The FCI-Motherboard (FCI-MB) contains connectors for either one or two 25-watt audio amplifier modules. The
amplifier assembly is supplied with one amplifier module mounted on the Command Board. The optional second
25-watt amplifier module can also be mounted on the FCI-MB for an additional 25 Watt output.
Primary amplifier operation is determined by the settings of DIP Switches S1 and S5 on the FCI-MB. DIP
Switch S1 selects the tone that the amplifier broadcasts, determines whether the tone is broadcast before and
after a recorded message, and sets the number of tone and/or message repetitions.
Figures 2-14 and 2-15 illustrate the settings for DIP Switches S1 and S5.
SWITCH 1:
ON -
TEMPORAL PATTERN PER ANSI S3.41 GENERATED (OVERRIDES TONE SELECTION OF SWITCHES 2 AND 3)
OFF-
TONE GENERATED AS SELECTED BY SWITCHES 2 AND 3
SWITCHES 2 AND 3:
USED TO DETERMINE WHAT TONE WILL BE BROADCASTED BY THE SPEAKERS BEFORE AND AFTER MESSAGE
IS BROADCAST. ALSO SELECTS BACK-UP TONE TO BE BROADCAST IF DIGITAL VOICE GENERATOR FAILS.
SWITCH
2
3
OFF OFF
OFF ON
ON OFF
ON ON
STEADY
HI - LO
SLOW WHOOP (FACTORY DEFAULT)
CHIME
SWITCH 4:
OFF -
NO TONE BEFORE MESSAGE
ON-
TONE BEFORE MESSAGE (FACTORY DEFAULT)
SWITCH 5:
OFF -
NO TONE AFTER MESSAGE
ON-
TONE AFTER MESSAGE (FACTORY DEFAULT)
SWITCHES 6, 7, & 8:
USED TO DETERMINE THE NUMBER OF TIMES THAT VOICE MESSAGE WILL REPEAT
SWITCH
6
7
8
OFF OFF OFF
TONE ONLY. NO VOICE*
3
4
6
ON OFF OFF
OFF ON OFF
ON ON OFF
OFF OFF ON
8
ON
ON
ON
CONTINUOUS (UNTIL SYSTEM IS RESET)
*
SOME JURISDICTIONS REQUIRE EVACUATION TONE ONLY. THIS OPTION PREVENTS VOICE
MESSAGE FROM BEING GENERATED.
TONE GENERATED
NO. OF MESSAGE REPETITIONS
AMPLIFIER MOTHER BOARD DIP SWITCH S1
"ON" (UP) "OFF" (DOWN)
Figure 2-14
SWITCH 1:
ON -
FACTORY DEFAULT
SWITCH 2:
DETERMINES WHICH MESSAGE WILL BE BROADCAST
ON:
AMP1 INPUT (CMD1) ACTIVATES BOTH SPKR CKTS AND BROADCASTS UP TO 30-SEC.
ALARM MESSAGE (I.E., FIRST RECORDED MESSAGE).
AMP2 INPUT (CMD2) ACTIVATES BOTH SPKR CKTS AND BROADCASTS UP TO 30-SEC.
SECONDARY MESSAGE (I.E., SECOND RECORDED MESSAGE)
NOTE:
MESSAGE #1 BROADCASTS IF BOTH CMD1 AND CMD2 ACTIVATED.
FACTORY DEFAULT SETTING
AMPLIFIER MOTHER BOARD DIP SWITCH S5
"ON" (UP) "OFF" (DOWN)
SWITCH 3:
OFF-
FACTORY DEFAULT SETTING
SWITCH 4:
ON-
REMOTE AMPLIFIER
OFF-
PRIMARY AMPLIFIER
SWITCH 5:
ON -
AMP1 ACTIVATED BY UNPOWERED, NORMALLY-OPEN CONTACT
OFF-
AMP1 ACTIVATED BY NAC POLARITY REVERSAL
SWITCH 6:
ON -
AMP2 ACTIVATED BY UNPOWERED, NORMALLY-OPEN CONTACT
OFF-
AMP2 ACTIVATED BY NAC POLARITY REVERSAL
SWITCH 7:
OFF-
FACTORY DEFAULT SETTING
SWITCH 8:
OFF-
FACTORY DEFAULT SETTING
Figure 2-15
32 of 61
9000-0405
Technical Manuals Online! - http://www.tech-man.com
Содержание FireVac 7200 Series
Страница 2: ...Technical Manuals Online http www tech man com...
Страница 9: ...SECTION ONE OVERVIEW 9000 0405 7 of 61 Technical Manuals Online http www tech man com...
Страница 10: ...8 of 61 9000 0405 Technical Manuals Online http www tech man com...
Страница 16: ...14 of 61 9000 0405 Technical Manuals Online http www tech man com...
Страница 59: ...SECTION THREE POWER UP TEST PROCEDURE 9000 0405 57 of 61 Technical Manuals Online http www tech man com...
Страница 60: ...58 of 61 9000 0405 Technical Manuals Online http www tech man com...
Страница 64: ...Technical Manuals Online http www tech man com...
Страница 65: ...Technical Manuals Online http www tech man com...