Page
5
ML435 | v23
Expo Technologies UK
T: +44 (0) 20 8398 8011
Expo Technologies US
T: +1 (440) 247 5314
Expo Technologies China
T: +86 532 8906 9858
Stop the stopwatch when the purging indicator stops flashing.
Check stopwatch timing to verify that the actual purge time is equal to or greater than the required purge time.
Note: The recorded purge time must never be less than the required purge time.
The system is now operating correctly in leakage compensation mode.
If the system has not performed as expected, check the installation thoroughly and ensure it has been carried
out according to the instructions.
If an obvious problem has not been highlighted and corrected, follow the procedures in the
Fault Finding
section.
If all checks have been carried out and the system still does not perform as expected, contact your local
distributor or Expo Technologies.
Indicator
Colour
Status
Alarm / Pressurized
Green
Pressurized and in leakage compensation mode
Purging
Black
No longer in purge mode