16
agility
TM
Series Soft Start User Manual
MAN-AGY-001. Version 04. 21/09/2018
Electromagnetic Compatibility
EMC Emission levels
EN 55011
Class A
EMC Immunity levels
IEC 61000-4-2
8kV/air discharge or 4kV/contact discharge
IEC 61000-4-3
10 V/m
IEC 61000-4-4
2kV/5kHz (main and power ports)
1kV/5kHz (signal ports)
IEC 61000-4-5
2kV line-to-ground
1kV line-to-line
IEC 61000-4-6
10V
NOTICE: This product has been designed for environment A. Use of this product in environment
B may cause unwanted electromagnetic disturbances, in which case the user may be required to
take adequate mitigation measures
Wire Sizes and Torques
Terminal
Wire Size
Torque
mm
2
AWG
Nm
Ib-in
Main terminals Cu STR 75
o
C only
2.5 - 70
12- 2/0
9
80
Control terminals
0.5
–
1.5
20-16
0.8
7.0
M6 screw
Protective
Earth
1)
Cu
only
≥ 10
≥
8
8
70
1)
Protective Earth wire size based on bonding conductor requirements of UL508 Table 6.4 and UL508A
Table 15.1.
Electrical Installation (continued)