background image

48VTR English     9/00    Ver. 2.7    

 

10 

Control
Relay

Alarm
Relay

AC Power

Load

Wiring the Alarm and Control Relays in Series

8
9

4

5

6

7

Meter Contacts

Figure 4

13. RAMP AND SOAK FUNCTIONS 

The Extech 48VTR controller operates as a fixed setpoint controller. However, the 
controller offers several advanced features which can enhance your application. These 
include Ramp-to-Setpoint and Soak/Event Timers. Refer to the details below. 

13.1 Ramp-to-Setpoint (‘rAmP’ Parameter)

 

To limit the rate at which the controller allows the process (PV) to move towards 
setpoint (SV), enter a value in units per minute for the 'rAmP' parameter. The 
programmable limit ranges from 0.0 to 100.0 units per minute. The controller will 
automatically adjust its outputs to observe this limit. Setting this parameter to zero 
defeats the Ramp-to-Setpoint function. The “rAmP” parameter will not appear if 
“Parameter Lock” (P-L) is set to a “0” or “2”. 

13.2 Soak Timer Function 

The Soak Timer function allows the process to ramp to setpoint and remain (Soak) at 
that setpoint for a user-programmable period of time. Set the "A1Fu" parameter to 
either '10' (Soak ON-TIMER) or '11' (Soak OFF-TIMER) depending upon the application 
(refer to Table IV in Appendix A for the difference between ON and OFF Timers). Set 
the Soak time in parameter 'timE' in the First Programming Level. The Output and 
Alarm Relays must be wired in series so that the Alarm relay can switch the control 
relay at the appropriate times (refer to Fig. 4). For example, when a setpoint of 500

o

F is 

reached, the Soak time (programmed by the user under parameter 'timE") begins to 
countdown. After the desired Soak time has elapsed, the Alarm relay switches thereby 
switching the Control relay circuit. 

13.3 Event Timer Function 

The Alarm relay can be 
programmed to switch state at 
desired times in a process. This 
is accomplished by first setting 
the alarm function in parameter 
"A1Fu" to either an EVENT-ON 
or EVENT-OFF timer (refer to 
the function list and Table IV in 
Appendix A for the difference 
between ON and OFF Timers). 
Next, select a countdown time 
in parameter ‘timE’. The relay 
timer will start counting down 
when the PV equals the SV. 
 
For example, while maintaining a certain temperature for 4 hours, an event is to take 
place 2 hours into the process. The Event, in this example, is the controller's alarm 
relay activating a pump. To do this, set the alarm function to an EVENT-ON Timer 
(selection 8) in parameter "A1Fu". Set the time to 120 minutes (2 hours) in parameter 
"timE". When the controller is powered the alarm relay will be OFF, when the PV = SV 
the relay remains OFF but the timer begins to countdown, and after 2 hours the relay 
will turn ON permitting the process event to take place. 
 

Содержание 48VTR

Страница 1: ...etpoint and adjust the process via relay or analog output to bring the process to the desired setpoint This Three Mode PID controller offers Simultaneous Process Value PV and Setpoint Value SV display...

Страница 2: ...0 x 45 0mm 0 5mm 2 2 Input Specifications Thermocouple input Programmable Types J K T E B R S N Cold Junction Compensation Thermocouple Break Protection Upscale and Downscale Lead Wire Effect 0 015 o...

Страница 3: ...nting bracket Slide meter into panel through the cutout 3 3 Replace the mounting bracket and then tighten the bracket screws Do not tighten the mounting screws excessively 3 4 Connect the power cord t...

Страница 4: ...user s requirements Error messages are also displayed on these red LED Digits Programming details and error messages are explained later in this manual 5 2 SV Setpoint Variable Display LEDs During no...

Страница 5: ...regard to input signal nnnn Under range condition with regard to input signal Input sensor not connected or is inoperable 5 4 Keypad Descriptions SCROLL Key Press once to access the programming mode...

Страница 6: ...controller will monitor the changing PV and override the controller output if necessary to limit the PV s rate of change oPoF Output Offset Manual reset function The user can program a value 0 0 to 10...

Страница 7: ...arameters adjustable Level 1 parameters A1SP only 1 Same as 0 level 1 parameters Ramp and A1SP 2 Same as 0 level 1 parameters oPoF and A1SP 3 Same as 0 level 1 parameters Ramp oPoF and A1SP 4 Same as...

Страница 8: ...larm relay outputs default in the event of controller error 0 OFF OFF 1 OFF ON 2 ON OFF 3 ON ON Addr Not used Set to 0 PVoF PV Offset Permits the user to offset the PV indication from the actual PV Fo...

Страница 9: ...ch corresponds to the range you are using i e for 4 20 mA inputs 4 mA would now be applied to the controller d Use the UP DOWN arrow keys to set the value which will display for a 4mA input For exampl...

Страница 10: ...de manually if desired in programming level 2 e To abort an Auto Tune process simply press and hold the SCROLL key again for 5 seconds until the decimal stops flashing NOTE The Auto Tune process can l...

Страница 11: ...Set the Soak time in parameter timE in the First Programming Level The Output and Alarm Relays must be wired in series so that the Alarm relay can switch the control relay at the appropriate times ref...

Страница 12: ...e Selections for parameter A1Fu 00 Deviation High Alarm For the Deviation High Alarm the value entered for the A1SP parameter equals the amount the controller s HIGH alarm setpoint is offset from the...

Страница 13: ...er up the alarm relay energizes When the PV SV the alarm relay de energizes When the timer counts down to zero the relay energizes Set the timer at parameter time in Programming Level 1 See Table IV b...

Страница 14: ...to 0 Hysteresis is similar to deadband A region extending from the alarm setpoint up or down depending upon the alarm type where no relay action can occur to eliminate relay chatter Act Action This is...

Отзывы: