EXAMPLES OF CORRECT CONNECTION TO THE CHIMNEY

In the presence of type B gas appliances with intermittent operation not intended for heating, they must have their own aeration and/or 

ventilation opening. 
The air inlets must meet the following requirements:

 

Š

they must be protected with grids, metal mesh, etc., but without reducing the net useful section;

 

Š

they must be made so as to make the maintenance operations possible;

 

Š

positioned so that they cannot be obstructed;

The clean and non-contaminated air flow can also be obtained from a room adjacent to that of installation (indirect aeration and 

ventilation), as long as the flow takes place freely through permanent openings communicating with the outside.

The adjacent room cannot be used as a garage, or to store combustible material or for any other activity with a fire hazard, bathroom, 

bedroom or common room of the building.

FLUE GAS EXHAUST

The heat generator works in depression and is equipped with an outlet fan for flue gas extraction. There must be a single exhaust system for 

the generator. Using a flue that is shared with other devices is not allowed.

The components of the flue gas exhaust system must be chosen in relation to the type of appliance to be installed in compliance with:

 

Š

UNI/ TS 11278 in the event of metal chimneys, with particular attention to that stated in the specification; 

 

Š

UNI EN 13063-1 and UNI EN 13063-2, UNI EN 1457, UNI EN 1806 in the event of non-metallic chimneys.

 

Š

The length of the horizontal section must be minimal and, in any case, no longer than 3 metres, with a minimum upward slope of 3%

 

Š

There must not be more than 4 direction changes including the one due to the use of the "T" element.

 

Š

A “T” fitting with a condensation collection cap must be provided at the base of the vertical section.

 

Š

If the exhaust is not inserted in an existing flue, a vertical section with a windproof end piece is required (UNI 10683).

 

Š

The vertical duct can be inside or outside the building. If the smoke duct is inserted in an existing flue, it must be certified for solid fuel.

 

Š

If the smoke duct is outside the building, it must always be insulated.

 

Š

The smoke ducts must have at least one airtight inlet for flue gas sampling.

 

Š

All the sections of the flue gas duct must be accessible to inspection.

 

Š

Inspection openings must be provided for cleaning.

 

Š

If the generator has a fume temperature lower than  160°C+ ambient temperature caused by the high yield (contact technicians) it 

MUST be resistant to humidity.

 

Š

A flue system that does not respect the previous points or, in general, that does not comply with the regulations, may cause condensation 

phenomena inside it.

CHIMNEY CAP

The chimney caps must meet the following requirements:

 

Š

they must have a useful outlet section no less than double that of the chimney/ducted system on which it is installed;

 

Š

they must be adapted in order to prevent the penetration of rain and snow in the chimney/ducted system;

 

Š

they must be built so that, in the event of winds coming from all directions and from any angle, the expulsion of combustion products 

is in any case ensured;

Protection from rain 

and wind

Condensation-proof 

"T" fitting with 

inspection plug 

Insulated flue

Insulated "T" 

fitting with 

inspection plug

Protection from rain and wind

"T" fitting with 

i n s p e c t i o n 

plug

CONNECTION TO THE MAINS ELECTRIC SUPPLY

The generator is supplied with an electric power cable to be plugged into a 230V 50 Hz socket, possibly with a circuit breaker switch. The 

socket must be easily accessible.

The electrical system must be compliant with standards. The efficiency of the earthing circuit must be checked. Unsuitable earthing of the 

system can cause malfunctioning for which the manufacturer will not be held liable. 

Power supply variations beyond 10% can cause faulty operation of the product.

FOR GERMANY ONLY

The product can be connected to a shared flue

 (multi-connection) provided that the requirements of the regional and national regulations, 

amongst which DIN EN 13384-2, DIN V 18160-1, DIN 18896 and of the MFeuV-2007 (Muster-Feuerungsverordnung) are strictly complied with, 

and that the local chimney sweep has checked and approved the installation conditions. 

Please also remember the following indications, which the end user must comply with:

• 

The device can be operated only with the doors closed.

• 

The doors and all setting devices must remain closed when the device is not on (except for cleaning and maintenance operations).

Содержание MIETTA EVO

Страница 1: ...MADE IN ITALY design production MIETTA EVO SINFONY UK PELLET STOVES USER MANUAL 004280462 Rev 000...

Страница 2: ...2 ENGLISH APPLY TECHNICAL DATA LABEL...

Страница 3: ...1 4 25 SETTINGS 27 DISPLAY 27 STAND BY 27 OPERATION WITH ADDITIONAL THERMOSTAT OPTIONAL 27 DELTA T 28 FIRST LOAD 28 CLEANING 28 RESET 28 EASY CONTROL 28 ADDITIONAL FUNCTIONS 29 SUPPLEMENTARY THERMOSTA...

Страница 4: ...VITER DES D G TS VORSICHT OBLIGATORISCH BEVOR SIE DEN OFEN BEWEGEN BITTE UNBEDINGT DIE BEZEICHNETE KERAMIK KACHELN ENTFERNEN UM SCH DEN ZU VERMEIDEN ATENCI N PERENTORIO ANTES DE MOVER LA ESTUFA SACAR...

Страница 5: ...S POUR VITER DES D G TS VORSICHT OBLIGATORISCH BEVOR SIE DEN OFEN BEWEGEN BITTE UNBEDINGT DIE BEZEICHNETE KERAMIK KACHELN ENTFERNEN UM SCH DEN ZU VERMEIDEN ATENCI N PERENTORIO ANTES DE MOVER LA ESTUFA...

Страница 6: ...ance has been installed as well as the instructions contained in this manual The use of the appliance must comply with all local regional national and European regulations The Manufacturer cannot be h...

Страница 7: ...IF IT IS DISCONNECTED FROMTHE MAINS IT IS ADVISED TO POSITION THE POWER SUPPLY CABLE SO THAT IT DOES NOT COME INTO CONTACT WITH HOT PARTS OFTHE APPLIANCE THE POWER SUPPLY PLUG MUST BE ACCESSIBLE AFTE...

Страница 8: ...CLEAN THE MAJOLICAS IT IS RECOMMENDED TO USE A SOFT DRY CLOTH IF A DETERGENT OR LIQUID IS USED THE LATTER COULD PENETRATE INSIDE THE CRACKLES HIGHLIGHTING THEM SINCE THE PRODUCT CAN TURN ON AUTOMATICA...

Страница 9: ...th moisture content 12 Seasonal space heating energy efficiency Space heating emissions at nominal heat output Space heating emissions at minimum heat output Nominal heat output Minimum heat output in...

Страница 10: ...omestichotwaterproductionandinadjacentandcommunicating rooms 3 where the depression measured in situ between the external and internal environment is greater than 4 Pa N B Watertight appliances can al...

Страница 11: ...always be insulated The smoke ducts must have at least one airtight inlet for flue gas sampling All the sections of the flue gas duct must be accessible to inspection Inspection openings must be prov...

Страница 12: ...installed This means that it is ideal for passive houses because it does not take air in from within the house COMBUSTION AIR To ensure the stove remains hermetically sealed the connection pipe for th...

Страница 13: ...DETAILS A Room air outlet E Radio emergency card I Additional thermostat input B Pellet hopper pressurised closure F ON OFF j Combustion air inlet C Access to combustion chamber G Fuse K Fumes outlet...

Страница 14: ...TAILS A Room air outlet E Radio emergency card I Additional thermostat inlet B Pellet hopper pressurised closure F ON OFF j Combustion air inlet C Access to combustion chamber G Fuse K Fumes outlet D...

Страница 15: ...isplay to show the following CLOSE HOPPER STOVE DOOR This indication means that you have 60 seconds to close the hatch door and the pellet lid After the 60 seconds during ignition the stove will go in...

Страница 16: ...OR QUALITY PELLETS OR ANY OTHER MATERIAL DAMAGES THE FUNCTIONS OF THE GENERATOR AND MAY INVALIDATE THE WARRANTY AND RELIEVE THE MANUFACTURER OF ALL RESPONSIBILITY Keep clean The pellet used must compl...

Страница 17: ...r L2 LED off stove off LED on stove in P1 2 3 and operating LED flashing stove in P1 2 3 and off in alarm on stand by P2 Increase power L3 LED off stove off LED on stove in P3 4 5 and operating LED fl...

Страница 18: ...n the display In this case repeat the procedure J THE RADIO CONTROL DEVICE IS ALREADY CONFIGURED WITH UNIT 0 IF THERE IS ANOTHER STOVE TO AVOID INTERFERENCES A NEW CONFIGURATION MUST BE PERFORMED MODI...

