background image

48VTR English     9/00    Ver. 2.7    

 

9. FOURTH PROGRAMMING LEVEL PARAMETERS 

Press and hold the SCROLL and RETURN keys simultaneously for 5 seconds to enter 
this level from the third programming level. To return to normal operation at any time, 
press the RETURN key. 

LoCA and HiCA:

 Low and High Input Calibration values. Refer to Section 10 

“Calibration” for details.  

tunE:

  

Auto Tuning ‘initialization mode’ selection. This parameter allows the user to 
select when an Auto Tune session is automatically initiated by the controller. 
Set this parameter as desired from the Table in Section 11.1. To activate Auto 
Tune manually, refer to Section 11.2. 

10. CALIBRATION 

Important Note: 

Calibration is rarely required and special equipment is needed to 

perform calibrations. The calibration procedure cannot be aborted once the calibration 
parameters are fully accessed. Do not initiate the calibration process until fully prepared 
and qualified to do so. It is safe to scroll through the 4

th

 programming level to view the 

setting. Follow these steps only if prepared to do so. 

a. 

"LoCA" (Low Calibration) will be the first parameter to appear in this level. 

b. 

Remove the sensor from the controller's input screw terminals and connect a 
Thermocouple (mV) or RTD (resistance) simulator to the controller's input 
terminals.  For a process DC input, use a 4-20mA or 1-5VDC signal, depending on 
the input type of the controller.    

c. 

Apply the low input signal to the controller which corresponds to the range you are 
using, i.e., for 4-20 mA inputs, 4 mA would now be applied to the controller. 

d. 

Use the UP/DOWN arrow keys to set the value, which will display for a 4mA input. 
For example, for a 4-20mA input to display –50 to +150, set ‘LoCA’ to –50. 

e. 

Press and hold the RETURN key for at least 5 seconds and the parameter on the 
display will change from "LoCA" to "HiCA" (High Calibration).  The Low Calibration 
value is now written into the controller's non-volatile memory. 

f. 

Apply the high input signal to the controller, which corresponds, to the range you 
are using. For example, for a 4-20mA input controller, apply a 20mA signal. 

g. 

Use the UP/DOWN arrow keys to set the value that will display for a 20mA input. 
For example, for a 4-20mA input to display –50 to +150, set ‘HiCA’ to +150. 

h. 

Press and hold the RETURN key for at least 5 seconds and the meter will return to 
normal operation. The High Calibration value is now written into the controller's 
non-volatile memory. 

i. 

Input a signal midway between the Low and High Calibration signals previously 
applied and verify that the display indicates a value midway between the high 
display (+150, in the above example) and the low display value (-50).  For the 
example, apply 12mA to d50. 

 

11. AUTO TUNING 

11.1 Auto Tune Initialization Modes 

The Controller has the capability to start an Auto Tune session automatically. If this is 
desired, select the conditions whereby an Auto Tune session will automatically begin 
from Table III below. The controller defaults to Setting = ‘0’ (user initiates an Auto Tune 
session). To manually initiate an Auto Tune session, follow the procedure in Section 
11.2. 
 
 

Содержание 48VTR

Страница 1: ...etpoint and adjust the process via relay or analog output to bring the process to the desired setpoint This Three Mode PID controller offers Simultaneous Process Value PV and Setpoint Value SV display...

Страница 2: ...0 x 45 0mm 0 5mm 2 2 Input Specifications Thermocouple input Programmable Types J K T E B R S N Cold Junction Compensation Thermocouple Break Protection Upscale and Downscale Lead Wire Effect 0 015 o...

Страница 3: ...nting bracket Slide meter into panel through the cutout 3 3 Replace the mounting bracket and then tighten the bracket screws Do not tighten the mounting screws excessively 3 4 Connect the power cord t...

Страница 4: ...user s requirements Error messages are also displayed on these red LED Digits Programming details and error messages are explained later in this manual 5 2 SV Setpoint Variable Display LEDs During no...

Страница 5: ...regard to input signal nnnn Under range condition with regard to input signal Input sensor not connected or is inoperable 5 4 Keypad Descriptions SCROLL Key Press once to access the programming mode...

Страница 6: ...controller will monitor the changing PV and override the controller output if necessary to limit the PV s rate of change oPoF Output Offset Manual reset function The user can program a value 0 0 to 10...

Страница 7: ...arameters adjustable Level 1 parameters A1SP only 1 Same as 0 level 1 parameters Ramp and A1SP 2 Same as 0 level 1 parameters oPoF and A1SP 3 Same as 0 level 1 parameters Ramp oPoF and A1SP 4 Same as...

Страница 8: ...larm relay outputs default in the event of controller error 0 OFF OFF 1 OFF ON 2 ON OFF 3 ON ON Addr Not used Set to 0 PVoF PV Offset Permits the user to offset the PV indication from the actual PV Fo...

Страница 9: ...ch corresponds to the range you are using i e for 4 20 mA inputs 4 mA would now be applied to the controller d Use the UP DOWN arrow keys to set the value which will display for a 4mA input For exampl...

Страница 10: ...de manually if desired in programming level 2 e To abort an Auto Tune process simply press and hold the SCROLL key again for 5 seconds until the decimal stops flashing NOTE The Auto Tune process can l...

Страница 11: ...Set the Soak time in parameter timE in the First Programming Level The Output and Alarm Relays must be wired in series so that the Alarm relay can switch the control relay at the appropriate times ref...

Страница 12: ...e Selections for parameter A1Fu 00 Deviation High Alarm For the Deviation High Alarm the value entered for the A1SP parameter equals the amount the controller s HIGH alarm setpoint is offset from the...

Страница 13: ...er up the alarm relay energizes When the PV SV the alarm relay de energizes When the timer counts down to zero the relay energizes Set the timer at parameter time in Programming Level 1 See Table IV b...

Страница 14: ...to 0 Hysteresis is similar to deadband A region extending from the alarm setpoint up or down depending upon the alarm type where no relay action can occur to eliminate relay chatter Act Action This is...

Отзывы: