Version 6
Operating instructions
CCS Silver
Firmware 2021-01-14
Page:
8
of:
72
FAUDI Aviation GmbH, Scharnhorststraße 7 B, D-35260 Stadtallendorf
Manual_CCS_silver_Eng_
operation_version6.docx
Terminal panel
Inscription
Connected Signal
SYSTEM
24V
Power Supply 24V DC
SYSTEM
GND
Power Supply GND
SYSTEM
PE
PE / GND (optional)
DIGITAL_INPUT
DI1
Interlock
DIGITAL_INPUT
DI2
SLUGGUARD
DIGITAL_INPUT
DI3
Override
CONTROL
RESET
Reset Switch
CONTROL
TRIGGER
Deadman/Trigger
ANALOG_1
mA
AFGUARD Inlet
ANALOG_2
mA
AFGUARD Outlet
ANALOG_3
mA
DP Transmitter
ANALOG_4
mA
Flow (analog) optional
PULSE_1
PULSE
Flow (pulsed) optional
PULSE_2
PULSE
Unused
PULSE_3
PULSE
Unused
PULSE_4
PULSE
Unused
DIGITAL OUTPUT
DO1
Blue LED Flashlight
DIGITAL OUTPUT
DO2
Optional Output, free programmable, 24V
DIGITAL OUTPUT
DO3
Optional Output, free programmable, 24V
DIGITAL OUTPUT
DO4
Optional Output, free programmable, 24V
REL_1
REL_1
ALARM Relay
REL_2
REL_2
WARN Relay
REL_3
REL_3
Optional Output, free programmable, Default: Ready
REL_4
REL_4
Optional Output, free programmable
ANALOG OUTPUT
AO1
Unused
ANALOG OUTPUT
AO2
Unused
ANALOG OUTPUT
AO3
Optional Output, free programmable, 4…20mA
ANALOG OUTPUT
AO4
Optional Output, free
programmable, 4…20mA
Please connect all signals according to the table. All sensor signals are optional.
2.1
AFGUARD® Inlet, Outlet
The main application of the CCS is to evaluate water levels measured by the AFGUARD® -
free water sensor. You can connect one or two AFGUARD®s to the CCS.
The
ANALOG_1
terminal is for the AFGUARD® in the
Inlet
of the vessel.
The
ANALOG_2
terminal is for the AFGUARD® in the
Outlet
.
The “mA”-Terminal is the path where the given current-signal flows in. For Ex-i Safety, a
barrier is needed. The barrier connects between AFGUARD® and CCS ANALOG_1 or
ANALOG_2 input. To power and ground the barrier and the sensor, you can use the “24V”,
“GND”, and “PE” connector of the terminal.