Warning: 

Always disconnect the electric power supply before

carrying out any work on the control unit (connection,
maintenance).

DS1

No.2: Lock activation delay

OFF = DISABLED
ON = ENABLED

If this dip-switch is enabled, the door movement is delayed
by 500msec with respect to the electric lock command. If
disabled, delay is 200 msec.

    No.1: Inactive

SW1 SET-UP pushbutton

Hold down the SET-UP button for 5 sec. to start the set-up
cycle.

FUSE F1 

1AT/230Vac - 5x20

J1 CONNECTOR

 Transformer Secondary winding - fig. 10

J2 CONNECTOR

Rapid Connector of Manual/Night,Open,Automatic
function selector switch

     

J3  CONNECTOR

  KP-Controller Connection

1- 2 

Connector of KP-Controller programming unit (optional) as

shown in fig. 24.
Use a 2 x 0.5 mm² shielded cable (“bus” communication) for
the connection. Respect the connection polarity as  shown
in figure 24.

Important

: The maximum permissible length of the connection

cable is 50 m.
To inhibit operation of the SD-KEEPER, make the jumper
between terminals of the LOCK switch (fig.24).

J4  TERMINAL BOARD 

Inputs Connection (figs. 11,12,16)

7- 8 GND

Accessories power supply Negative and contacts Common

9

+24Vdc

+24Vdc accessories power supply

10

Internal Command - N.O. Contact

Any pulse generator (pushbutton, sensor, etc.) which, by
closing a contact, commands door opening.
To install several pulse generators as Internal Command,
connect the N.O. contacts in parallel.

11

External Command - N.O. Contact

Any pulse generator (pushbutton, sensor, etc.) which, by
closing a contact, commands door opening.
To install several pulse generators as External Command,
connect the N.O. contacts in parallel.

12

Emergency Command - N.C. Contact

Any pulse generator (normally a pushbutton) which, by
opening a contact, commands an emergency closure of the
system. Alternatively this input can be used to command
emergency opening by programming the system in a suitable
manner using the KP-CONTROLLER programming unit (optio-
nal).
To install several emergency command devices, connect the
N.C. contacts in series.

N.B.

: If emergency command devices are not connected,

jumper inputs 

7

 and 

12

.

Attention:

 Using the KP-CONTROLLER programming unit, you

can change the type of contact from N.C. to N.O. contact.

13

CLOSURE Safety Command - N.C. Contact

Any device (safety sensor, photocell, etc.) which, by opening
a contact, has a safety effect on the closing movement of the
door.
The safety device causes an immediate reversing of the
closing movement of the door, but has no effect on the
opening movement of the door.
To install several CLOSURE safety devices, connect the N.C.
contacts in series.

N.B.

: If CLOSURE safety devices are not installed, jumper inputs

7

 and 

14

.

14

STOP Safety Command - N.C. Contact

Any device (safety sensor, photocell, etc.) which, by opening
a contact, has a safety effect on the operating cycle. In
particular, this safety device interrupts the opening/closing
movement of the door.
When the safety device is disengaged, the door resumes its
opening/closing movement and continues to the end of the
cycle.
To install several STOP safety devices, connect the N.C.
contacts in series.

N.B.

: If STOP safety devices are not installed, jumper inputs 

7

and 

13

.

 7   8    9   10  11 12  13  14  15  16  17  18  19

GND

GND

+ 24 Vdc

Internal Command

External Command

Closure Safety Command

STOP Safety Command

Emergency Command

Key Command

Fire-alarm Command

Card Reader Command

GND

GND

J4

Fig. 11

 7   8    9

 13  14  15

TX

RX

PB SENSOR

+

-

C

+

+

-

-

C

J4

Fig. 12

 7   8    9   10  11 12  13  14 15  16  17  18 19

Содержание 950 BM

Страница 1: ...950BM 950BM para la naturaleza 100 papel reciclado ist umweltfreundlich 100 Altpapier pour la nature papier recycl 100 for nature recycled paper 100 carta riciclata 100 per la natura...

Страница 2: ...Fig 2a Fig 2b Fig 3 1 1 2 2 3 3 1 2 4 5 Fig 4 Fig 4b Fig 4a 6...

Страница 3: ...Fig 5 Fig 6...

Страница 4: ...onter plus de 2 rallonges Cota con eje est ndar Si fuera necesario aumentar la distancia entre el actuador y el brazo utilizar las prolongaci nes modulares opcionales Cada prolungaci n aumenta la altu...

Страница 5: ...pas monter plus de 2 rallonges Cota con eje est ndar Si fuera necesario aumentar la distancia entre el actuador y el brazo utilizar las prolongaci nes modulares opcionales Cada prolungaci n aumenta la...

Страница 6: ...pas monter plus de 2 rallonges Cota con eje est ndar Si fuera necesario aumentar la distancia entre el actuador y el brazo utilizar las prolongaci nes modulares opcionales Cada prolungaci n aumenta l...

Страница 7: ...pas monter plus de 2 rallonges Cota con eje est ndar Si fuera necesario aumentar la distancia entre el actuador y el brazo utilizar las prolongaci nes modulares opcionales Cada prolungaci n aumenta l...

Страница 8: ...under the provisions of Directive 98 37 EC conforms to the essential safety requirements of the following EEC directives 73 23 EEC and subsequent amendment 93 68 EEC 89 336 EEC and subsequent amendme...

