
Adjust  the  DC  power  supply  output  to  the
High  Idle  off  voltage  (default:  12.8V)  and
press key 6. Adjust the DC power supply out-
put to the Load Shed Threshold  voltage (de-
fault: 11.8V) and press key 5. Adjust the DC
power  supply  output  to  the  Low  Voltage
Alarm Threshold voltage (default: 11.0V) and
press key 4.

The adjustable voltage threshold range is
11 - 15 volts.

The flow chart on page 19 illustrates how the
load manager works in conjunction with volt-
age thresholds.

Press key 9 to save after all voltage thresh-
olds are programmed and return to Level 5 -
Load Management, page 16

IMPORTANT

Voltage  thresholds  dramatically  affect  the
performance of the load manager. Changing
voltage thresholds from default settings is the
user’s responsibility.

Voltage  measurement  during  programming
voltage thresholds is critical. Voltage MUST
be  measured  at  pin  6  (red  wire)  and  pin  4
(black wire) of the unit’s power cable (see fig-
ure  3-6  in  the  supplied  Hardware  Installa-
tion and Maintenance Instructions). Improper
load manager operation will result if voltage
measurements, or settings, are incorrect.

It  is  strongly  recommended  that  only
trained, or experienced technicians, perform
the voltage threshold settings.

SmartSystem-LMS

SAVE

9

10

11

12

13

14

15

16

4

5

6

7

8

20

19

17

18

Low

Voltage

Alarm

Threshold

High

Idle

Off

Threshold

Load

Shed

Threshold

Enable Higher

Voltage

Threshold

Programming

Enable lower

Voltage

Threshold

Programming

290A4318-14

OFF

1

2

3

Содержание SmartSystem SS2000C31

Страница 1: ...OPERATION AND CONFIGURATION INSTRUCTIONS Model SS2000C31 SmartSystem Load Management System LOAD MANAGER WITH ELECTRONIC SIREN LIGHT CONTROL SYSTEM AND DIRECTIONAL LIGHT with Slide Switch Control Head...

Страница 2: ...h examination reveals a defect in material and or workmanship This warranty does not cover travel expenses the cost of specialized equipment for gaining access to the product or labor charges for remo...

Страница 3: ...g will do the same if it is transferred to the siren A H Will produceAir Horn tone any time it is pressed LRC O Directional light Arrow Step through Left Right Center Out Off WARN Directional light Wa...

Страница 4: ...ring process You will find that filling out the worksheet will help greatly reduce the time needed to configure your system to meet your requirements Once you have determined how your system should op...

Страница 5: ...ux Relay Push on Push off Momentary 8 Second Timer Security Timer LEVEL 3 Power Up Select which keys should automatically activate when first powered up LEVEL 4 Horn Ring Select Horn Ring Transfer Fun...

Страница 6: ...4...

Страница 7: ...less effective at warning others Maximum sound output will be severely re duced if any objects are in front of the speaker If your installation has obstructions in front of the speaker drive even more...

Страница 8: ...nd the configuration session and put the system into op eration mode LEVEL 1 Pressing LEVEL 1 Key 10 will enter LEVEL 1 Keyboard If LEVEL 1 is selected go to page 7 LEVEL 1 Keyboard LEVEL 2 Pressing L...

Страница 9: ...fore the siren tone will be produced Which slide switch will turn on the sirens is optional and will be dis cussed in Level 2 Slide Switch Function on page 10 Default Configuration If key 15 is on th...

Страница 10: ...Slide Switches is selected go to page 9 Level 2 Slide Switches Aux Relay Keys Pressing Aux Relay Keys Key 14 will enter LEVEL 2 Aux Relay Keys If Aux Relay Keys is selected go to page 11 Level 2 Aux...

Страница 11: ...gure Slide Switch 1 Slide 2 Press Slide 2 to reconfigure how Slide Switch position 2 functions If Slide 2 is selected go to Level 2 Slide Switch Function page 10 to reconfigure Slide Switch 2 Slide 3...

Страница 12: ...n be con figured to automatically turn on with the Slide Switches To do so turn on Key 15 Horn Ring Trans fer Siren Enable If sirens are configured to be depen dent on the slide switch this is where y...

Страница 13: ...ux Relay C Press Aux Relay C to reconfigure how Aux Relay C key 6 functions IfAux Relay C is selected go to Level 2 Aux Relays Function page 12 to reconfigure Aux Relay C Aux Relay D Press Aux Relay D...

Страница 14: ...t the Aux Relay you are con figuring to automatically turn itself off after 8 seconds Security Timer Select Security Timer Key 15 if you want the Aux Relay you are con figuring to require security ope...

Страница 15: ...s page 8 RAD WAIL YELP MAN A H Turn on the key to enable one of the above tones key Turn off the key to disable one of the above tones key H L or PRIORITY Key 14 can be configured to activate either t...

Страница 16: ...omatically when the system is powered up Remember only one siren or the RAD key can be selected at a time If no sirens or RAD is selected the system will power up in stand by Note If the sirens are co...

Страница 17: ...and you press the horn If the tone cannot transfer to a more urgent tone the Air Horn will mo mentarily sound Activate key 13 if you want YELP to be this tone Activate key 14 if you want PRIORITY No...

Страница 18: ...quence Press key 10 Load Shed Sequence to reconfigure how the load manager man ages relays It can be configured so that relay outputs are not managed Relays then opreate in a normal on off control mod...

Страница 19: ...nds or more If the High Idle Control is enabled High Idle will activate to remedy the low battery condition before load shedding begins Previously shed loads are NOT restored if the bat tery voltage r...

Страница 20: ...d Management page 16 Lower Voltage The lower voltage threshold programming can be performed only when key 12 is pressed and the key 12 LED turns on Press key 12 to enable lower voltage threshold progr...

Страница 21: ...on EXIT C1 C2 C3 Shed load according to the programmed sequence Volts 13 8V for 30 sec Volts 12 8V for 30 sec Volts 12 8V for 30 sec Turn High Idle Off NOTE 11 8V 12 8V AND 13 8V CAN BE PROGRAMMED TO...

Страница 22: ...ren Enable Circle the tones switches to be enabled RAD WAIL YELP H L or PRIORITY MAN A H Level 1 Sirens independent of slide switch Yes No Function Indicator Sound Yes No Directional light Type 6 Lamp...

Страница 23: ...mperes max Relay 2 20 amperes max Relay 3 40 amperes max Relay A 10 amperes max Relay B 10 amperes max Relay C 10 amperes max Relay D 10 amperes max Relay E 10 amperes max Is Horn Ring Transfer used Y...

Страница 24: ...Printed in U S A 255352A REV A 903...

Отзывы: