48VTR English     9/00    Ver. 2.7    

 

Warning:

 An independent redundant alarm should be used if control/alarm 

relay failure could result in potential harm or damage. 

 

4. METER DESCRIPTION  

1.  

Process Variable (PV) Display  

2.  

Setpoint Variable (SV) Display  

3.  

Control Output Status LED 

4.  

Alarm Status LED 

5.  

'Return' Programming Key 

6.  

Down Arrow Programming Key 

7.  

Up Arrow Programming Key 

8.  

'Scroll' Programming Key 

9.  

Auto Tune Decimal Indication 

10.  

Mounting Bracket 

11. Bracket 

Screw 

 

5. FRONT PANEL DESCRIPTION 

5.1 PV (Process Variable) Display LEDs 

During normal operation, the top LED (red digits) displays the actual process 
measurement (temperature, voltage, or current input signal). This process 
measurement is known as the "Process Variable" or PV. In programming mode, 
these red LEDs display the parameters from Programming Levels 1 through 4 (input 
type, control action, etc.), one at a time. These parameters can be edited to suit the 
user's requirements. Error messages are also displayed on these red LED Digits. 
Programming details and error messages are explained later in this manual.

 

5.2 SV (Setpoint Variable) Display LEDs

 

During normal operation, the bottom LED (green) displays the user-programmable 
Setpoint Variable (SV). This represents the desired process equilibrium point to 
which the controller's output will adjust the process. To adjust the setpoint, use the 
up/down arrow keys. The allowable setting range equals the range the user selects 
in LoLt (Low Limit) and HiLt (High Limit) parameters during programming. While 
programming, this green LED display shows the actual data that can be edited for 
the parameter shown on the red LED display. For example if the red LED is 
displaying input type, then the green LED lists the input types (J, K, Linear, etc.). 
The user can then select the desired type using the programming keys. Refer to 
later sections for more on programming. 

6       7      8 +    9 -     10

 

 1       2      3       4      5

 

AC

 

Control Output 

 

Alarm Output

 

TC

 

Analog

 

RTD

 

Figure 3

 

2-wire RTD

4-wire RTD

1    2    3

1    2    3

Short terminals 1 and 2

Leave the 4th wire open

+

 

4-20

 

Содержание 48VTR

Страница 1: ...etpoint and adjust the process via relay or analog output to bring the process to the desired setpoint This Three Mode PID controller offers Simultaneous Process Value PV and Setpoint Value SV display...

Страница 2: ...0 x 45 0mm 0 5mm 2 2 Input Specifications Thermocouple input Programmable Types J K T E B R S N Cold Junction Compensation Thermocouple Break Protection Upscale and Downscale Lead Wire Effect 0 015 o...

Страница 3: ...nting bracket Slide meter into panel through the cutout 3 3 Replace the mounting bracket and then tighten the bracket screws Do not tighten the mounting screws excessively 3 4 Connect the power cord t...

Страница 4: ...user s requirements Error messages are also displayed on these red LED Digits Programming details and error messages are explained later in this manual 5 2 SV Setpoint Variable Display LEDs During no...

Страница 5: ...regard to input signal nnnn Under range condition with regard to input signal Input sensor not connected or is inoperable 5 4 Keypad Descriptions SCROLL Key Press once to access the programming mode...

Страница 6: ...controller will monitor the changing PV and override the controller output if necessary to limit the PV s rate of change oPoF Output Offset Manual reset function The user can program a value 0 0 to 10...

Страница 7: ...arameters adjustable Level 1 parameters A1SP only 1 Same as 0 level 1 parameters Ramp and A1SP 2 Same as 0 level 1 parameters oPoF and A1SP 3 Same as 0 level 1 parameters Ramp oPoF and A1SP 4 Same as...

Страница 8: ...larm relay outputs default in the event of controller error 0 OFF OFF 1 OFF ON 2 ON OFF 3 ON ON Addr Not used Set to 0 PVoF PV Offset Permits the user to offset the PV indication from the actual PV Fo...

Страница 9: ...ch corresponds to the range you are using i e for 4 20 mA inputs 4 mA would now be applied to the controller d Use the UP DOWN arrow keys to set the value which will display for a 4mA input For exampl...

Страница 10: ...de manually if desired in programming level 2 e To abort an Auto Tune process simply press and hold the SCROLL key again for 5 seconds until the decimal stops flashing NOTE The Auto Tune process can l...

Страница 11: ...Set the Soak time in parameter timE in the First Programming Level The Output and Alarm Relays must be wired in series so that the Alarm relay can switch the control relay at the appropriate times ref...

Страница 12: ...e Selections for parameter A1Fu 00 Deviation High Alarm For the Deviation High Alarm the value entered for the A1SP parameter equals the amount the controller s HIGH alarm setpoint is offset from the...

Страница 13: ...er up the alarm relay energizes When the PV SV the alarm relay de energizes When the timer counts down to zero the relay energizes Set the timer at parameter time in Programming Level 1 See Table IV b...

Страница 14: ...to 0 Hysteresis is similar to deadband A region extending from the alarm setpoint up or down depending upon the alarm type where no relay action can occur to eliminate relay chatter Act Action This is...