         732642 - Rev. F

 6 

START-UP

6.1 

 LEDS CHECK

Check the status of the inputs, from the LEDs on the board (Tab.1).
Tab. 1: input LED status 
(the condition of closed automation in standby is provided in 
bold)

LED STATUSES

LED

ACTIVE CONTROL

NOT ACTIVE CONTROL

STOP

Off

On

OPEN A

On

Off

OPEN B

On

Off

BUS

See paragraph 7.2

6.2 

PROGRAMMING THE DIP-SWITCHES

The settings of the DS1 dip-switch for programming the force 
and the type of motor are shown in the following table.

Tab. 2 - DS programming 

 (default settings in bold)

 Before performing the Setup, select the op-

erator connected to the E024S unit with the 

DS1(DS3-DS4) DIP switches.

6.3.1  AUTOMATIC SETUP

To enter the Automatic setup, press the SETUP push-button until 
the two LD4 and LD5 LEDs are permanently lit. Then release 
the SETUP push-button. 
During the Setup phase both LEDs flash.
The leaves start to open one at a time, from any position, 
till they detect the opening limit stop. Next, the leaves start 
to close, one at a time, till they detect the closing limit stop.
Then, the leaves start again to move automatically one at a 
time from the closed position.
1.  When the leaves detect the opening limit stop, they stop in 

the open position and the set-up is completed.     

 

If the SETUP procedure is performed correctly , the LD4 and 
LD5 LEDs turn off at the end. Otherwise the procedure ends 
by asking a new SETUP with flashing LEDs.    

          

 With the AUTOMATIC SETUP, the deceleration 

spaces, the leaf closing delays and the pause 

time (30 s, with logic A) are automatically 

preset during setup. 

 6.3.2 MANUAL SETUP

To enter the Manual setup, press the SETUP push-button until 
both LD4 , press the SETUP push-button until the two LD4 and LD5 
LEDs are permanently lit. Keep it pressed until the automated 
system starts moving automatically.
During the Setup phase both LEDs flash.

The leaves start to open one at a time, from any position till they 
detect the opening limit stop. Next the leaves start to close one 
at a time till they detect the closing limit stop.
Then the leaves start again to move automatically one at a 
time from the closed position.
  1.  Open impulse --->leaf 1 decelerated opening and start of 

 

      the search for leaf 1 opening limit stop

  

-

   if the limit stop is detected, it is set as stop point for leaf 1 

 

      and leaf 2 starts to open.
 (*) if an open command is detected, it is set as opening
      stop point for leaf 1 and leaf 2 starts to open. 
  2. Open impulse ---> leaf 2 decelerated opening and start 
      of the search for leaf 2 opening limit stop.    

   

-

  if the limit stop is detected, it is set as opening stop point 

      for leaf 2.

 

(*)

 if an open command is detected, it is set as opening stop

 

      point for leaf 2.

DS4

DS3 DS2 DS1

Description

OFF

OFF

MOTOR 391

ON

OFF

MOTOR 418

OFF

ON

MOTOR 412-413-415-390-770

ON

ON

HYDRAULIC MOTOR (*) 

S450H/S700H/S800H/S800H ENC

OFF OFF

LOW FORCE

ON OFF

MEDIUM - LOW FORCE

OFF ON

MEDIUM - HIGH FORCE

ON

ON

HIGH FORCE  

6.3 

TIME LEARNING – SETUP

 Before any manoeuvre is executed, a SETUP cycle 

must first be run.

 If the motor type is changed with the DS3 and 

DS4 dip-switches after the SETUP, a new SETUP is 
requested with flashing LD4 and LD5 LEDs.

 

If, after the start of the SETUP procedure, the 
leaves close instead of open, reverse the motor 
power cables

(*) with the DS3-DS4 selection on ON the opera-
tor connected to the encoder is automatically 
recognized during the set-up phase

Important:
The dip-switch arrangement on the E024S board 
for 391 is overturned.

When the board is powered up and a SETUP cycle has 
never been executed, LEDs LD4 and LD5 begin to flash 
slowly to signal that a SETUP cycle must be executed.
There are two possible types of SETUP: 
- AUTOMATIC SETUP 
- MANUAL SETUP

(*) During SETUP, to set the stop point, the OPEN 
command must ONLY be used with SAFECODER

ENGLISH

Содержание E024S

Страница 1: ...E024S...

Страница 2: ...ETUPS MUSS MIT DEN DIP SWITCHES DS1 DS3 DS4 DER AN DIE ANLAGE E024S ANGESCHLOSSENE ANTRIEB ANGEW HLT WERDEN ANLEITUNGEN BER ALLE ANDEREN EINSTELLUNGEN SIND DER BETRIEBSANLEITUNG E024S ZU ENTNEHMEN ATE...

Страница 3: ...Bologna 10 11 2014 CEO A Marcellan INDEX BOX LAYOUT 4 1 WARNINGS E024S 5 2 LAYOUT AND CONNECTIONS E024S 5 1 WARNINGS E024S FITTED ON 391 6 2 LAYOUT AND CONNECTIONS E024S FITTED ON 391 6 3 TECHNICAL SP...

Страница 4: ...e box are shown in Fig A The cover hinges can be moved upward to allow opening the box housing Fig C they can also be removed and re posi tioned in order to enable the cover to open to the right or le...

Страница 5: ...rate power cables from control and safety cables push button receiver photocells etc To avoid any electrical disturbance use separate sheaths or a shielded cable with the shield earthed CONTROL UNIT E...

Страница 6: ...wer cables from control and safety cables push button receiver photocells etc To avoid any electrical disturbance use separate sheaths or a shielded cable with the shield earthed CONTROL UNIT E024S fi...

Страница 7: ...o shut down 4 OPEN B Device with N O contact 5 OPEN A J10 RED terminal BUS Safety devices with BUS technology J2 GREY terminal SERVICE LIGHT on for 90 sec following movement Service Light control outp...

Страница 8: ...utomatically During the Setup phase both LEDs flash The leaves start to open one at a time from any position till they detect the opening limit stop Next the leaves start to close one at a time till t...

Страница 9: ...t stop is detected it is set as leaf 1 closing stop point if an open command is detected it is set as leaf 1 closing stop point If the SETUP procedure is performed correctly the LD4 and LD5 LEDs turn...

Страница 10: ...push button is released both LD4 and LD5 LEDs flash 6 The default configuration is reset and the new Setup can be started Fig 2 6 3 6 PARAMETER DEFINITION Anti wind the anti wind function enables the...

Страница 11: ...memory store total opening OPEN A or partial opening OPEN B and by holding it down press the push button SETUP SW1 6 The LED on the board lights up on steady beam for 1 second and then goes OFF indic...

Страница 12: ...ing OPEN B and as you hold it down also press the SETUP SW1 push button The relevant LED starts to flash slowly for 5 sec 3 Release both push buttons Within these 5 sec press the appropriate push butt...

Страница 13: ...e recognised during bus device acquisition chapter 7 2 The use of this type of encoder offers precise and constant information on leaf position guaranteeing reverse movement in case of obstacles The e...

Страница 14: ...orrect coupling of the encoder with the leaf as indicated in the following figure LED ON FLASHING OFF DL 1 Power supply on and BUS connected to board Power supply on but BUS not connected No power sup...

Страница 15: ...The closing photocells reapply the pause E Semiautomatic an OPEN pulse opens the gate and the following one closes it An OPEN pulse stops the gate when opening and reopens when the gate is closing The...

Страница 16: ...at release OPEN stops saves CLOSE OPEN recloses leaves immediately 1 recloses leaves immediately no effect OPEN CLOSE disabled no effect no effect CLOSE disabled no effect OPEN CLOSE disa bled CLOSIN...

Страница 17: ...loses after 5 s stops and opens at release saves CLOSE OPEN IN PAUSE recharges pause time 1 recharges pause time 1 stops operation no effect stops and closes on release after 5 s recharges pause time...