C850
31
532015 - Rev.B
T
ranslation of the original instructions
ENGLISH
12.3 12.3 INVERTER DEFAULTS
Contents Description
Value
Unit
A001
Reference frequency selection
02
A002
RUN command selection
01
A003
Basic frequency
50
Hz
A004
Maximum frequency
120
Hz
A005
O/IO Selection
02
A011
O Start Frequency
0.00
Hz
A012
O End Frequency
0.00
Hz
A013
O Start ratio
0
%
A014
O/IO Final ratio
100
%
A015
O, IO Sampling
01
A016
O, IO Sampling
8
A020
Multi-speed reference 0
10.0
Hz
A021
Multi-speed reference 1
50.0
Hz
A022
Multi-speed reference 2
0.0
Hz
A023
Multi-speed reference 3
0.0
Hz
A024
Multi-speed reference 4
0.0
Hz
A025
Multi-speed reference 5
0.0
Hz
A026
Multi-speed reference 6
0.0
Hz
A027
Multi-speed reference 7
0.0
Hz
A028
Multi-speed reference 8
0.0
Hz
A029
Multi-speed reference 9
0.0
Hz
A030
Multi-speed reference 10
0.0
Hz
A031
Multi-speed reference 11
0.0
Hz
A032
Multi-speed reference 12
0.0
Hz
A033
Multi-speed reference 13
0.0
Hz
A034
Multi-speed reference 14
0.0
Hz
A035
Multi-speed reference 15
0.0
Hz
A038
Motion frequency
6.00
Hz
A039
Motion stop selection
00
A041
Torque boost selection
00
A042
Manual torque boost voltage
1.8
%
A043
Manual torque boost frequency
10.0
%
A044
V/f characteristics selection
00
A045
Output voltage gain
100
%
A051
DC injection braking selection
00
A052
DC injection braking frequency
0.5
Hz
A053
DC injection braking delay time
0.0
Sec
A054
DC injection braking power
50
%
A055
DC injection braking time
0.5
Sec
A056
DC injection braking mode selection
01
A061
Upper frequency limit
0.0
Hz
A062
Lower frequency limit
0.0
Hz
A063
Jump frequency 1
0.0
Hz
A064
Jump frequency 1 amplitude
0.5
Hz
A065
Jump frequency 2
0.0
Hz
A066
Jump frequency 2 amplitude
0.5
Hz
A067
Jump frequency 3
0.0
Hz
A068
Jump frequency 3 amplitude
0.5
Hz
A071
PID selection
00
A072
PID P Gain
1.0
A073
PID I Gain
1.0
Sec
A074
PID D Gain
0.00
Sec
Contents Description
Value
Unit
A075
PID Scale
1.00
Times
A076
PID feedback selection
00
A077
Inverted PID function
00
A078
PID output limitation function
0.0
%
A081
AVR selection
02
A082
AVR voltage selection
230
V
A085
RUN mode selection
00
A086
Energy savings response/Precision
adjustment
50.0
%
A092
Acceleration time 2
10.00
Sec
A093
Deceleration time 2
10.00
Sec
A094
2-phase acceleration/deceleration selection
00
A095
2-phase acceleration frequency
0.0
Hz
A096
2-phase deceleration frequency
0.0
Hz
A097
Acceleration type selection
01
A098
Deceleration type selection
01
A101
O/IO Start-up frequency
0.0
Hz
A102
O/IO Final frequency
0.0
Hz
A103
O/IO Start-up ratio
0
%
A104
O/IO Final ratio
100
%
A105
IO start-up selection
01
A141
Input A operating frequency setting
01
A142
Input B operating frequency setting
02
A143
Operator selection
00
A145
Frequency addition quantity
0.0
Hz
A146
Frequency addition direction
00
A151
VR Start-up frequency
0.0
Hz
A152
VR Final frequency
0.0
Hz
A153
VR Start-up ratio
0
%
A154
VR Final ratio
100
%
A155
VR start-up selection
01
b001
New attempt selection
00
b002
“Allowed time for temporary power
interruption”
0.3
Sec
b003
New attempt wait time
1.0
Sec
b004
“Temporary power interruption/Sub voltage
drop during stop selection”
00
b005
“New attempt time selection for temporary
power interruption”
00
b011
Start-up frequency at frequency extraction
restart
00
b012
Electronic heat level
7.10
A
b013
Electronic heat characteristics selection
01
b021
Overload limit selection
00
b022
Overload limit level
10.65
A
b023
Overload limit parameter
1.0
Sec
b028
Overload limit origin selection
00
b029
“Deceleration speed constant at frequency
extraction restart”
0.5
Sec
b030
Frequency extraction restart level
7.10
A
b031
Software block selection
01
b050
“No stop in case of temporary power
interruption function selection”
00
b051
“No start-up voltage stop in case of
temporary power interruption function”
0.0
V