The amplifier output can be wired for Class A, Style Z or Class B, Style Y operation. Amplifier output should
use twisted, shielded wiring if being run in the same conduit or raceway as either an ALU or AEU signaling line
circuit. Use twisted, unshielded wire if the amplifier audio output is run in a separate conduit or raceway. It is
important to connect the shields of all entering and exiting wires at each electrical connection point, and to
ensure that these shields are not connected to earth ground. Shields must be terminated on each FCI-AAM-25
at TB1-1 or TB1-2. All amplifier output power is inherently power limited.
Designation
Description
Comments
TB1-1, -2
Shield termination point.
TB1-3
Audio Amplifier
Class B (+) field wiring, power limited. Connect to speakers
Output
AOMs and AAIs.
TB1-4
Class B ( - ) field wiring, power limited. Connect to speakers
AOMs and AAIs.
TB1-5
Class A (+) field wiring, power limited. Connect to speakers
AOMs and AAIs.
TB1-6
Class A ( - ) field wiring, power limited. Connect to speakers
AOMs and AAIs.
TB2-1
Standby Audio
Input (+), internal, power limited.
Input
TB2-2
Input ( - ), internal, power limited.
TB2-3
Output (+), internal, power limited.
TB2-4
Output ( - ), internal, power limited.
P1
5-position Header
Factory set with jumpers in positions 3 to 5 (left to right).
This is the setting for 25 VRMS operation. DO NOT REMOVE
LEDs
LED1
Green
Amplifier supervision.
LED2
Yellow
Speaker circuit trouble
Switch
S1
Back-up Mode
When a second FCI-AAM-25 is used for 100% backup
Enable
on the FCI-MB.
Table 2-5 Audio Amplifier Module (FCI-AAM-25)
CAUTION: Disconnect all sources of power before servicing, removing, or inserting any circuit boards.
Control unit and associated equipment may be damaged by removing and/or inserting cards, modules,
or interconnecting cables while the unit is energized.
!
34 of 61
9000-0405
Technical Manuals Online! - http://www.tech-man.com
Содержание FireVac 7200 Series
Страница 2: ...Technical Manuals Online http www tech man com...
Страница 9: ...SECTION ONE OVERVIEW 9000 0405 7 of 61 Technical Manuals Online http www tech man com...
Страница 10: ...8 of 61 9000 0405 Technical Manuals Online http www tech man com...
Страница 16: ...14 of 61 9000 0405 Technical Manuals Online http www tech man com...
Страница 59: ...SECTION THREE POWER UP TEST PROCEDURE 9000 0405 57 of 61 Technical Manuals Online http www tech man com...
Страница 60: ...58 of 61 9000 0405 Technical Manuals Online http www tech man com...
Страница 64: ...Technical Manuals Online http www tech man com...
Страница 65: ...Technical Manuals Online http www tech man com...