manualshive.com logo in svg
background image

9

ENGLISH

5.1  

Basic confi guration

To perform BASIC programming:

1.  Press and hold button 

F

; the name of the first function is 

displayed.

2. 

Release the button; the function value is displayed and can be 
modified using the + and - buttons.

3. Press 

and 

hold 

F

 again; the name of the following function is 

displayed, and so on.

The last function St lets you choose whether to save the configuration 
made (

Y

) or exit without saving (

no

). Later, the display will resume 

showing the automated system status

 You can go to St at any time. To exit programming, 
simultaneously press F and -.

BASIC CONFIGURATION 

Display

Function

Default

cF

Barrier configuration

01 

Minimum mass

06 

Maximum mass

Before automated system start-up, you must 
set the correct value, directly correlated to 
the length of the beam and the number and 
type of accessories installed. To determine 
said value, refer to Tables 4 and 5 on page 25

WARNING: Setting a mass default 
lower than the one actually 
installed could cause irreversible 
damage to the bar and barrier 
structure.
Loading a different configuration 
will reset the parameters to the 
default values

06

dF

Default

Y

 

indicates that all values set correspond 
to the defaults

no

 

indicates that one or more set values 
are different from the defaults. Select 

Y

 to restore the default configuration.

Y

Ct

Master / slave configuration

MA

 

Configures the board in master mode

SL

 

Configures the board in slave mode

For details on MASTER / SLAVE 
configuration, refer to section 9.

MA

bu

BUS accessories menu

For functions associated with this parameter 
see paragraph 5.3

no

Display

Function

Default

LO

Operating logics

Automatic

A1 

Automatic 1

Semi-automatic

Parking

PA 

Automatic parking

Cn 

Condo

CA 

Automatic condo

Dead-man

CU 

Custom

E

PA

Pause time

Is effective only if an automatic logic is chosen; 
the value can be set from  

O

 to 

59

 

sec. in 

one second steps. Next, the display changes 
to minutes and tenths of a second (separated 
by a decimal point) and time is adjusted in 
10-second steps up to the maximum value 
of 

4.1

 minutes.

e.g. if the display shows 

2.5

, the pause time 

will be 2 minutes and 50 seconds.

20

So

Opening speed

Adjusts the barrier opening speed.

00 

Minimum speed

10 

Maximum speed

WARNING: Setting an excessive speed 
could cause irreversible damage to the 
beam and barrier structure.

10

Sc

Closing speed

Adjusts the barrier closing speed.

00 

Minimum speed

10 

Maximum speed

WARNING: Setting an excessive speed 
could cause irreversible damage to the 
bar and barrier structure.

02

L1

Loop 1

Activating this parameter, any loop that is 
connected to the Loop 1 input will serve as 
an OPEN function.

Loop 1 enabled

no 

Loop 1 disabled

Note: Should this function be disabled, the 
detection status of the loop will in any case 
remain available on one of the two outputs, 
if configured (see parameters 

o1

... 

o4

 in 

Advanced Configuration)

no

L2

Loop 2

Activating this parameter, any loop that is 
connected to the Loop 2 input will serve as a 
SAFETY/CLOSE function.

Loop 2 enabled

no 

Loop 2 disabled

(see note regarding Loop 1)

no

Содержание B680

Страница 1: ...B680H...

Страница 2: ......

Страница 3: ...NNECTIONS 7 4 1 Terminal board J1 inputs 7 4 2 Terminal board J2 outputs 8 4 3 Terminal board J3 external flashing lamp 8 4 4 Terminal board J4 loop detector 8 4 5 Connector J5 Motor 8 4 6 Connector J...

Страница 4: ...AAC declines all liability as concerns safety and efficient operation of the automated system if system components not produced by FAAC are used 19 For maintenance strictly use original parts by FAAC...

Страница 5: ...e covering compartment is the same for both models while the bar dimensions differ as shown in detail at bar S and bar L Fig 8 4 INSTALLING THE AUTOMATED SYSTEM 4 1 Preliminary checks For the safety a...

Страница 6: ...rrectly operate the barrier pointing out the areas of potential danger 6 MANUAL OPERATION Should manual operation of the barrier be required due to electrical power cut offs or automated system ineffi...

Страница 7: ...photocell The barrier is equipped with a lateral covering profile fitted in the compartment opening under which there are holes for containing Safebeam BUS or wireless photocells To install the photoc...

Страница 8: ...re upgrade J15 Integrated flashing traffic light connector SW1 Programming key F SW2 Programming key SW3 Programming key SW4 SW5 LOOP 1 LOOP 2 calibration button M1 M1A M2 Optional module connector Co...

Страница 9: ...P and GND Fig 26 EMR Emergency contact N C terminal 7 means any device e g switch which if activated in a situation of emergency will open the barrier until the contact is restored When activated this...

Страница 10: ...24 25 for OPENING LOOP 2 magnetic loop LOOP 2 SAFETY CLOSE terminals 26 27 for SAFETY CLOSING 4 5 Connector J5 Motor Rapid connector for connecting the motor 4 6 Connector J7 Encoder The B680H barrie...

Страница 11: ...details on MASTER SLAVE configuration refer to section 9 MA bu BUS accessories menu For functions associated with this parameter see paragraph 5 3 no Display Function Default LO Operating logics A Aut...

Страница 12: ...NG movement to then display 01 once the position of gate OPEN is reached Example of a status sequence displayed starting from a closed barrier The sequence does not include statuses 09 and 10 which co...

Страница 13: ...status of the segments of the left hand digit must correspond to the automated system at rest and without pulse generators or or safeties engaged When the CLOSE photocells are engaged the bottom segme...

Страница 14: ...mum power 40 FC Closing motor power Adjusts the thrust of the motor during the closing phase 00 Minimum power 50 Maximum power 40 PF Pre flashing This parameter is used to activate the flashing lamp f...

Страница 15: ...used together with n C to verify the use of the system and for use of Service Request 00 nC Cycle programming in hundreds of thousands Is used to set a countdown of the system operation cycles the val...

Страница 16: ...t have double insulation Make a preferably square or rectangular loop by preparing a PVC cable duct or by tracing the paving as shown in figure 16 the corners must be cut at a 45 angle to avoid cable...

Страница 17: ...lways closes 16 When this function is activated during closing the CLOSING SAFETIES stop and allow motion to resume when they are disengaged otherwise they immediately reverse opening Y closes when di...

Страница 18: ...value Read only parameter F1 Loop 1 frequency selection This parameter lets you set an oscillation frequency specific to the loop connected to the Loop 1 input or lets the system choose the most adeq...

Страница 19: ...is value increases or decreases the output voltage for OUT 5 changing the brightness of the rope light 04 St STATUS OF THE AUTOMATED SYSTEM Exit from programming storage of data and automated system s...

Страница 20: ...display the indicationshowntothesideconfirming the fact that there are no engaged photocells or active pulse generators 7 2 Setup Before being put into operation the E680 board requires a setup proced...

Страница 21: ...tion systems to the fully closed position with the Mt parameter of the Base configuration level or by operating the release device as indicated in sections 6 and 7 on page 4 3 Access Base programming...

Страница 22: ...03 04 05 06 dF Y Y Y Y Y Y Ct MA MA MA MA MA MA bu no no no no no no So 10 10 10 10 10 10 Sc 10 05 05 04 02 02 S1 05 05 05 05 05 05 S2 05 05 05 05 05 05 Advanced Configuration cF 01 02 03 04 05 06 FO...

Страница 23: ...eted no effect closes immediately after opening is completed OPEN IN PAUSE resets pause time closes blocks operation closes resets pause time closes when disengaged WHEN CLOSING immediately reverses t...

