SECTION ONE: OVERVIEW
This section provides an overview of the FireVac
®
7200 system audio-specific components and related NFPA
standards.
1.1 Description
The FCI FireVac
®
7200 Audio Evacuation System is an integral part of the 7200 Series Fire Alarm Control. For
7200 Series system details and FireVac
®
7200 battery calculation information, see FCI manual
P/N 9000-0176.
•
Important audio evacuation capabilities supplied by the FireVac
®
7200 System include:
•
Voice/alarm signaling service in accordance with NFPA 72
•
Two-way telephone communications service in accordance with NFPA 72
•
Manually controllable process monitoring system
The FireVac®7200 System is a microprocessor-based, field configurable fire alarm control unit that operates
according to a user defined set of instructions. These instructions take the form of general alarm lists and input-
to-output relationships among alarm initiating points, notification appliance circuits, and control points such as
addressable output modules (AOM-2s). The general alarm lists and the input-to-output relationships are stored
in the system non-volatile memory and become the basis of its automatic operation. For a description of how to
create general alarm lists, input-to-output relationships and how to store these instructions in non-volatile mem-
ory, refer to FCI manual P/N 9000-0360, Field Configuration Program (FCP).
1.2 Configurations
The FireVac
®
7200 system can be configured in the following basic individual or combined systems:
•
A selective signaling single or dual channel fire alarm system.
•
A fire alarm system with general alarm voice evacuation signaling.
•
A fire alarm system with two way telephone communications.
•
A fire alarm system with manually controllable process monitoring.
NOTE: Dual Channel systems require a second amplifier.
1.2.1 A Selective Signaling Single or Dual Channel System
As a minimum, a single channel system notifies the occupants on the floor of fire origin to evacuate, while a
dual channel system notifies ALL building occupants of the fire emergency. The minimum components for this
system are:
•
Basic System Unit (BSU) with Switching Power Supply Unit (SPSU-V)
•
Audio Evacuation Unit, (AEU)
•
Command Center with backplane, one (1) CCU-S/D, one (1) SIM-S/D and microphone
•
Cabinet
•
Basic System Amplifier(s)
1.2.2 Fire Alarm System with General Voice Evacuation Signaling.
The minimum components of a Fire Alarm System with General Voice Evacuation Signaling are:
•
Basic System Unit (BSU) with Switching Power Supply Unit (SPSU-V)
•
Cabinet
•
Basic System Amplifier with microphone
1.2.3 Fire Alarm System with Two Way Telephone Communications
The minimum components of a Fire Alarm System with stand-alone telephone system are:
•
Basic System Unit (BSU) with Switching Power Supply Unit (SPSU-V)
•
Audio Evacuation Unit (AEU)
•
Command Center with one (1) TCU, one (1) CCU-S, one (1) SIM-P and handset
•
Cabinet
9000-0405
9 of 61
Technical Manuals Online! - http://www.tech-man.com
Содержание FireVac 7200 Series
Страница 2: ...Technical Manuals Online http www tech man com...
Страница 9: ...SECTION ONE OVERVIEW 9000 0405 7 of 61 Technical Manuals Online http www tech man com...
Страница 10: ...8 of 61 9000 0405 Technical Manuals Online http www tech man com...
Страница 16: ...14 of 61 9000 0405 Technical Manuals Online http www tech man com...
Страница 59: ...SECTION THREE POWER UP TEST PROCEDURE 9000 0405 57 of 61 Technical Manuals Online http www tech man com...
Страница 60: ...58 of 61 9000 0405 Technical Manuals Online http www tech man com...
Страница 64: ...Technical Manuals Online http www tech man com...
Страница 65: ...Technical Manuals Online http www tech man com...