Measure to verify the correct voltage between the pins.
2.
Connect the cable to the DC converter input.
3.
Connect the DC converter to the lift phone outlet marked ”DC”.
4.
Connect the DC converter on the outside of the lift and fasten the cable with cable ties
or cable clips.
Connection to loop amplifier
To enable passengers with impaired hearing to communicate with the alarm centre a loop
amplifier can be connected to the ECII™ Flex. Contact your local distributor for information
about approved loop amplifiers that can be used with ECII™ Flex.
Connect the output marked “LOOP AMP” to the loop amplifier. The loop amplifier must work
during power failure. Connect it to a power supply that is known to work during power failure.
Connection of external pictogram
It is possible to connect external lamps to indicate alarm status on the lift phone according to
EN81:70 using the system component Pictogram Driver. It consists of a DC-converter and drive
circuits for external lamps. It is connected to the output marked “DC”, to 12V emergency power
and to the external lamps. Contact your distributor for more information.
Connection to Intercom (art. 102153-01)
For communication between the machine room and the ECII™ Flex use the ECII Intercom Unit
(art. 102153-01). Mount the Intercom Unit in the machine room and connect the power and
telephone line. Connect the ECII™ Flex in the lift car to the LIFT CAR output on the Intercom
Unit. Please view the Intercom installation instruction for more information.
Connection to additional Alarm buttons ALBU (art.
102142 and 252142)
For additional alarm buttons on top and below the lift car use the Technician alarm button (art.
102142). Mount the ALBU on an appropriate location and connect it to the “ALARM 2” input on
the ECII™ Flex. If using two Alarm Buttons they need to be connected in series; the Alarm
Buttons are always Normally Closed.
To activate the “ALARM 2” input for the Alarm Button, program:
Connection to Speaker Unit (art. 142230)
For additional microphone and speaker on top and below the lift car use the FältCom Flex
Speaker Unit (art. 142230). Mount the Speaker Unit on an appropriate location and connect it
to the ECII™ Flex AUX input using the Cat5 cable, use the IN connector on the Speaker Unit.
Please note that the cable must be ordered separately depending on the required length of the
cable. The alarm input on the ECII™ Flex is activate by default.
If using two Speaker Units; connect the second Cat5 cable from the OUT connector of Speaker
Unit 1 to the IN connector on Speaker Unit 2.
To speak to the Speaker Unit first call in to the ECII™ Flex and establish a duplex conversation.
Then press key ‘3’ to activate the sound in the Speaker Unit, press ‘3’ again to switch the sound
back to the ECII™ Flex.