Note:

 If you are using both a receiver and a

decoder,  hard wire the decoder and plug the
receiver in.

Open/Hold Open Device

: To open and hold open the

gate, an Open/Hold Open device must make a set of
contacts across terminals 18 and 21 and must break a set
of contacts between terminals 13 and 21.  See Figure 22
for more detail.

Stop Button

: The stop button you install must have

normally closed (N.C.) contacts. Multiple stop buttons
must be wired in series. Connect your stop device
between terminals 14 and 15.

The LED Indicators

: The five light-emitting diodes

(LEDs) on the control panel can be used to check for the
proper functioning of the devices you attach to the
control panel. The LED lights are on whenever the
contacts are closed across each of the respective
terminals.

DL1 and DL2 should illuminate only when an activating
signal is sent for 2 and 1 gate leaves, respectively. DL3
should be illuminated except when the stop button is
pressed. DL4 and DL5 should be illuminated except
when the reversing devices for opening and closing,
respectively, are triggered. Use the LEDs and the table
below to determine if the accessory devices you have
installed are operating properly.

LED

On

Off

DL1,
Open 2 leaves

Command
active

Command
inactive

DL2,
Open 1 leaf

Command
active

Command
inactive

DL3, Stop

Command not
active

Command
active

DL4,
FTSW Open

Opening
reversing
devices not
triggered

Opening
reversing
device triggered

DL5,
FTSW Close

Closing
reversing
devices not
triggered

Closing
reversing
device triggered

Electric Lock

: Connect your lock to the terminals 24

and 25. The terminals provide 12 VAC that pulses for 4
seconds whenever the gate starts to open. An electric
lock can make use of the reversing stroke function
controlled by DIP switch 5. A reversing stroke is a short
closing phase that allows the electric lock time to
disengage itself before the operator starts its opening.
Turn DIP switch 5 on only if necessary for your lock to
function correctly.

See Figure 22 for the wiring of a magnetic locking
device.

Warning Light

: Connect a warning light to terminals

22 and 23 in the group labeled 

W.LIGHT

 in terminal

block J3. The terminals provide an output voltage of 30
VDC, maximum power 3 Watts. This output voltage
will power most 24 VDC warning lights.

Note

: The behavior of the warning light varies

according to the logic you have set.

Logics A, S, E, EP, and B

: The warning light is

on steadily during opening and the pause phase.
During closing, the light flashes.

Logic C

: The warning light is on steadily during

opening and flashes during closing.

Set Operating Controls

WARNING

! Turn off the main power before you make

any electrical connections or set any switches inside the
control panel box.

You need to set DIP switches and adjust the
potentiometers on the control panel for your gate's
operation. The 450 MPS Control Panel has 5 DIP
switches and 4 potentiometers that control a wide range
of functions.

Set DIP Switches

Switches 1, 2, and 3 (Operating Logic)

: The 450 MPS

Control Panel offers six operating modes: A, S, E, EP,
B, and C.

Refer to the operating logic tables earlier in these
instructions for more detail about the logical modes
available on the 450 MPS control panel.

Switches 1, 2, and 3 control the operating logic
according to the following table:

Switch

Logic

1

2

3

A

on

off

on

S

on

off

off

E

off

on

off

EP

on

on

off

B

on

on

on

C

off

off

on

Switch 4 (Reversing Device Behavior on Closing):

Refer to the operating logic tables earlier in this manual
and to the chart below for how to set DIP switch 4.

Содержание 760

Страница 1: ...oe 11 Install the Gate Leaf 14 Install the Operator in the Load Bearing Box 14 Install the 450 MPS Control Panel 16 Connect the Main Power Supply 16 Connect the Operator s to the Control Panel 17 Chec...

Страница 2: ...ough away from the road to eliminate the potential of traffic getting backed up This distance is affected by the size of the gate how often it is used and how fast the gate operates 2 The operator you...

Страница 3: ...the equipment 3 If a gate system component malfunctions turn off the main power before making any attempt to repair it 4 Do not attempt to impede the movement of the gate You may injure yourself as a...

Страница 4: ...t lb kg 1760 800 Maximum gate length ft m 7 2 1 10 3 13 4 Maximum angle of rotation deg 148 degrees 90 deg opening time sec 12 17 Nominal torque ft lb Nm 399 543 200 272 Your standard 220 VAC power so...

Страница 5: ...are included 760 Operator Figure 1 Hydraulic pump drive assembly with a plastic shipping cover fitted over the rack Package containing 4 bolts and 4 lock washers for attaching the 760 Operator to the...

