B. Class A, Wiring Instructions (alternate wiring methods using isolators, NFPA 72 Style 7)
Style 7 operation can be accomplished by isolating each addressable output device. The portion of the SLC
to be protected must also have a Fault Isolator Module (M-500X) at each end as shown in Figure 2-2.
NFPA 72 Style 7 wiring can only be accomplished by installing two M500X Fault Isolators close-nippled to
the single device being protected. These isolators are installed to protect the wires going to and coming from the
protected device.
•
Connect an electronic EOL device (consisting of an AMM-2 module, Address “99") (red and black wires)
to the AEU as shown in Figure 2-2. (Yellow and violet wires are not used.)
•
Be sure to observe polarity.
•
Maximum allowable field wiring resistance is 40 ohms per circuit. Use unshielded, twisted pair cable.
•
Maximum circuit capacitance is 0.5 uf.
•
Power limited, supervised
7
8
2
3
4
6
5
1
AEU TERMINALS
Note:
Wiring from AEU terminals 2 and 3
to last M500X Module shall be as
short as possible and run in rigid
conduit.
(+)
4
5
(-)
(-)
1
(-)
3
(+)
2
(+)
(-)
AOM-2(+)
8
7
9
6
(+)
4
(-)
1
(-)
3
(+)
2
M500X
(+)
4
(-)
1
(-)
3
(+)
2
M500X
(+)
4
(-)
1
(-)
3
(+)
2
M500X
(+)
4
5
(-)
(-)
1
(-)
3
(+)
2
(+)
(-)
AOM-2(+)
8
7
9
6
(+)
4
(-)
1
(-)
3
(+)
2
M500X
(+)
4
(-)
1
(-)
3
(+)
2
M500X
(+)
4
5
(-)
(-)
1
(-)
3
(+)
2
(+)
(-)
AOM-2(+)
8
7
9
6
2
1
7
6
5
3
4
8
AUDIO-SYSTEM BACK-PLANE
TERMINAL STRIP TB2
ISOLATOR MODULE
(OPTIONAL; STYLE 7 ONLY)
Note:
Wiring from backplane terminals 5 and 7 to
first M500X Module shall be as short as
possible and run in rigid conduit.
AOM-2 MODULE CONFIGURED
AS A SPEAKER CIRCUIT
NOTE:
ONLY M500Xs AND AOM-2s USED AS SPEAKER CIRCUITS SHOWN FOR SIMPLICITY. SLC CAN ACCOMMODATE MANY MORE MODULES SUCH AS AOM-2s
USED FOR EQUIPMENT INTERLOCKS. THE USE OF M500X MODULES IS OPTIONAL AND IS ONLY REQUIRED FOR CLASS-A, STYLE-7 CIRCUITS.
7
AMM-2
5
4
5
9
0
6
8
3
2
1
9
8
7
6
4
0
1
2
3
RED
EOL DEVICE
(AMM-2 WITH ADDRESS SET AT 99)
NOTE:
VIOLET & YELLOW WIRES NOT USED.
BLK
USE TWISTED, UNSHIELDED WIRE.
(40 OHMS, 0.5 MICROFARADS MAX.)
ASSIGN EACH AOM-2 A UNIQUE ADDRESS.
(+)
4
(-)
1
(-)
3
(+)
2
M500X
(+)
4
(-)
1
(-)
3
(+)
2
M500X
(+)
4
(-)
1
(-)
3
(+)
2
M500X
Figure 2-2
9000-0405
19 of 61
Technical Manuals Online! - http://www.tech-man.com
Содержание FireVac 7200 Series
Страница 2: ...Technical Manuals Online http www tech man com...
Страница 9: ...SECTION ONE OVERVIEW 9000 0405 7 of 61 Technical Manuals Online http www tech man com...
Страница 10: ...8 of 61 9000 0405 Technical Manuals Online http www tech man com...
Страница 16: ...14 of 61 9000 0405 Technical Manuals Online http www tech man com...
Страница 59: ...SECTION THREE POWER UP TEST PROCEDURE 9000 0405 57 of 61 Technical Manuals Online http www tech man com...
Страница 60: ...58 of 61 9000 0405 Technical Manuals Online http www tech man com...
Страница 64: ...Technical Manuals Online http www tech man com...
Страница 65: ...Technical Manuals Online http www tech man com...