Страница 9: ...ol Board 950 MPS Power supply 230 Vac 6 10 50 60 Hz Accessories power supply 24 Vdc 500mA max Electric lock power supply N O N C 24 Vdc 500mA max Standard operating functions selector switch Open Auto...

Страница 10: ...lesarenotinacentral position see Mounting tables The holes are offset in order to ensurethattheoperatorismountedwiththecorrectdirectionof rotation of the mechanism The mounting tables are the followin...

Страница 11: ...in Table 7 N B The default status of the LEDs with the door closed at rest is shown in bold type Table 7 Operation of the status signalling LEDs for 950 I O board LED ON OFF LD1 Accessories power pre...

Страница 12: ...ostrongwind accordingtoitsstructureanddimensions as this could activate the system s spontaneous opening or motionreversing 5 4 5 MICROSWITCHES Nos 5 6 8 9 INACTIVE 5 4 6 MICROSWITCH No 7 STOP SAFETY...

Страница 13: ...llel 12 Emergency Command N C Contact Any pulse generator normally a pushbutton which by openingacontact commandsanemergencyclosureofthe system Alternatively this input can be used to command emergenc...

Страница 14: ...J5 TERMINAL BOARD Connection to relay Outputs figs 13 14 15 Description of the terminal board 1 Electric lock Common 2 Electric lock N O Contact max capacity 0 5 A 24 V fig 13 Ifnopowerissuppliedtheel...

Страница 15: ...able to the 950I O unit must be positioned as shown in figs 4a b The selector switch can be easily inspected by opening the protection door fig 4 ref 1 The selectable operating functions are shown in...

Страница 16: ...loading rotate the arm in closing direction until the next fixing position of the stop point screw fig 21 ref 5 is in line with the inspection slot and fix the screw again 5 Reinstall the arm correctl...

Страница 17: ...ntroller to the 950 I O control board by a 2x0 5mm max 50m cable Fig 24 If the two LOCK terminals are connected to each other as shown in Fig 24 all keys on the programmer are disabled 10 3 DIAGNOSTIC...

Страница 18: ...ctivated The internal and external radars are disabled The Key command causes opening and closing after the night pause time elapses standard 7 sec Adjusting range of night pause time from 0 to 30 sec...

Страница 19: ...eys or to select sub menu or parameter and confirm with the OK key An asterisk on the display indicates the currently active setting To exit programming select the exit function at each level Otherwis...

Страница 20: ...ENGLISH Diagram 3 Setup Diagram 4 Lock SETUP 80 7 SEC 2 SEC CLOSING STANDARD NO STANDARD OBSTACLE DETECTION NIGHT PAUSE TIME PARTIAL OPENING PAUSE TIME EXIT LOCK OFF ON ALWAYS ONE WAY NIGHT NIGHT KIT...

Страница 21: ...950 v DIAGNOSTICS NR CYCLE XXXX ALARM N alarm description PASSWORD 0000 PASSWORD 0000 PASSWORD 0000 PASSWORD 0000 KEEP SETTINGS OFF ON 8 8 EXIT ADVANCED MENU OPERATION PARAMETERS CLOSING SPEED OPENIN...

Страница 22: ...Out Setup PASSWORD 0000 PASSWORD 0000 PASSWORD 0000 PASSWORD 0000 IN OUT SETUP EMERG OPEN CLOSE OUT OP CL NO OUT ALARM NO NC USCITA NC NO NC ADVANCED MENU OPERATION PARAMETERS VARIOUS EXIT CHANGE PASS...

Страница 23: ...00 IN OUT SETUP STAND SETUP STANDARD NO STANDARD INTERLOCK MASTER SLAVE NO MEMORY WITH MEMORY EXIT NEW PASSWORD 0000 NEW PASSWORD 0000 NEW PASSWORD 0000 NEW PASSWORD 0000 MASTER SLAVE ON OFF ON OFF 2...

Страница 24: ...E BAND 4 FUN 0 00 00 TIME BAND 3 FUN 0 00 00 TIME BAND 1 FUN 0 00 00 TIME BAND 2 FUN 0 00 00 TIME BAND 5 FUN 0 00 00 TIME BAND 4 FUN 0 00 00 TIME BAND 3 FUN 0 00 00 TIME BAND 1 FUN 0 00 00 TIME BAND 2...

Страница 25: ...rocedure and if the cause of signalled malfunction was removed it restores normal operation 5 ADVANCED MENU PASSWORD To access the advanced menu insert the 4 digit password default 0000 1 OPERATION PA...

Страница 26: ...can create up to 5 different time bands for each day of the week by setting the band starting time and assign an operational function to each time band When the KP Controller s internal clock reaches...

Страница 27: ...or to close totally in order to activate the sensor of the second door 6 Door B opens Fig 28 Door A Door B 7 The person exits 8 Door B closes after the night pause time elapses The operation is identi...

Страница 28: ...s is immediately reversed The partial opening function enables control of total opening of the master only The operating functions must be set on the master automated system only or on the KP Controll...

Страница 29: ...sshouldbefollowed to prevent problems from arising accidentally Do not stand or allow children or adults to stand within range of the door especially during operation and do not leave objects near it...

Страница 30: ...tunas para el perfeccionamiento t cnico o para cualquier otro tipo de exigencia de car cter constructivo o comercial Timbro del Rivenditore Distributor s Stamp Timbre de l Agent Fachh ndlerstempel Sel...

Отзывы: