17
1
J1 terminal block for main power supply
8
Leaf delay potentiometer
2
J2 terminal block for connecting the operator(s)
9
DIP switch assembly
3
J3 terminal block for low-voltage accessories
Fuses
220 VAC
115 VAC
4
J4 quick connector port
10
F1, Main power
5 A
10 A
5
Pressure adjustment potentiometer
11
F2, Accessories
800 mA
800
mA
6
Pause time potentiometer
12
F3, Electric lock
1.6 A
1.6 A
7
Potentiometer for adjusting open/close time
13
F4, Microprocessor
250 mA
250 mA
Figure 19. The 450 MPS control panel
Connect the Operator(s) to
the Control Panel
WARNING
! Turn the main power off before you make
any electrical connections or set any switches inside the
control panel box.
Using a Junction Box
Connecting your operator(s) to the control panel may
require the use of one or more junction boxes. Whether
you need 0, 1, or 2 U.L. Listed junction boxes depends
on your gate design.
If any operator is more than 2 ft away from the U.L.
Listed control panel enclosure, the connection must be
made inside a junction box. Use a U. L. Listed cord grip
where the operator cord enters the junction box; use
conduit between the junction box and the enclosure.
Caution
: The control panel will not operate without an
operator connected to terminals 3, 4, and 5.
If your gate system has one operator, connect the
capacitor and the red and black (or brown and black)
wires from your operator to the terminals 3 and 5 in
block J2. Connect the white (or blue) wire from the
operator to terminal 4.
Note
: If you want to delay the closing of one gate
leaf in a two-leaf gate design, be sure to connect
its operator to Motor 1 (terminals 3, 4, and 5).
If your gate system has two operators, connect the
second operator to terminals 6, 7, and 8 in block J2.
Connect the second capacitor and the red and black (or
brown and black) wires to terminals 6 and 8, and
connect the white (or blue) wire from the operator to
terminal 7.