Страница 24: ...ly after opening is completed blocks operation no effect no effect closes immediately after opening is completed OPEN IN PAUSE resets pause time closes blocks operation resets pause time closing inhib...

Страница 25: ...time immediately reverses to opening immediately reverses to opening BLOCKED opens and closes after the pause time closes no effect opening and closing inhibited no effect closing inhibited opens and...

Страница 26: ...hts Foot 2 3 3 4 4 5 6 6 Foot 2 3 3 4 4 4 5 6 Skirt 2 3 3 4 4 5 6 Skirt Foot 3 3 3 4 4 5 Table 3 12 BALANCING TABLES The following two tables indicate the fixing position of the pistons on the rocker...

Страница 27: ...5 5 5 5 6 6 Skirt 4 5 5 5 5 6 6 Skirt Foot 5 5 5 5 5 6 Table 5 13 DEFAULT SELECTION TABLES cF parameter The purpose of the two following tables is to determine depending on the length of the bar and...

Страница 28: ...1 5 m m 2 3 X 1 5mm 2 230V 6 6 2 3 4 2 1 1100 mm 900 mm 470 mm 436 m m 280 m m Fig 5 Fig 5 Raccolta immagini Pictures collection Collection d images Photo Kollection Conjunto de imagenes Afbeeldingen...

Страница 29: ...27 DX SX Fig 10 Fig 10 Fig 11 Fig 11 M M L1 L2 L3 L1 L2 L3 Fig 12 Fig 12 Fig 13 Fig 13 Fig 14 Fig 14 Fig 15 Fig 15 Fig 16 Fig 16...

Страница 30: ...28 Fig 17 Fig 17 L...

Страница 31: ...29 Fig 18 Fig 18 Fig 19 Fig 19 1 2 Fig 20 Fig 20...

Страница 32: ...30 Fig 21 Fig 21...

Страница 33: ...8 9 10 11 SAFE TX CL RX CL 1 2 5 4 3 1 2 12 13 14 15 16 17 18 19 20 21 24 24 24 24 OUT1 OUT2 OUT3 GND Relais NO COM J2 Fig 24 Fig 24 J1 24 GND 24 GND OPEN CLOSE FSW STOP ALARM GND 24 3 4 5 6 7 8 9 10...

Страница 34: ...32 DS1 DL1 DL2 BUS BUS RX TX DL2 DS1 ON ON BUS BUS DS1 DL1 DL2 BUS BUS DL2 DS1 ON ON BUS BUS 2EASY 1 2 J6 Fig 28 Fig 28 Fig 27 Fig 27 Fig 29 Fig 29 Fig 30 Fig 30...

Страница 35: ...33 Fig 31 Fig 31...

Страница 36: ...34 Fig 32 Fig 32...

Страница 37: ...B680H Guida per l utente User s guide Instructions pour l utilisateur Anleitungen f r den Benutzer Gu a para el usuario Gebruikersgids...

Страница 38: ...anovra prima di inserire il sistema di blocco togliere alimentazione all impianto chiave di sblocco triangolare standard ruotare la chiave in senso orario fino all arresto ed estrarla Fig 18 rif a chi...

Страница 39: ...1 Die Firma FAAC lehnt jede Haftung f r Sch den ab die durch unsachgem en oder nicht bestimmungsgem en Gebrauch derAutomatik verursacht werden 2 Die Firma FAAC bernimmt keine Haftung im Falle von nich...

Страница 40: ...YSTEEMB680H 1 WAARSCHUWINGEN 1 FAAC aanvaardt geen enkele aansprakelijkheid voor schade die ontstaat uit oneigenlijk gebruik of ander gebruik dan waarvoor het automatische systeem is bedoeld 2 FAACisn...

Страница 41: ...5 1 2 Fig 18...

Страница 42: ...732719 Rev FAAC S p A Soc Unipersonale Via Calari 10 40069 Zola Predosa BOLOGNA ITALY Tel 39 051 61724 Fax 39 051 758518 www faac it www faacgroup com...

Отзывы: