2.6.2 Push-to-Talk Receiver Module (PTT-R)
The PTT Receiver Module (PTT-R) receives the conditioned and amplified instructions generated at a remote
Command Center. A PTT-R is needed only when a microphone is installed in a remote Command Center.
The PTT-R is mounted in the main Command Center on the FCI-MB. One (1) PTT-R is required per system with
a maximum of five (5) PTT-Ds allowed.
A. PTT-R Addressing information
Switch SW1 (“ones" digit) and Switch SW2 (“tens” digit) can be addressed using addresses 00 - 99.
These addresses are interpreted by the Audio Evacuation Unit/Keyboard Display Unit (AEU/KDU) as addresses
100 -199 (identically to the AOM-2s). To set the address of an PTT-R module, refer to the following example.
A maximum of one PTT-R can be used per system
EXAMPLE:
For address 00, SW1 is set to “0" and Switch SW2 is set to ”0". (The AEU/KDU interprets switch address “00"
as ”100".)
1 2 3 4 5 6 7 8 9 101112
TB1
P5
ADDRESS SWITCH
TENS DIGIT
ADDRESS SWITCH
ONES DIGIT
5
9 8
7
6
4
0
1
23
5
9 8
7
6
4
0
1
2 3
CLASS A/B OUT (+)
CLASS A/B OUT (-)
CLASS A RETURN (+)
CLASS A RETURN (-)
SHIELD GROUND-WIRE CONNECTION
SHIELD GROUND-WIRE CONNECTION
NOT USED
NOT USED
IN (-)
OUT (+)
OUT (-)
IN (+)
REMOTE MICROPHONE
RISER TERMINALS
AEU SIGNALING LINE
CIRCUIT TERMINALS
Note:
PTT-R must be assigned as address 00
on AEU signaling line circuit.
Figure 2-26 Push-to-Talk Receiver, PTT-R
Designation Description
Comments
TB1-1
AEU-SLC
Input, positive (+), power limited, from backplane TB2-7.
TB1-2
See Fig. 2-1
Output, negative ( - ) power limited, out to additional devices.
TB1-3
for ratings
Output, positive (+), power limited, out to additional devices.
TB1-4
Input, negative ( - ), power limited, from Backplane TB2-6.
TB1-5, -6
Not used.
TB1-7, -8
Shield ground points.
TB1-9
Microphone
Input, negative ( - ), power limited, return from PTT-D TB1-4.
TB1-10
riser
Input, positive (+), power limited, return from PTT-D TB1-3.
TB1-11
See Fig. 2-25
Output, negative ( - ), power limited, to PTT-D TB1-2.
TB1-12
for ratings
Output, positive (+), power limited, to PTT-D TB1-1.
CONNECTOR
P5
Connects to P5 of the FCI-MB.
Table 2-9 PTT-R Field Wiring
9000-0405
45 of 61
Technical Manuals Online! - http://www.tech-man.com
Содержание FireVac 7200 Series
Страница 2: ...Technical Manuals Online http www tech man com...
Страница 9: ...SECTION ONE OVERVIEW 9000 0405 7 of 61 Technical Manuals Online http www tech man com...
Страница 10: ...8 of 61 9000 0405 Technical Manuals Online http www tech man com...
Страница 16: ...14 of 61 9000 0405 Technical Manuals Online http www tech man com...
Страница 59: ...SECTION THREE POWER UP TEST PROCEDURE 9000 0405 57 of 61 Technical Manuals Online http www tech man com...
Страница 60: ...58 of 61 9000 0405 Technical Manuals Online http www tech man com...
Страница 64: ...Technical Manuals Online http www tech man com...
Страница 65: ...Technical Manuals Online http www tech man com...