Страница 19: ...adio control device is fitted with an LCD backlit display The display remains lit for 5 seconds After a certain period of time in order to minimise battery consumption the display turns off Sleep mode...

Страница 20: ...E TERMINAL TA DISPLAY Display text Temperature detected in room Set ambient temperature Power 1 5 Time Chrono active STAND BY active Battery low Display text Time Indicates contact of the external add...

Страница 21: ...roduct at the maximum power and temperature Avoid remaining in the room for a long time Do not touch the surfaces of the product Notes The process is completed after a few heating cooling cycles Do no...

Страница 22: ...T AND RESULT IN THE IMMEDIATE NULLIFICATION OF THE WARRANTY PERIOD IN THE EVENT OF WEAR OR DETERIORATION REQUEST THE PART S REPLACEMENT FROM THE AFTER SALES SERVICE REPLACEMENT DOES NOT FALL WITHIN TH...

Страница 23: ...m power If the contact is closed request the stove works at the set power If the setting is on HOT set above 37 C the stove always operates at the set power ignoring the external contact and the tempe...

Страница 24: ...on the burning pot access the EASY SETUP program and lower the value by one unit to 1 then wait until the next day and if there is no improvement decrease again to a maximum of 3 Instead if it is nec...

Страница 25: ...and also the desired power Current day and time settings are essential for the correct operation of the Chrono To set OK CHRONO PRGX ENABLING Allows the chrono and the different stove time slots to b...

Страница 26: ...3 1 02 00 23 00 08 00 16 30 t 22 18 2 1 26 ENGLISH Time slot 1 Start 02 00 Stop 23 00 Power 3 set temp 22 C Time slot 2 Start 08 00 Stop 16 30 Power 1 set temp 18 C Stove operation Time slot Power Set...

Страница 27: ...n the STAND BY function is not enabled OFF if the stove exceeds the set ambient temperature it will switch to the minimum power level modulating and displaying MODULATION on the screen When the room t...

Страница 28: ...ating the combustion chamber cleaning operations CONTROLS PROCEDURE Press key 6 Press 3 until SETTINGS appears and confirm by pressing 6 Keep pressing 3 until CLEANING appears and confirm by pressing...

Страница 29: ...TION OPTIONAL The stove can control the room temperature through a supplementary thermostat optional After ignition by pressing key 1 or in chrono mode the stove will work to reach the set value on th...

Страница 30: ...hemically aggressive detergents for cleaning The ceramic glass must be cleaned when the glass is completely cold To clean the ceramic glass simply use a dry brush and some damp newspaper dipped in ash...

Страница 31: ...combustion chamber and the bottom of the burn pot completely using a suitable vacuum cleaner B Clean the ash conveyor using the special tool to remove any deposits C Clean the chamber probe take care...

Страница 32: ...se each time the flue pipe needs to be vacuumed and cleaned If there are horizontal sections the residue must be removed to prevent it from obstructing the flow of fumes SHUT DOWN END OF SEASON At the...

Страница 33: ...1 2 SINFONY MIETTA EVO 33 ENGLISH HEAT EXCHANGER AND INSPECTION COMPARTMENT THE IMAGES ARE FOR ILLUSTRATIVE PURPOSES...

Страница 34: ...cated C Combustion chamber and heat exchanger full cleaning including ignition plug pipe D Hopper complete emptying and cleaning and check gasket E Check the air intake pipe and check clean the mechan...

Страница 35: ...cone in the provided points B Gaskets pellet hopper inspections ash drawer and door replace and apply silicone where indicated C Combustion chamber and heat exchanger full cleaning including ignition...

Страница 36: ...re ignition due to an external thermostat COOLING STAND BY A new ignition is attempted when the generator has just been switched off When the generator switches off one must wait for the complete shut...

Страница 37: ...The door is not closed correctly The ash drawer is not closed correctly Check that the door closes correctly Check that the burn pot is clear and clean The automatic cleaning of the burn pot is block...

Страница 38: ...kindly asked to separate this equipment and or batteries or accumulators included from other types of waste and to arrange for disposal by the municipal waste service It is possible to ask your local...

Страница 39: ...39 ENGLISH...

Страница 40: ...Y 39 0445 865911 39 0445 865912 info extraflame it www lanordica extraflame com TO FIND THE SERVICE CENTRE NEAREST TO YOU CONTACT YOUR DEALER OR CONSULT THE SITE WWW LANORDICA EXTRAFLAME COM The manuf...

Отзывы: