SAFETY DEVICES
14
Chapter 4
Adjustment automatic circuit breaker switch
Automatic circuit breaker switch (block thermostat)
Circulation system
Expansion system*
Safety dissipation system incorporated with the generator with thermal safety valve (self-activated),
whenever the appliance does not have a temperature self-adjustment system.
The temperature safety sensors must be in place on the machine at a distance no greater than 30 cm from
the fl ow connection.
Whenever the generators lack a device, those missing can be installed on the thermo product fl ow pipe,
within a distance no greater than 1m from the machine.
The domestic heating appliances with automatic feeding must:
be equipped with a fuel block thermostat, or
be equipped with a cooling circuit prepared by the manufacturer of the appliance.
The cooling circuit must be activated by a heat safety valve such to guarantee that the limit temperature
set by the Standard is not exceeded.
Connection between the power supply unit and the valve must be free from interceptions.
The pressure upstream from the cooling circuit must be at least 1.5 bar.
6 Litre expansion vessel
3 Bar safety valve
Pressure switch
*The product expansion vessel is equal to 6 litres. The
closed system expansion vessel must be dimensioned
between 4% and 6% of the total volume of the plant
therefore, the standard closed vessel may not be
suffi
cient in cases of greater water volumes.