EXPO ML384 Скачать руководство пользователя страница 31

Expo Technologies Limited

¤

¤

 

Page 7 of 7 

ML384  Issue 03 

   09.01.13 

 

Possible cause 1: 

Insufficient purging Flow due to 

inadequate air supply pressure. Check the air supply 
pressure at the inlet to the CU when flow is taking place. 
Excessive pressure drop in the supply pipe is a very 
common cause of this problem. The supply pipe must be at 
least as big as the CU inlet fitting, i.

e. at least ½” NB (12 

mm). Super-MiniPurge

£

 

systems with ¾” or 1” connections 

must have AT LEAST this internal diameter for supply and 
outlet tubing. Due to the high flows demanded from these 
large systems the need for adequate supply tubing is 
VITAL. If in doubt, or for long distances, install tubing that 
is at least 50% larger than the inlet size! 

Possible cause 2:  Excessive Pressurized Enclosure (PE) 
leakage. Check around the PE when flow is taking place. 
Any significant leakage must be cured. Has a Leakage 
Test been done? The total leakage should not exceed 10% 
of the Purge Flow Sensor setting. Check for leakage down 
the conduit through unsealed stopping boxes. 

Possible cause 3:  PE not strong enough. Repeat the PE 
pressure test. Is is recommended that the PE is tested to 

three times the Relief Valve opening pressure e.g. 12”WC 

(30 mbar) for systems with default settings. Has this been 
done? 

Possible cause 4:  The tubing from the RLV Flow Sensing 
point to the Purge Flow Sensor is not air-tight e.g. fitting 
nuts not tightened or tube damaged. Check and repair as 
necessary. 

Possible cause 5:  The Purge Flow Sensor is not operating 
correctly or out of calibration. The basic operation of the 

Purge Flow Sensor can be checked by unscrewing the 2.4” 

(60 mm) diameter diaphragm and by using a finger, block 
the threaded hole in the top of the valve module. The valve 
should operate and the indicator turn Yellow. If this works 
correctly and the flow through the Relief Valve is above the 
minimum required WITH THE RELIEF VALVE COVER 
FIRMLY SECURED IN PLACE the Sensor diaphragm 
needs re-calibrating or replacing. 

4.5  System 

Fails 

to 

Switch 

Power On after the Purge 

Time has Elapsed? (“X”

-Purge Systems Only) 

Possible cause 1: Is power available? Is the power 
disconnect closed? Are the fuses or circuit breaker OK? 

Possible cause 2:  System fault? Timer not timed out? 

a) 

Has the “Purging” indicator been Yellow for the whole of 

the purge time? 

b)  Is the logic pressure gauge at 30 psi (2 bar) 

r

10%. 

c)  Is there pressure at the Power Switch output bulkhead 
and at the Power Switch itself? Is the Switch set at 15 psi 
(1 bar)? 

d)  Is the pipe to the Power Switch airtight? The signal 
to the Power Switch bulkhead has a restrictor that 
limits the permissible leakage from the pipe. 

e) Note  the  timer  setting. Reset the timer to the 
minimum available purging period (see 2.2.6) and 
check operation on that purge time. If it works OK, 
increase the time progressively until either it is correct, 
or the system ceases to time out at all. In the latter 
case, there is an air leak in the timer circuit. (A leak in 
the timing circuit can cause the timer not to time out.) If 
possible, establish the source of the leak with soapy 
water and retest the system. This will involve removing 
the chassis from the Control Unit 

be sure this is the 

cause before starting the work. It is VERY unusual!! 

Ensure that the timer is returned to its original 
setting and the purge time checked before putting 
the system back into service. 

Possible cause 3:  Power Switch Fault. Check the 
operation of the Power Switch. It should close above 20 psi 
(1.4 bar). 

4.6  

Pressure Sensor Calibration 

If it is decided that the Minimum Pressure Sensor or 
Purge Flow Sensor needs re-calibrating it can either be 
returned to Expo for this service or it can be done by 
the user as follows: 

Disconnect the pressure sensing pipe from the top of 

the diaphragm. (It is a “push

-

in” quick release fitting; 

firmly push inwards the collar surrounding the pipe 
where it enters the fitting, and then pull the pipe 
outwards while maintaining the pressure on the collar). 

Unscrew the 2.4” (60 mm) diameter diaphragm 

housing from the top of the Sensor. Invert it and note 
the brass adjusting screw in the center. Turning the 
screw inwards (clockwise) will lower the setting. It is 
likely that the screw will be very stiff due to the locking 
sealant. If the screw cannot be moved the application 
of gentle heat in the area of the brass screw can often 
help. DO NOT OVERHEAT! 

4.7  Filter 

Cleaning

 

If the filter element needs cleaning the transparent 
bowl can be unscrewed and removed. The filter 
element also unscrews and can then be cleaned in 
soapy water. Do not use solvents on any part of the 
filter assembly. 

Expo Technologies tip: It is sometime easier, if the bowl 
is very tight, to remove the filter by undoing the fitting 
that holds the filter into the Control Unit. On Sub-Mini-X-
Purge

£

 systems it may be necessary to remove the 

Minimum Pressure Sensor diaphragm first. 

Section 5 

Annex of Options fitted 

Refer to the annex of this manual for any options fitted as designated by the model code of the system

Expo 

Technologies 

Ltd                Expo 

Technologies 

Inc, 

Unit 

The 

Summit,                 9140 

Ravenna 

Road 

Unit 

#3,  

Hanworth 

Road, 

                  Twinsburg, 

Sunbury-On-Thames,  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OH 44087, 

TW16 5DB. UK. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U.S.A. 

Содержание ML384

Страница 1: ...llow these instructions Please refer to the standard for principles and definition These instructions apply only to the pressurizing system it is the responsibility of the manufacturer of the pressuri...

Страница 2: ......

Страница 3: ...rminal Box 11 Section 6 Installation of the System 12 Relief Valve Unit 12 Air Supply Quality 12 Pipe Work 13 Multiple Enclosures 13 Provision and Installation of Alarm Devices 13 Power Supplies and t...

Страница 4: ...b 20 C to 55 C T V 12 1462X Ex pxb ia IIC T6 Gb Ex pxb ia IIIC T95 C Db Tamb 20 C to 55 C OV Purge Outlet Valve is pneumatically operated IS Intrinsically Safe Power Alarm terminal box Timing Method E...

Страница 5: ...nts signals 1 8 NPT female minimum 6 mm pipe to be used Visual Indicators Alarm Red Pressurized Green System Purging 4 LEDs that flash sequentially to indicate elapsed time black when not purging IS T...

Страница 6: ...te intervals up to 99 minutes tolerance 0 3 seconds Default Setting 99 minutes Weight 27 kg 60lb Type RLV104 ss FS Design number D758RLV Bore Purge Outlet Valve 104 mm Relief Valve 75 mm Relief Valve...

Страница 7: ...air supply pres sure during the purge process Operation of the System Once the system is installed correctly turn on the air supply Refer to Commissioning section The purge system commences the purge...

Страница 8: ...ver be less than the required purge time The system is now operating correctly in leakage compensation mode If the system has not performed as expected check the installation thoroughly and ensure it...

Страница 9: ...switching devices may be limited in their gas group The certification documentation supplied with any such devices must be checked to ensure their suitability This system is primarily designed for use...

Страница 10: ...entered the enclosure before pressurization Purging is the process of removal contaminated air and replacement with air or inert gas known to be free from flammable gas The duration of this purge proc...

Страница 11: ...ower Interlock switch Alarm Trip Purge Time Machinery Start Normal Operation CLAPS Regulator Pressure Intermediate switch contacts open Intermediate sensor sends falling pressure signal Fault Conditio...

Страница 12: ...m specified pressure Purge Flow Sensor The Purge Flow Sensor monitors flow through the Purge Outlet Valve At correct purge flow rates above the minimum specified for purging the sensor sends a signal...

Страница 13: ...ntially dangerous to energise the pressurized enclosure in an non pressurized condition when it is known that there is potentially explosive gas or dust in the hazardous location Visual Indicators Vis...

Страница 14: ...controls the leakage compensation air flow into the enclosure after the purging is complete It either increases or decreases the air flow into the enclosure as appropriate to maintain a stable runnin...

Страница 15: ...might affect the calibration of the device In particular the exterior of the spark arrestor should not be painted or blocked in any way Air Supply Quality The MiniPurge system should be connected to...

Страница 16: ...above the minimum the Minimum Pressure Sensor re turns a positive pressurized signal causing the alarm indicator on the control unit to change from red to green When the pressure falls below the minim...

Страница 17: ...all screws in the terminals are secure In all cases the application and isolation of power must be controlled by the MiniPurge system using the power interlock signal No switches are permitted between...

Страница 18: ...e minimum pressure sensing pipe was removed Open the Purge Flow Restrictor Valve very slowly until the Pressure Relief Valve opens Check the opening pressure is within calibration limits This test can...

Страница 19: ...check readings on manometer as system will automatically re purge when it reaches minimum pressure 20 While the system re purges return the CLAPS Regulator to the initial setting 21 If minimum pressu...

Страница 20: ...ation There are no unauthorised modifications The air supply is uncontaminated The interlocks and alarms function correctly Approval labels are legible and undamaged Adequate spares are carried The ac...

Страница 21: ...nsitive and it is recommended that a 1 4 turn maximum adjustments are applied between tests Re calibration of the Pressure Sensors The brass nozzle on the sensor is sealed into position using Loctite...

Страница 22: ...designed for ease of fault finding and many of the components fitted are plug in or chassis mounted Check components by substitution only after establishing that such action is necessary Before carryi...

Страница 23: ...n the supply pipe Static pressure of 5 barg must be maintained during purge Check air supply pressure at the inlet to the control unit Ensure that the supply pipe bore is suitable for the flow rate Pr...

Страница 24: ...as stated on the Customer Test and Inspection Sheet S0015 018 Pressure gauge Air Supply Pressure 0 10 barg S0015 135 Miniature gauge Logic Pressure 0 4 barg ETM IS31 001 IS battery pack for electronic...

Страница 25: ...system merely tops up for any enclosure leakage The system provides an initial high flow of purging air that leaves the PE through the Relief Valve After the initial purging has been completed the Co...

Страница 26: ...one PE can be protected by a single system If PEs are connected and purged in series e g Daisy Chained the Outlet Orifice must be fitted on the last enclosure with the Purge Inlet to the first enclosu...

Страница 27: ...ally by the user by the use of local isolating switch 1 4 2 In accordance with NFPA 496 Expo Mini X Purge systems can have the Action on Pressure Failure normally Alarm and Trip adjusted by the user t...

Страница 28: ...ation do not confuse this flow rate with that caused by excessive setting of the LCV Close the LCV slowly observing the manometer or gauge see item 2 1 3 above The PE pressure will start to fall as th...

Страница 29: ...quantity The LCV is too far open and the air flow is holding the RLV open continuously Note Some CFHP systems have a deliberate but modest Continuous air flow through the RLV in normal operation do n...

Страница 30: ...in the air supply For this reason a dust and water filter should always be fitted But debris can enter from other sources and it is vital therefore that the procedures described in Section 2 is carrie...

Страница 31: ...d Is the pipe to the Power Switch airtight The signal to the Power Switch bulkhead has a restrictor that limits the permissible leakage from the pipe e Note the timer setting Reset the timer to the m...

Страница 32: ...e com Appendix A Certifications Download the certificates at www expoworldwide com downloads Component Certificate Number Purge System ATEX Certificate SIRA 01ATEX1295X IECEx Certificate IECEx SIR07 0...

Страница 33: ...7 6 29 3 32 3 57 2 027256 6 5 9 02 180 5 33529 7 33529 5 1 0 41 0 0 7 5 6 6 67 0 286 1 67 1 66 67 H 81 7 21 2 67 1 66 67 8 77 1 6 67 1 66 67 72 5 1 81 66 67 7 27 5 6 0 7 5 6 6 127 6 UG 1 352 7 21 0 16...

Страница 34: ...50 7 6 7 78 725 17 50 7 6 7 9 6312 G 7521 385 7 0 5 6 77 5 3 1 725 50 35 6685 1 725 6 67 0 385 1 0 1 385 28 1 725 81 7 21 2 25 175 16 6 5 8 76 21 0 1 080 3 0 1 385 57 7 21 77 16 225 7521 7 0 5 72 5 1...

Страница 35: ...d NOTE LC BOOST system is optional LC BOOST 71 66 72 66 7 1 PP 29 5 1 PP 1 7 8163 72 5 1 6 0 7 5 5 1 67 786 33529 02 1R 7 668 UG 1 352 7 21 0 16 216 1 PP 2 127 6 SR 7HFKQRORJLHV LPLWHG 2 1R 1 6 7 7 86...

Страница 36: ...RM 1 8 NPT 1 8 NPT 1 4 6mm I D 1 4 6mm I D 1 NPT PI H CONNECT TO EITHER A OR B 1 2 NPT 1 2 NPT A B 1 25mm I D MINIMUM 1 8 NPT 1 8 NPT 1 8 NPT ELECTRICAL SIGNAL VIA EEx e JUNCTION BOX RECOMMENDED MINIM...

Страница 37: ......

Страница 38: ...09 110 111 112 113 114 115 116 117 118 BLACK GREY BROWN BLACK GREY BROWN GREY BLACK BLUE BROWN TERMINAL LAYOUT INTERMEDIATE PRESSURE CONTACTS SEE CIRCUIT DIAGRAM ALARM PRESSURISED CONTACTS MOTOR INTER...

Страница 39: ......

Страница 40: ...N O T S C A L E SR 7HFKQRORJLHV LPLWHG JOB No FINISH TITLE CUSTOMER SHEET No O F PROJECTION D I M E N S I O N S I N m m 81 7 1 20 DRAWING No 1 NRB from Expo Technologies Limited neither are they to b...

Страница 41: ...Pressure Equipment Directive 97 23 EC MiniPurge Systems are classified as not higher than category I under Article 9 of this Directive and intended for use in potentially explosive atmospheres Hazard...

Страница 42: ......

Страница 43: ......

Страница 44: ...ologies Ltd Unit 2 The Summit Hanworth Road Sunbury on Thames TW16 5DB UK Tel 44 0 20 8398 8011 Fax 44 0 20 8398 8014 E mail sales expoworldwide com Qingdao Expo M E Technologies Co Ltd 329 Huashan Er...

Отзывы: