Version 6
Operating instructions
CCS Silver
Firmware 2021-01-14
Page:
66
of:
72
FAUDI Aviation GmbH, Scharnhorststraße 7 B, D-35260 Stadtallendorf
Manual_CCS_silver_Eng_
operation_version6.docx
Multiple Warnings cause Alarm
no
no
No. Of Warnings for Alarm
2
2
Activate Alarms
no
no
Level Alarm
50 ppm
50 ppm
On Delay Alarm
9 sec
9 sec
AFGUARD Outlet
Available
yes
Check assembly
Measure range (20mA)
50 ppm
50 ppm
Signal Attenuation time
1 sec
1 sec
Activate Warnings
yes
yes
Limit Warning
15 ppm
15 ppm
On Delay Warning
9 sec
9 sec
Multiple Warnings cause Alarm
yes
yes
No. Of Warnings for Alarm
2
2
Activate Alarms
yes
yes
Level Alarm
30 ppm
30 ppm
On Delay Alarm
9 sec
9 sec
Level Water Slug
50 ppm
50 ppm
On Delay Water Slug
4 sec
4 sec
SLUGGUARD
Available
yes
Check assembly
Invert Signal
yes
yes
On Delay
5 sec
5 sec
Off Delay
1 sec
1 sec
Filter Parameter
Enable Overflow Alarm
yes
yes
Rated Flow
5000 l/min
Check Filter documentation
Enable Over DP Alarm
yes
yes
DP Changeout
2.0 bar
Check Filter documentation
Datalogger
Logger Interval
2 sec
2 sec
Interlock Signal Available
no
Check assembly
On Delay
5 sec
Off Delay
5 sec
End Refuelling Process after
0 sec
0 sec
Ignore missing USB Drive /
Battery Error
no
no