Version 6
Operating instructions
CCS Silver
Firmware 2021-01-14
Page:
36
of:
72
FAUDI Aviation GmbH, Scharnhorststraße 7 B, D-35260 Stadtallendorf
Manual_CCS_silver_Eng_
operation_version6.docx
3.2.4.3.8 Water Monitoring setup
This menu has been removed from the installer to since firmware 2020-08-28 to simplify the
configuration process.
The water monitoring gets automatically started when one of the following conditions fulfilled:
-
Trigger signal pressed
or
-
Flow greater than the specified value (default: 50l/min)
or
-
Differential pressure greater than the specified value (default: 0.05bar)
So at least one of the three signals must be connected to the system.
If you have issues due water monitoring or need different values, do not hesitate to contact
FAUDI Aviation.
3.2.4.3.9 Filter Parameter
This page is optional and will be skipped if in the last steps of the installer the sensor types of
Flow Meter and Differential Pressure sen
sor were set to “N/A”.
3.2.4.3.9.1 Rated Flow
This input box disappears if no Flowmeter is installed (Flow Rate Sensor type “N/A”).
Please input the rated flow of your filter vessel or enter the max. achievable (max.
necessary) Flow of your refuelling process here. The effect of this value is, to release the
alarm relay immediately when the flow is higher than the set limit. The blue lamp will switch
off and a reset will be required.
3.2.4.3.9.2 Max. Differential Pressure
This input box disappears if no DP sensor is installe
d (DP Sensor type “N/A”).
Please input the max allowed differential pressure of your refuelling process here. The effect
of this value is, to release the alarm relay immediately when the measured DP is higher than
the entered value. The blue lamp will switch off and a reset will be required.
Click Next >> to continue.
3.2.4.3.10 Interlock Settings
This menu has been removed from the installer to since firmware 2020-08-28 to simplify the
configuration process. it is integrated into “Logger settings” (The next page in the installer).