H3 -2
main unit. Users can easily find each terminal with its I/O number and LED status indication, as shown in the figure
below using X10 and Y6 as an example:
OUT
Y
(
)
Y6
Y1
AC100~240V
C0
Y0
Y4
Y2
C2
Y3
PORT0
Y5
C4
C6
Y8
Y7
Y9
SINK
SRCE
(
)
IN
X
X8
X0
PROGRAMMABLE
CONTROLLER
24V OUT
S/S
RX
TX
RUN
ERR
POW
X4
X2
X1
X3
X6
X5
X7
X12
X10
X9
X11
X13
X10
Y6
max.
400mA
IN
0
I
2 3
7
6
5
4
I0 I I
9
8
I3
I2
0
4
8
9
5 6
2
I
3
7
While the various expansion units/modules other than the main units have the same printed labels on the input/output
terminals as the main units do, these labels are only relative I/O numbers, different from the absolute I/O numbers on
main units. The number of a terminal only represents its order on the expansion unit/module. For example, the first
contact is X1 or Y1, the second X2 or Y2, etc. All numbers on the expansion unit/module begin with 1. The actual
number of digital input contact or the output replay, however, is determined by summing the numbers on all previous
expansion units/modules and the main unit. See the following figure and its calculation.
X0
X23
X24
X37
X38
X61
X49
Y0
Y15
Y16
Y25
Y26
Y41
FB
S
-40M
△
FB
S
-24EA
FB
S
-40EAP
(
主機
)
(
第1個擴充機/模組
)
(
第2個擴充機/模組
)
Y0 Y1
• • • • • • • • • • • •
Y15
X0 X1
• • • • • • • • • • • • • •
X23
X1 X2
• • • • • • • •
X14
Y1 Y2
• • • • • • • •
Y10
X1 X2
• • • • • •
X12
• • • • • •
X24
Y1 Y2
• • • • • • • • • • • •
Y16
As shown in the above figure, because the top X numbers of the previous two units are 23 and 14, respectively, the
number of input contact X12 on second expansion unit should be:
X
(23
+
14
+
12)
=
X49
Main Unit
1
st
expansion
unit/module
2
nd
expansion
unit/module