background image

Expo Technologies Limited

¤

¤

 

Page 2 of 7 

ML384  Issue 03 

   09.01.13 

 

- For low flow rates, the Outlet Orifice may be incorporated 
within the Relief Valve making use of the existing Spark 

Arrestor. The Relief Valve will then have a suffix /CF**, 
where ** is the orifice size in millimeters. 

Section 1 

Installation of the System

The installation of the MiniPurge

£

 system, the 

protective gas supply, any alarm device should be in 
accordance with the requirements of NFPA 496. 

The electrical installation associated with the 
MiniPurge

£

 system shall conform to the local codes 

and the relevant clauses of NFPA 496. 

1.1  

Installation of the Expo LC and CFHP Systems 

1.1.1  The Expo system should be installed either directly 
on or as close as possible to the Pressurized Enclosure 
(PE). It should be installed so that the system indicators 
may be readily observed. 

1.1.2 All parts of any system carry a common serial 
number. If installing more than one system, ensure that 
this commonality is maintained on each installation. 

1.1.3  Any tubing, conduit and fittings used to connect to 
the PE should be metallic, or, if non-metallic, conform to 
the local codes for flammability ratings. No valve may be 
fitted in any tube connecting the Expo system to the PE. 

1.1.4 The user or manufacturer of the PE shall determine 
the volume of the PE, the necessary purging volume, and 
the time to be allowed for purging, using the chosen Expo 
system purging flow rate. It is the user's responsibility to 
verify or enter this data on the PE and/or Expo system 
nameplate. Ask Expo if in doubt. 

Example calculations: 

a)  If the PE external dimensions give a volume of 20 cubic 
feet, and it is NOT a motor, multiply the volume by four to 
get the Purging Volume i.e. 80 cubic feet. Divide the 
Purging Volume by the purge rate e.g. 32 cubic feet per 
minute, and round up to the next even minute above, i.e. 
Purging time would be 4 minutes. 

b)  If the PE is a motor, multiply the internal free volume by 
ten to get the Purging Volume. For the example above, 
Purging time would be 8 minutes. 

1.1.5  If the PE contains an internal source of release of 
flammable gas or vapor, the procedures for assessment of 
the release as given in NFPA 496 shall be observed. The 
user must verify that the specification of the Expo system 
e.g. pressures, continuous flow (dilution) rate and type of 
protective gas are correct for the specific application. If an 
inert protective gas is required, the Expo Control Unit can 
be specified to have Compressed Air for the control logic 
and Inert Gas for the protective gas to minimize Inert Gas 
consumption. 

1.1.6 More than one PE can be protected by a single 

system. If PEs are connected and purged in “series” e.g. 
“Daisy Chained”, the Outlet Orifice must be fitted on the 

last enclosure with the Purge Inlet to the first enclosure. 
The bore and length of the tube or conduit used to 
interconnect the enclosures is critical and will determine 
the maximum pressure experienced by the first enclosure 
in the series. Advice on sizing can be obtained from Expo 
Technologies. The test pressure for all the enclosures 

should be 3 times the pressure inside the first 
enclosure when purging is taking place. 

If PE’s are to be connected in parallel each enclosure 

must have its own outlet Relief Valve, Purge Flow 

Sensor and Pressure Sensor. System “Models” can be 

mixed e.g. Model LC for one enclosure and Model CF 
for another. An example would be a Gas 
Chromatograph instrument. Expo systems with this 

facility have option code “TW”.

 

1.2  Quality 

and 

Installation 

of the Pressurizing 

Air or Inert Gas Supply 

1.2.1  The source of the compressed air must be in a 
non-classified area. Inert gas may be used as an 
alternative to compressed air. 

1.2.2 Unless a supply shut-off valve has been 
specially fitted within the Expo system, a valve with the 
same, or larger, thread size as the Control Unit inlet 
fitting shall be fitted externally. In addition, for "Y" and 
"Z" Pressurization systems, a suitable indicator shall 
be provided. 

1.2.3 The tubing and fittings used must conform to 
1.1.3 above. 

 

1.3  

Provision and Installation of Alarm Devices 

Expo Technologies systems have a Minimum Pressure 

Sensor set to a pressure of at least 0.1” WC (0.25 

mbar). When the PE pressure is above this set point 
the Sensor produces a positive "Pressurized" signal. 
This is displayed on a Red/Green indicator. This signal 
can be used to operate an electrical contact for a 

remote “Alarm”. The pneumatic signal may be supplied 

either 

a) to a pressure operated switch (MiniPurge

£

 Option 

Code /IS) suitable for an Intrinsically Safe circuit, in 
accordance with Expo drawing EP80-2-11, (or for a 
Non-Incendive circuit in Division 2), or 

b) to a bulkhead fitting where it is available to the user 
(MiniPurge

£

 Option Code /PO).  This signal can be 

used to operate an external electrical switch either 
local (e.g. explosionproof) or remote in a non-classified 
area. 

When the enclosure pressure falls below the set point 
of the Sensor the "Pressurized" signal is removed, i.e. 
the absence of the signal indicates 

a “Alarm” 

("Pressure Failure") condition. The user must make 
use of this external alarm facility in accordance with 

NFPA 496 requirements, if the system “Alarm” 

indicator is not located in a place where it can be 
readily observed. 

Example: The "Pressurized" signal can be used to 
produce an "Alarm" action by means of a conventional 
"pressure switch" set to operate at around 15 psi (1 

Содержание ML384

Страница 1: ...llow these instructions Please refer to the standard for principles and definition These instructions apply only to the pressurizing system it is the responsibility of the manufacturer of the pressuri...

Страница 2: ......

Страница 3: ...rminal Box 11 Section 6 Installation of the System 12 Relief Valve Unit 12 Air Supply Quality 12 Pipe Work 13 Multiple Enclosures 13 Provision and Installation of Alarm Devices 13 Power Supplies and t...

Страница 4: ...b 20 C to 55 C T V 12 1462X Ex pxb ia IIC T6 Gb Ex pxb ia IIIC T95 C Db Tamb 20 C to 55 C OV Purge Outlet Valve is pneumatically operated IS Intrinsically Safe Power Alarm terminal box Timing Method E...

Страница 5: ...nts signals 1 8 NPT female minimum 6 mm pipe to be used Visual Indicators Alarm Red Pressurized Green System Purging 4 LEDs that flash sequentially to indicate elapsed time black when not purging IS T...

Страница 6: ...te intervals up to 99 minutes tolerance 0 3 seconds Default Setting 99 minutes Weight 27 kg 60lb Type RLV104 ss FS Design number D758RLV Bore Purge Outlet Valve 104 mm Relief Valve 75 mm Relief Valve...

Страница 7: ...air supply pres sure during the purge process Operation of the System Once the system is installed correctly turn on the air supply Refer to Commissioning section The purge system commences the purge...

Страница 8: ...ver be less than the required purge time The system is now operating correctly in leakage compensation mode If the system has not performed as expected check the installation thoroughly and ensure it...

Страница 9: ...switching devices may be limited in their gas group The certification documentation supplied with any such devices must be checked to ensure their suitability This system is primarily designed for use...

Страница 10: ...entered the enclosure before pressurization Purging is the process of removal contaminated air and replacement with air or inert gas known to be free from flammable gas The duration of this purge proc...

Страница 11: ...ower Interlock switch Alarm Trip Purge Time Machinery Start Normal Operation CLAPS Regulator Pressure Intermediate switch contacts open Intermediate sensor sends falling pressure signal Fault Conditio...

Страница 12: ...m specified pressure Purge Flow Sensor The Purge Flow Sensor monitors flow through the Purge Outlet Valve At correct purge flow rates above the minimum specified for purging the sensor sends a signal...

Страница 13: ...ntially dangerous to energise the pressurized enclosure in an non pressurized condition when it is known that there is potentially explosive gas or dust in the hazardous location Visual Indicators Vis...

Страница 14: ...controls the leakage compensation air flow into the enclosure after the purging is complete It either increases or decreases the air flow into the enclosure as appropriate to maintain a stable runnin...

Страница 15: ...might affect the calibration of the device In particular the exterior of the spark arrestor should not be painted or blocked in any way Air Supply Quality The MiniPurge system should be connected to...

Страница 16: ...above the minimum the Minimum Pressure Sensor re turns a positive pressurized signal causing the alarm indicator on the control unit to change from red to green When the pressure falls below the minim...

Страница 17: ...all screws in the terminals are secure In all cases the application and isolation of power must be controlled by the MiniPurge system using the power interlock signal No switches are permitted between...

Страница 18: ...e minimum pressure sensing pipe was removed Open the Purge Flow Restrictor Valve very slowly until the Pressure Relief Valve opens Check the opening pressure is within calibration limits This test can...

Страница 19: ...check readings on manometer as system will automatically re purge when it reaches minimum pressure 20 While the system re purges return the CLAPS Regulator to the initial setting 21 If minimum pressu...

Страница 20: ...ation There are no unauthorised modifications The air supply is uncontaminated The interlocks and alarms function correctly Approval labels are legible and undamaged Adequate spares are carried The ac...

Страница 21: ...nsitive and it is recommended that a 1 4 turn maximum adjustments are applied between tests Re calibration of the Pressure Sensors The brass nozzle on the sensor is sealed into position using Loctite...

Страница 22: ...designed for ease of fault finding and many of the components fitted are plug in or chassis mounted Check components by substitution only after establishing that such action is necessary Before carryi...

Страница 23: ...n the supply pipe Static pressure of 5 barg must be maintained during purge Check air supply pressure at the inlet to the control unit Ensure that the supply pipe bore is suitable for the flow rate Pr...

Страница 24: ...as stated on the Customer Test and Inspection Sheet S0015 018 Pressure gauge Air Supply Pressure 0 10 barg S0015 135 Miniature gauge Logic Pressure 0 4 barg ETM IS31 001 IS battery pack for electronic...

Страница 25: ...system merely tops up for any enclosure leakage The system provides an initial high flow of purging air that leaves the PE through the Relief Valve After the initial purging has been completed the Co...

Страница 26: ...one PE can be protected by a single system If PEs are connected and purged in series e g Daisy Chained the Outlet Orifice must be fitted on the last enclosure with the Purge Inlet to the first enclosu...

Страница 27: ...ally by the user by the use of local isolating switch 1 4 2 In accordance with NFPA 496 Expo Mini X Purge systems can have the Action on Pressure Failure normally Alarm and Trip adjusted by the user t...

Страница 28: ...ation do not confuse this flow rate with that caused by excessive setting of the LCV Close the LCV slowly observing the manometer or gauge see item 2 1 3 above The PE pressure will start to fall as th...

Страница 29: ...quantity The LCV is too far open and the air flow is holding the RLV open continuously Note Some CFHP systems have a deliberate but modest Continuous air flow through the RLV in normal operation do n...

Страница 30: ...in the air supply For this reason a dust and water filter should always be fitted But debris can enter from other sources and it is vital therefore that the procedures described in Section 2 is carrie...

Страница 31: ...d Is the pipe to the Power Switch airtight The signal to the Power Switch bulkhead has a restrictor that limits the permissible leakage from the pipe e Note the timer setting Reset the timer to the m...

Страница 32: ...e com Appendix A Certifications Download the certificates at www expoworldwide com downloads Component Certificate Number Purge System ATEX Certificate SIRA 01ATEX1295X IECEx Certificate IECEx SIR07 0...

Страница 33: ...7 6 29 3 32 3 57 2 027256 6 5 9 02 180 5 33529 7 33529 5 1 0 41 0 0 7 5 6 6 67 0 286 1 67 1 66 67 H 81 7 21 2 67 1 66 67 8 77 1 6 67 1 66 67 72 5 1 81 66 67 7 27 5 6 0 7 5 6 6 127 6 UG 1 352 7 21 0 16...

Страница 34: ...50 7 6 7 78 725 17 50 7 6 7 9 6312 G 7521 385 7 0 5 6 77 5 3 1 725 50 35 6685 1 725 6 67 0 385 1 0 1 385 28 1 725 81 7 21 2 25 175 16 6 5 8 76 21 0 1 080 3 0 1 385 57 7 21 77 16 225 7521 7 0 5 72 5 1...

Страница 35: ...d NOTE LC BOOST system is optional LC BOOST 71 66 72 66 7 1 PP 29 5 1 PP 1 7 8163 72 5 1 6 0 7 5 5 1 67 786 33529 02 1R 7 668 UG 1 352 7 21 0 16 216 1 PP 2 127 6 SR 7HFKQRORJLHV LPLWHG 2 1R 1 6 7 7 86...

Страница 36: ...RM 1 8 NPT 1 8 NPT 1 4 6mm I D 1 4 6mm I D 1 NPT PI H CONNECT TO EITHER A OR B 1 2 NPT 1 2 NPT A B 1 25mm I D MINIMUM 1 8 NPT 1 8 NPT 1 8 NPT ELECTRICAL SIGNAL VIA EEx e JUNCTION BOX RECOMMENDED MINIM...

Страница 37: ......

Страница 38: ...09 110 111 112 113 114 115 116 117 118 BLACK GREY BROWN BLACK GREY BROWN GREY BLACK BLUE BROWN TERMINAL LAYOUT INTERMEDIATE PRESSURE CONTACTS SEE CIRCUIT DIAGRAM ALARM PRESSURISED CONTACTS MOTOR INTER...

Страница 39: ......

Страница 40: ...N O T S C A L E SR 7HFKQRORJLHV LPLWHG JOB No FINISH TITLE CUSTOMER SHEET No O F PROJECTION D I M E N S I O N S I N m m 81 7 1 20 DRAWING No 1 NRB from Expo Technologies Limited neither are they to b...

Страница 41: ...Pressure Equipment Directive 97 23 EC MiniPurge Systems are classified as not higher than category I under Article 9 of this Directive and intended for use in potentially explosive atmospheres Hazard...

Страница 42: ......

Страница 43: ......

Страница 44: ...ologies Ltd Unit 2 The Summit Hanworth Road Sunbury on Thames TW16 5DB UK Tel 44 0 20 8398 8011 Fax 44 0 20 8398 8014 E mail sales expoworldwide com Qingdao Expo M E Technologies Co Ltd 329 Huashan Er...

Отзывы: