FRCC.PC.015.A5.02
19
Application Guidelines
CSR wiring provides additional motor torque
at start-up, by the use of a start capacitor in
combination with the run capacitor. The start
capacitor is only connected during the starting
operation, a potential relay is used to disconnect
it after the start sequence.
Some applications with high differential pressure
and start duty as "soft serve ice cream machine"
can require CSR wiring. This configuration
can also be used to reduce erratic starting
at unfavourable conditions such as very low
ambient temperature or weak voltage.
remains at high temperature and thus at high
resistance as long as power is connected to the
compressor. When the compressor is switched
off, the PTC cools down to its initial low resistance
and becomes available to support the next
compressor start.
It is important to provide sufficient time between
motor starts to allow the PTC to cool down
close to ambient temperature. Depending on
the ambient conditions and the cooling of the
PTC, this may take about 5 minutes. A restart
before the PTC is back to low resistance may be
successful or the motor may stall in a locked-rotor
state depending on the ambient and system’s
conditions. A locked-rotor state causes the
internal protector to open and would cause even
further delay until the overload is reset.
The following PTC types are recommended for
the MLZ/MLM single phase compressors:
CSR wiring
Nominal capacitor value
and relays
Electrical data, connections and wiring
Model
Voltage code 1
208-230 V/1~/60 Hz
Voltage code 5
220-240 V/1~/50 Hz
MLZ/MLM015
305C12*
305C9* / 305C11*
MLZ/MLM019
305C9* / 305C11*
305C9* / 305C11*
MLZ/MLM021
305C9* / 305C11*
305C9* / 305C11*
MLZ/MLM026
305C12*
305C9* / 305C11*
MLZ/MLM030
305C9* / 305C11*
305C9* / 305C11*
MLZ/MLM038
305C9* / 305C11*
305C9* / 305C11*
MLZ/MLM042
305C9* / 305C11*
305C9* / 305C11*
Note: MLZ compressors with PTCSCR are not approved by UL. It is the customers’ responsibility to get final approval for the
system when required.
Compressor models
Default solution: PSC wiring
with run capacitor only
Additionnal components for CSR wiring
PSC wiring
CSR wiring
Run capacitor
Start capacitor
Relay
µF
Volt
µF
Volt
Reference
220-240 V /1/50 Hz
Motor voltage code 5
MLZ/MLM015
40
370
145-175
330
3ARR3J3AL4
RVA9CKL
MLZ/MLM019-021-026
70
370
145-175
330
3ARR3J3AL4
RVA9CKL
MLZ/MLM030
50
440
161-193
250
3ARR3J24AP4
RVA3EKL
MLZ/MLM038-042
55
440
88-108
330
3ARR3J25AS4
RVA4GKL
For information
208-230 V / 1 / 60 Hz
Motor voltage code 1
not provided with the
compressor
MLZ/MLM015
45
370
145-175
330
3AAR3*3M*
-
MLZ/MLM019-021
45
370
145-175
250
3AAR3*3M*
-
MLZ/MLM026
60
370
88-108
330
3ARR3*3L*
-
MLZ/MLM030
70
370
161-193
250
3ARR3*3L*
-
MLZ/MLM038
55
440
88-108
250
3ARR3*25S*
-
MLZ/MLM042
80
370
189-227
330
3ARR3*3L
-
N
L₁
Run capacitor
PTC
Thermostat
C
S
R
IOL
N
L₁
Thermostat
Start capacitor
Start Relay
5
2
1
15 kΩ -1 w
C
S
R
Run capacitor
Содержание Danfoss Maneurop MT
Страница 2: ......
Страница 3: ......
Страница 39: ......
Страница 42: ......
Страница 43: ......
Страница 65: ......
Страница 66: ......
Страница 67: ......
Страница 103: ......
Страница 105: ...Maneurop reciprocating compressors NTZ R404A R507 60 Hz Application guidelines http danfoss us com...
Страница 106: ......
Страница 138: ......
Страница 139: ......
Страница 192: ......
Страница 193: ......
Страница 196: ......
Страница 239: ...Danfoss scroll compressors SM SY SZ R22 R407C R134a R404A R507A 50 60 Hz Application guidelines http cc danfoss com...
Страница 240: ......