14
agility
TM
Series Soft Start User Manual
MAN-AGY-001. Version 04. 21/09/2018
Rating Table
–
Vertical Mounting
I
e
kW
1)
FLA
Hp
2)
Trip Class 10 Trip Class
20
Trip Class 30
A
3)
230V 400V 500V
4)
A
3)
200V 208V 220-240V 440-480V 550-600V
4)
I
e
: AC-53a:
3.5-17: 90-5
5)
I
e
: AC-53a:
4-19: 90-5
5)
I
e
: AC-53a:
4-29: 90-5
5)
17
4
7.5
7.5
17
3
5
5
10
15
-
-
AGY-101
17
4
7.5
7.5
17
3
5
5
10
15
-
AGY-101
AGY-103
17
4
7.5
7.5
17
3
5
5
10
15
AGY-101
AGY-103
AGY-105
22
5.5
11
11
22
5
5
7.5
15
20
AGY-103
AGY-105
AGY-107
29
7.5
15
15
27 7.5
7.5
7.5
20
25
AGY-105
AGY-107
AGY-109
35
7.5 18.5
22
34
10
10
10
25
30
AGY-107
AGY-109
AGY-111
41
11
22
22
41
10
10
10
30
40
AGY-109
AGY-111
AGY-113
55
15
30
37
52
15
15
15
40
50
AGY-111
AGY-113
-
66 18.5
37
45
65
20
20
20
50
60
AGY-113
-
-
Rating Table
–
Horizontal Mounting
I
e
kW
1)
FLA
Hp
2)
Trip Class 10 Trip Class
20
Trip Class 30
A
3)
230V 400V 500V
4)
A
3)
200V 208V 220-240V 440-480V 550-600V
4)
I
e
: AC-53a:
3.5-17: 90-5
5)
I
e
: AC-53a:
4-19: 90-5
5)
I
e
: AC-53a:
4-29: 90-5
5)
17
4
7.5
7.5
17
3
5
5
10
15
-
AGY-101
AGY-103
17
4
7.5
7.5
17
3
5
5
10
15
AGY-101
AGY-103
AGY-105
17
4
7.5
7.5
17
3
5
5
10
15
AGY-103
AGY-105
AGY-107
22
5.5
11
11
22
5
5
7.5
15
20
AGY-105
AGY-107
AGY-109
29
7.5
15
15
27 7.5
7.5
7.5
20
25
AGY-107
AGY-109
AGY-111
35
7.5 18.5
22
34
10
10
10
25
30
AGY-109
AGY-111
AGY-113
41
11
22
22
41
10
10
10
30
40
AGY-111
AGY-113
55
15
30
37
52
15
15
15
40
50
AGY-113
-
Minimum current ratings based on typical rated operation currents of motors for the
corresponding rated operational powers.
Current rating optimised for kW@400V & hp@440-480V - Ref IEC 60947-4-1:2009 Table G.1 where
applicable.
1)
Rated operational powers in kW as per IEC 60072-1 (primary series) corresponding to IEC current
rating.
2)
Rated operational powers in HP as per UL508 corresponding to FLA current rating.
3)
The I
e
and FLA rating applies for a maximum surrounding air temperature of 40
o
C. Above 40
o
C de-rate
linearly by 2% of Ie or FLA per
o
C to a maximum of 60
o
C.
4)
kW and HP ratings applicable for AGY-101-6 to AGY-113-6 models only.
5)
A duty cycle F-S of up to 90-40 (up to 40 starts per hour) is possible with optional fan fitted
Electrical Installation (continued)