Application guidelines
22
FRCC.PC.002.A5.22
Installation and service
Compressor mounting
Compressor handling
Compressor handling,
mounting and connection
System cleanliness
The compressor must be mounted onto a
horizontal surface with a maximum slope of
3 degrees. Always use the rubber mounting
grommets that are shipped with the compressor.
Mounting torques are listed in the below table.
Maneurop® NTZ compressors must be handled
with care and all handling procedures must
be performed smoothly and gently. Each NTZ
has been fitted with one lift ring which shall
always be used to lift the compressor. Once the
compressor is installed, the lift ring shall never be
used to lift the complete installation.
Always use the proper tools for transporting the
compressor. Keep the compressor in an upright
position during all handling tasks (manipulating,
transport, storage). The angle off the vertical
must not exceed 15 degrees.
System contamination is one of the main factors
that affects equipment reliability and compressor
service life. Therefore it is important to take care
of the system cleanliness when assembling a
refrigeration system. During the manufacturing
process, circuit contamination can be caused by:
• Brazing and welding oxides,
• Filings and particles from removing burrs from
pipe-work,
• Brazing flux,
• Moisture and air.
Only use clean and dehydrated, refrigeration-
grade copper tubes and silver alloy brazing
material. Clean all parts before brazing and
always purge nitrogen or CO
2
through the
pipes during brazing to prevent oxidation. If
flux is used, take every precaution to prevent
the leakage of flux into the piping. The use
of flux core or flux coated braze wire or rod
instead of brush applied paste flux is strongly
recommended. Do not drill holes (e.g. for
schrader valves) in parts of the installation
that are already completed, when filings and
burrs cannot be removed. Carefully follow the
instructions below regarding brazing, mounting,
leak detection, pressure test and moisture
removal. All installation and service work shall
only be done by qualified personnel respecting
all procedures and using tools (charging systems,
tubes, vacuum pumps, etc.) dedicated for R404A
and R507.
Component
Torque (lbf.in)
Min.
Max.
Rotolock suction valve, NTZ048 - NTZ068
710
885
Rotolock suction valve, NTZ096 - NTZ271
885
1060
Rotolock discharge valve, NTZ048 – NTZ068
620
795
Rotolock discharge valve, NTZ096 - NTZ271
710
885
Electrical T-block screws HN°10-32 UNF x 9.5
-
27
Earth screw
-
27
Oil sight glass (with black chloroprene gasket)
355
400
3/8" flare oil equalisation nut
400
440
Schrader nut
100
150
Schrader valve (internal)
3.5
7
Mounting grommet bolt, NTZ048 – NTZ271
105
160
Belt crankcase heater
-
35
Содержание Danfoss Maneurop MT
Страница 2: ......
Страница 3: ......
Страница 39: ......
Страница 42: ......
Страница 43: ......
Страница 65: ......
Страница 66: ......
Страница 67: ......
Страница 103: ......
Страница 105: ...Maneurop reciprocating compressors NTZ R404A R507 60 Hz Application guidelines http danfoss us com...
Страница 106: ......
Страница 138: ......
Страница 139: ......
Страница 192: ......
Страница 193: ......
Страница 196: ......
Страница 239: ...Danfoss scroll compressors SM SY SZ R22 R407C R134a R404A R507A 50 60 Hz Application guidelines http cc danfoss com...
Страница 240: ......