Connection diagrams •
23
3110086 EHC20 UK 110515
N. Terminal plan and connections
N.1
Terminal box
The mains section on the right-hand side of the terminal box is protected by an additional plastic panel.
Before removing this, ensure that the controller has been disconnected from the power supply.
Bridge
N.2
Terminal plan for electrical connections
V2
V1
S8
S7
VFS2
RC
VFS1
SD Card
Ethernet
S6
S5
S4
S3
S2
S1
GND
R6
NC
C
NO
R5 R4 R3 R2 R1
N
L
Mains
Relays
PF relays
Extra low voltages
Max. 12 V
Extra low voltages
Max. 12 VAC/DC
Terminal: Connection for:
S1
Sensor 1
S2
Sensor 2
S3
Sensor 3
S4
Sensor 4
S5
Sensor 5
S6
Sensor 6
S7
Sensor 7
S8
Sensor 8
V1
0-10 V / PWM
V2
0-10 V / PWM
VFS1
Grundfos direct sensor
VFS2
Grundfos direct sensor
RC
Room controller
SD card slot
for data storage and
updates
Ensure that the card is
the right way around!
The card should lock
with no resistance,
do not use excessive
force!
Ethernet
(optional)
For connecting to a
LAN
Potential-free
relay
NO
Normally open
(closer)
C
Common
(voltage)
NC
Normally closed
(opener)
Mains
230 VAC
Mains voltages
230 VAC 50-60 Hz
Terminal: Connection for:
R1
Switch output 1 (rot. sp.)
R2
Switch output 2 (rot. sp.)
R3
Switch output 3
R4
Switch output 4
R5
Switch output 5
R6
Switch output 6
N
Mains neutral wire N
L
Mains live wire L
The PE earth wire should be connected
to the PE metal terminal block!