H5 -2
Note
The schematic diagram of AC power supply wiring in main/expansion units is shown below. Also be cautious
about the following:
Please follow the wiring schemes regulated by local national standards to use single-pole switch
(
break hot wire
〝
L
〞
)
, or double-pole switch
(
break both
〝
L
〞
and
〝
N
〞
)
, to turn on or off the AC input power.
In wiring, hot wire
〝
L
〞
must be connected to the L terminal on unit, while the ground line
〝
N
〞
connected to the
N terminal. Please use wires with diameters 1mm
2
~
2mm
2
.
All G terminals on main unit and expansion unit/module have to be connected to the EG (Earth Ground)
terminal of main power system as shown in the figure below, with wire diameters larger than 2mm
2
.
(FB
S
- E )
24VDC
external power
Expansion module
100-240VAC
main power
L
N
EG
Output
Main unit
(FB
S
- M )
SW
Input
CPU
0V
5V
24V
0V
AC-DC
Power
Supply
F
24V
OUT
POW-24
OR
24VDC output
(for input)
(FB
S
-6AD, 2DA,
TC6,RTD6...)
24VDC
external power
Expansion module
Expansion unit
Output
Output
(FB
S
- EAP)
POW-24
control
Input
F
24V
0V
0V
24V
5V
control
OUT
Input
AI
Expansion
power supply
(FB
S
-EPOW)
5V
F
0V
24V
24V
1V
0V
OUT
control
OR
IN
CONVERTER
(DC-DC)
AC-DC
Power
Supply
AC-DC
Power
Supply
24VDC output
(for input)
input /
Sensor
input /
Sensor
input /
Sensor
24VDC output
(for input)
5.2
Specifications of DC Power Sourced Power Supply and Wiring
The available DC power sourced power supplies of FB
S
-PLC are the 10 Watt (POW-10-D) supply for 10/14PTs main
unit, the 16 Watt (POW-16-D) supply for 20~60PTs main/expansion unit, and the 10 Watt expansion supply
(FB
S
-EPOW-D) for expansion modules. The out power of DC source power supply is smaller than its AC counterpart
because the power generated by the former only need to provide power to the 5VDC logic circuit and the 24VDC
output circuit, while the power of 24VDC input circuit is derived directly by the 24VDC input power source through filter
circuit. Besides the FB
S
-EPOW is an independent module, POW-14 and POW-24 are to be installed on a main unit or
inside an expansion unit, where their appearances are invisible. The following table lists the specifications:
Warning
Output of power for sensor cannot be connected in parallel with other powers, in which the conflict between two
sets of power will decrease their lifetime or cause immediate damage. This will induce unexpected malfunction of
PLC and cause serious or even deadly damage to people or equipment.