5.2. SETTING THE ADJUSTING TRIMMERS
The programming unit features trimmers (fig.8) which regulate the
following parameters:
Trimmer TR1
to set the opening speed.
Setting from 4 to 10 seconds.
Trimmer TR2
to set the closing speed.
Setting from 4 to 10 seconds.
Trimmer TR3
to set the pause time (AUTOMATIC logic).
Setting from 0 to 30 seconds.
5.3. SIGNALLING LEDs
LD1 Led =
Green LED - electric motor power supply.
LD2 Led =
Red LED - indicates SET-UP/Alarm.
LD3 Led =
Green LED - 5V power supply.
5.4.2. MICROSWITCH No. 2 - SET-UP PROCESS
When mounting the “sliding” arm or for opening angles greater
than 90°, this microswitch has to be enabled.
OFF = Function DISABLED
ON = Function ENABLED
5.4.3. MICROSWITCH No. 3 - SELECTOR FUNCTION (“ 2 ” POSITION)
This function allows the operating function to be selected with the
selector switch in the “2” position.
OFF = MANUAL Function
ON = NIGHT Function
5.4.4. MICROSWITCH No. 4 - PUSH AND GO
When activated, this function enables the opening command to
be given by pushing the closed door manually. It is sufficient to
give the door an initial push/pull in the opening direction.
OFF = Function DISABLED
ON = Function ENABLED
WARNING
: It is advisable not to enable this function if the door is
subject to strong wind, according to its structure and dimensions,
as this could activate the system's spontaneous opening or
motion reversing.
5.4.5 . MICROSWITCHES Nos. 5/6/8/9 - INACTIVE
5.4.6. MICROSWITCH No. 7 - STOP SAFETY DEVICE
It makes it possible to detect activation of the STOP safety device
during the entire door travel (COMPLETE) or to disable detection
beyond 70° opening (REDUCED).
OFF = COMPLETE Function
ON = REDUCED Function
When the STOP safety control is ensured by an active sensor fitted
on the leaf, if you enable the REDUCED function, the detection
of any obstacle (e.g. side wall) is prevented which would cause
interruption of the work cycle.
5.4.7 MICROSWITCH No. 10 - RS232 PORT
It makes it possible to enable the RS232 port connection to PC for
software update. In normal use conditions, the dip switch is in OFF
position.
OFF = Port DISABLED
ON = Port ENABLED
6. 950 I/O ELECTRONIC CONTROL UNIT
5.4. PROGRAMMING THE MICROSWITCHES (fig.9)
The programming unit has a series of microswitches which allow the
functions shown to be selected.
The system is supplied with all the microswitches in the
OFF
position.
5.4.1. MICROSWITCH No. 1 - CLOSING STROKE
This function enables the closed position force to be increased by
further loading the transmission system after the door has reached
the mechanical closure stop.
It is advisable to use this function to assist activation of the electric
lock.
OFF = Function DISABLED
ON = Function ENABLED
MICROSWITCHES
1 2 3 4 5 6 7 8 9 10
OFF
ON
Fig. 9
Fig. 10
6.1 LAYOUT AND DESCRIPTION