Страница 6: ...ety of both people and property FAAC safety standards state that the gate should stop its movement if it encounters a force of more than about 33 lb The installer of the 760 Operator makes the necessa...

Страница 7: ...hem after pause time Opens single leaf connected to Motor 1 and closes it after pause time No effect No effect No effect Off Opening Closes both leaves immediately Closes the leaf immediately Stops St...

Страница 8: ...1 No effect opening is inhibited No effect opening is inhibited No effect opening is inhibited Off Opening Stops Stops Stops Stops gate closes when reversing device no longer triggered No effect On O...

Страница 9: ...ate leaf has positive stops in both the opening and closing directions see Figure 5 Figure 5 Positive stops are required in the fully opened and fully closed gate positions 4 You need to determine a m...

Страница 10: ...toward the gate post for release Figure 6 The Manual Release in the 760 Standard Operator Installing the 760 Operator Installing the 760 Operator consists of the following steps Install the load bear...

Страница 11: ...d shaft of the pinion or the top edge of the box In fact you should recheck all alignments and adjust the mounting box if necessary Then you can pour concrete around the box and up to its top edge so...

Страница 12: ...the holes on the opposite sides of the pipes Figure 8 A sample shear pin assembly Axis of rotation within body of gate leaf Axis of rotation outside body of gate leaf Splined shaft Splined shaft slee...

Страница 13: ...d the splined collar into place on the bottom of the shoe s U shaped section If you are using the shear pin assembly spot weld the splined collar to the bottom of the shear pin assembly and spot weld...

Страница 14: ...erator see Figure 14 Be sure to keep track of the plugs and the rack and pinion covers in case you ever need to remove the operator for repair Pinion cover Mounting box cover Bolt 1 of 4 Figure 13 Rem...

Страница 15: ...and closing momentum completely before you operate the gate electrically The pressure valves are not preset at the factory and may operate the gate leaf with enough force to endanger people and serio...

Страница 16: ...ain power breaker switch and for making sure that the entire gate system meets all applicable electrical codes Follow the instructions that follow to install the 450 MPS control panel for the 760 Oper...

Страница 17: ...unction boxes depends on your gate design If any operator is more than 2 ft away from the U L Listed control panel enclosure the connection must be made inside a junction box Use a U L Listed cord gri...

Страница 18: ...The terminal strip wiring of the 450 MPS with photobeams Figure 21 Wiring detail a inside the junction box and b from the junction box or operator to the high voltage terminal strip on the 450 MPS co...

Страница 19: ...ns for installing such accessories follow Connect Other Devices WARNING Turn the main power off before you make any electrical connections or set any switches inside the control panel box Now you can...

Страница 20: ...20 Figure 22 Common accessories wired to 450 MPS...

Страница 21: ...en An electric lock can make use of the reversing stroke function controlled by DIP switch 5 A reversing stroke is a short closing phase that allows the electric lock time to disengage itself before t...

Страница 22: ...positive stop for opening and for closing Leaf Delay You may choose to delay one leaf on closing for overlapping gate leaves Be sure the operator on the leaf for delayed closing is connected to Motor...

Страница 23: ...en the brass lock nut Manually move the gate leaf to the fully opened position against the opened limit stop Loosen the brass lock nut for the opening brake adjustment bolt Next turn the square headed...

Страница 24: ...slide this hex head into the brass fitting of the 760 Operator that is located on the same end as the bypass valve adjustment screws see Figure 29 Brass gear assembly Plastic gear assembly Figure 25 A...

Страница 25: ...ing to Figure 30 Caution Do not weld anything to or on the inside of the sleeve of the splined shaft Next weld the outside of the sleeve for the splined shaft solidly to the inside of the hole in the...

Страница 26: ...se check once per year Heavy duty use check every 6 mo Rack and Pinion When you remove the 760 Operator from the mounting box to change the hydraulic oil grease the rack and the pinion Light duty use...

Страница 27: ...rs are running Solution Make sure that the motor is running in the right direc tion and make sure the Manual Release mechanism has fully engaged the hydraulic system Increase the bypass pressure in sm...

Страница 28: ......

Страница 29: ...UL strain relief kit 2167A 710914 710915 709020002 703930...

Страница 30: ......

Страница 31: ...t s or has been subject to misuse negligence or accident or has not been operated in accordance with FAAC International Inc s or FAAC S p A s instructions or has been operated under conditions more se...

Отзывы: