PNU Name
Description
Options
Words Type Units Detail
69
Limit Amps The current in Amps at which the soft Start
ramp is held.
Normally set to 350% of motor FLC.
Increase if motor fails to accelerate at
required rate
The "Limit Amps" will affect actual time to
start.
If set too low the motor may not accelerate
to full speed.
2
R/W A
Multiplier: 1
Divisor:1000
Offset: 0
Min: 0.5 x
PNU18
Max: 5 x
PNU20
Default: 3.5 x
PNU20
71
Limit Time The maximum time allowed for the current
limit.
If the current limit is still active at the end of
this period the Unit will either 'Trip' or
'continue'
1
R/W s
Multiplier: 1
Divisor:1
Offset: 0
Min: 1
Max: 60
Default: 30
72
Boot Ver
Software Version for the Bootloader
2
R
Multiplier: 1
Divisor:1
Offset: 0
Min: 0
Max: 65535
Default: 0
74
Cntrl Funct Allows the Digital inputs to be mapped to
different functions
Cntrl Mode must be set to "Remote"
Two Wire: D1 = Start (Reset) / Stop
Three Wire: D1 = Start (Reset) D2 = Stop
D2 Reset , D2 Hold , D2 Enable , D2 Fire :
D1= Start /Stop, D2 programmed as shown
0=Three Wire,
1=Two Wire,
2=D2 Reset,
3=D2 Hold,
4=D2 Enable,
5=D2 Fire.
1
R/W
Multiplier: 1
Divisor:1
Offset: 0
Min: 0
Max: 5
Default: 0