2.5.2 Power Supply Module & Transformer (FCI-PSM)
The Power Supply Module & Transformer (FCI-PSM) is equipped with a built-in battery charger that can
charge batteries up to 17-AH capacity. The remote-amplifier cabinet can house two 17-AH batteries. Primary AC
power is monitored by the FCI-PSM. The AC loss relay contacts change state and the “AC ON” LED
extinguishes upon loss of AC power or brown-out. Switch S1 is used to select immediate or 6 hour delay
of AC loss relay transfer.
The Model FVXFMR is used for 120 VAC input, while the Model FVXFMR 220 is used for 240 VAC input.
AC LOSS
RELAY
TB2
BATTERY
-
+
P2
P1
TB1
HOT NEU EARTH
J1
GRND
FAULT
BATT
TRBL
AC ON
1 2 3
120/240* VAC, 50/60 HZ, 1.0 A
MINIMUM WIRE SIZE 14 AWG (600 V INSULATION)
SUPERVISED
TRANSFORMER
CONNECTION
TRANSFORMER
TO POWER SUPPLY/BATTERY
CHARGER CONNECTOR P1
BATTERY CONNECTION
LEAD-ACID BATTERIES ONLY
MAX. CHARGING RATE: 0.8A @ 27.6 V
MAX. CHARGER CAPACITY: 17 AH BATTERY
SUPERVISED WIRING
AC LOSS/BROWNOUT TROUBLE CONTACTS
2A @ 30 VDC (RESISTIVE)
FOR CONNECTION TO A POWER-LIMITED, CLASS II OR
CLASS III SOURCE OF SUPPLY ONLY.
J1 CONNECTOR
(PLUGS INTO P7 CONNECTOR ON COMMAND BOARD)
REMOVE FACTORY-INSTALLED JUMPER FROM P7 CON-
NECTOR BEFORE PLUGGING IN POWER SUPPLY MODULE.
AC FAIL
DELAY ON
S1
AC FAIL DELAY SWITCH S1
(
MOVE TO RIGHT TO DELAY ACTIVATION OF
AC POWER FAIL RELAY FOR 6 HOURS)
YELLOW GROUND-FAULT LED
(LIGHTS IF GROUND FAULT)
YELLOW BATTERY-TROUBLE LED
(LIGHTS IF OPEN BATTERY CIRCUIT
OR LOW BATTERY)
GREEN AC POWER LED
(LIGHTS IF AC POWER IS PRESENT)
* USE FVXFMR-240 FOR 240 VAC APPLICATIONS
Figure 2-22 FCI-PSM and Transformer
40 of 61
9000-0405
Technical Manuals Online! - http://www.tech-man.com
Содержание FireVac 7200 Series
Страница 2: ...Technical Manuals Online http www tech man com...
Страница 9: ...SECTION ONE OVERVIEW 9000 0405 7 of 61 Technical Manuals Online http www tech man com...
Страница 10: ...8 of 61 9000 0405 Technical Manuals Online http www tech man com...
Страница 16: ...14 of 61 9000 0405 Technical Manuals Online http www tech man com...
Страница 59: ...SECTION THREE POWER UP TEST PROCEDURE 9000 0405 57 of 61 Technical Manuals Online http www tech man com...
Страница 60: ...58 of 61 9000 0405 Technical Manuals Online http www tech man com...
Страница 64: ...Technical Manuals Online http www tech man com...
Страница 65: ...Technical Manuals Online http www tech man com...