C850
30
532015 - Rev.B
ENGLISH
T
ranslation of the original instructions
12.2 PROGRAMMING THE INVERTER
WARNING: DO NOT CHANGE parameters other
than those indicated in this section.
Incorrect changes can be dangerous for
people, things or the C850 motor.
The inverter parameters have all been set on default values by
the manufacturer during testing.
Among all of them, the installer only has available a few
programmable inverter parameters:
A020 =
Deceleration Speed (Value Range = 0-20Hz / Default
Value = 10)
A021 =
Running Speed (Value Range = 50-120Hz / Default Value
= 50)
F002 =
Acceleration Time (Value Range = 0.01-99.99 / Default
Value = 2.5)
F003 =
Deceleration Time (Value Range = 0.01-99.99 / Default
Value = 2.5)
PROGRAMMING THE A020 DECELERATION SPEED
For programming, proceed as follows:
•
with the gate stationary and powered, the inverter display
will show
0.0
;
•
press the BLUE button, and the display will show
the first group of parameters
d001
;
•
press the GREY button until the parameter group
A
appears;
•
press the BLUE button, and the display will show
A001
;
•
press one of the two GREY buttons until
A020
appears;
•
press the BLUE button, and the display will
show the value of the parameter;
•
press one of the two GREY buttons until the
desired value appears;
•
press the YELLOW button to confirm;
•
to exit programming, press the BLUE button for 5
sec, until
d001
appears;
•
press the BLUE button to exit, and the display will
show
0.0
.
PROGRAMMING THE A021 RUNNING SPEED
For programming, proceed as follows:
•
with the gate stationary and powered, the inverter display
will show
0.0
;
•
press the BLUE button, and the display will show
the first group of parameters
d001
;
•
press the GREY button until the parameter group
A
appears;
•
press the BLUE button, and the display will show
A001
;
•
press one of the two GREY buttons until
A021
appears;
•
press the BLUE button, and the display will show
the value of the parameter;
•
press one of the two GREY buttons until
the desired value appears
•
press the YELLOW button to confirm;
•
to exit programming, press the BLUE button for 5
sec, until
d001
appears;
•
press the BLUE button to exit, and the display will
show
0.0
.
PROGRAMMING THE F002 ACCELERATION TIME
For programming, proceed as follows:
•
with the gate stationary and powered, the inverter display
will show
0.0
;
•
press the BLUE button, and the display will show
the first group of parameters
d001
;
•
press the GREY button until the parameter group
F
appears;
•
press the BLUE button, and the display will show
F001
;
•
press one of the two GREY buttons until
F002
appears;
•
press the BLUE button, and the display will show
the value of the parameter;
•
press one of the two GREY buttons until
the desired value appears;
•
press the YELLOW button to confirm;
•
to exit programming, press the BLUE button for 5
sec, until
d001
appears;
•
press the BLUE button to exit, and the display will
show
0.0
.
PROGRAMMING THE F003 DECELERATION TIME
For programming, proceed as follows:
•
with the gate stationary and powered, the inverter display
will show
0.0
;
•
press the BLUE button, and the display will show
the first group of parameters
d001
;
•
press the GREY button until the parameter group
F
appears;
•
press the BLUE button, and the display will show
F001
;
•
press one of the two GREY buttons until
F003
appears;
•
press the BLUE button, and the display
will show the value of the parameter;
•
press one of the two GREY buttons until
the desired value appears;
•
press the YELLOW button to confirm;
•
to exit programming, press the BLUE button for 5
sec, until
d001
appears;
•
press the BLUE button to exit, and the display will
show
0.0
.