48VTR English     9/00    Ver. 2.7    

 

dP:

  

Decimal Point selection. 

00 

no decimal point 

01 

0.1 resolution 

02 

0.01 resolution (cannot use this setting for temperature inputs) 

03 

0.001 resolution (cannot use this setting for temperature inputs) 

Ct:

   

Control Output Cycle Time. Range: 0 to 100 seconds. This is the period of 
time the controller waits between output percentage changes. The longer the 
time set here, the less responsive the controller will be to process changes. 
Set Ct for the longest period of time possible without causing process 
oscillations; this will help to prolong the life of the relay.  

 NOTE:

 Set ‘Ct’ to '0' seconds for the 4-20mA analog output option. Parameter 

'Ct' is not used when ON/OFF control is activated. 

Hyst:

  

Hysteresis for ON/OFF control output. Users can create a deadband region 
from 0.0 to 25.5% of SPAN. The SPAN is the region that extends from the 
user-programmable Low Limit (LoLt) value to the High limit (HiLt) value. 
Hysteresis is used to eliminate control relay chatter by creating a deadband 
that extends from the setpoint down or up (depending upon the relay's 
function) where no relay action can occur. 

EroP

:   Error Protection. The desired state to which the Control and Alarm relay 

outputs default in the event of controller error.   

0

 

OFF OFF 

1

 

OFF ON 

2

 

ON OFF 

3

 

ON ON 

Addr:

  

Not used. Set to 0. 

PVoF

  

PV Offset. Permits the user to offset the PV indication from the actual PV.  For 
example, if the thermocouple used is producing readings 2

o

 higher than the 

actual temperature across the range, the user can eliminate the 2

o

 difference 

by programming a "-2" value at this parameter. Overall range of the setting is -
180 to +180.  The default value  is '0'. 

tyPE:

 Sensor input selection.  Select from the list below: 

00 

J type thermocouple 

01 

K type thermocouple 

02 

T type thermocouple 

03 

E type thermocouple 

04 

B type thermocouple 

05 

R type thermocouple 

06 

S type thermocouple 

07 

N type thermocouple 

08 

RTD Pt100 ohm (DIN) 

09 

RTD Pt100 ohm (JIS) 

10 

Linear mode (voltage or current input)  

Note

: The controller can be 

ordered in one of four input types; 
Thermocouple, RTD, Voltage or 
Current. 
Conversion from one input type to 
another requires a hardware 
modification. Contact Extech for 
information. 

LoLt:

  

Low limit (of Span or Range). Set the Low Limit lower than the lowest 
expected SV and PV display.  Note that the low limit is restricted to the limits 
specified for the type of input selected.   

HiLt:

  

High limit (of Span or Range). Set High Limit higher than the highest expected 
SV and PV display. Note that the high limit is restricted to the specification for 
the type of input selected. 

 

Содержание 48VTR

Страница 1: ...etpoint and adjust the process via relay or analog output to bring the process to the desired setpoint This Three Mode PID controller offers Simultaneous Process Value PV and Setpoint Value SV display...

Страница 2: ...0 x 45 0mm 0 5mm 2 2 Input Specifications Thermocouple input Programmable Types J K T E B R S N Cold Junction Compensation Thermocouple Break Protection Upscale and Downscale Lead Wire Effect 0 015 o...

Страница 3: ...nting bracket Slide meter into panel through the cutout 3 3 Replace the mounting bracket and then tighten the bracket screws Do not tighten the mounting screws excessively 3 4 Connect the power cord t...

Страница 4: ...user s requirements Error messages are also displayed on these red LED Digits Programming details and error messages are explained later in this manual 5 2 SV Setpoint Variable Display LEDs During no...

Страница 5: ...regard to input signal nnnn Under range condition with regard to input signal Input sensor not connected or is inoperable 5 4 Keypad Descriptions SCROLL Key Press once to access the programming mode...

Страница 6: ...controller will monitor the changing PV and override the controller output if necessary to limit the PV s rate of change oPoF Output Offset Manual reset function The user can program a value 0 0 to 10...

Страница 7: ...arameters adjustable Level 1 parameters A1SP only 1 Same as 0 level 1 parameters Ramp and A1SP 2 Same as 0 level 1 parameters oPoF and A1SP 3 Same as 0 level 1 parameters Ramp oPoF and A1SP 4 Same as...

Страница 8: ...larm relay outputs default in the event of controller error 0 OFF OFF 1 OFF ON 2 ON OFF 3 ON ON Addr Not used Set to 0 PVoF PV Offset Permits the user to offset the PV indication from the actual PV Fo...

Страница 9: ...ch corresponds to the range you are using i e for 4 20 mA inputs 4 mA would now be applied to the controller d Use the UP DOWN arrow keys to set the value which will display for a 4mA input For exampl...

Страница 10: ...de manually if desired in programming level 2 e To abort an Auto Tune process simply press and hold the SCROLL key again for 5 seconds until the decimal stops flashing NOTE The Auto Tune process can l...

Страница 11: ...Set the Soak time in parameter timE in the First Programming Level The Output and Alarm Relays must be wired in series so that the Alarm relay can switch the control relay at the appropriate times ref...

Страница 12: ...e Selections for parameter A1Fu 00 Deviation High Alarm For the Deviation High Alarm the value entered for the A1SP parameter equals the amount the controller s HIGH alarm setpoint is offset from the...

Страница 13: ...er up the alarm relay energizes When the PV SV the alarm relay de energizes When the timer counts down to zero the relay energizes Set the timer at parameter time in Programming Level 1 See Table IV b...

Страница 14: ...to 0 Hysteresis is similar to deadband A region extending from the alarm setpoint up or down depending upon the alarm type where no relay action can occur to eliminate relay chatter Act Action This is...

Отзывы: