25
2551868A
Setting unit into operation
6.2.1
Pressure independent control valve (PICV)
Heating
PICV set points (if required)
Valve Tolerances
The maximum flow rate will vary depending on the varying differential pressure
across the units and the resulting flow rate may differ from the value shown
above. The valve should be set to 125% above the design flow rate. The project
specific set-point (if required) can be confirmed by Evinox Energy.
Tighten Actuator Connections
Ensure that the actuators are tightened to ensure the operation of the unit.
DHW PICV
(Types 1-4)
DHW PICV
(Types 5-8)
Heating PICV
(Types 1-8)
Maximum flow rate
1600 l/h
3609 l/h
575 l/h
Start up ∆P
25 kPa
25 kPa
25 kPa
Max ∆P
400 kPa
400 kPa
400 kPa
Valve size
DN20
DN25
DN15
Thread
G 1”
G 1 1/4”
G 3/4’’
Actuator Stroke
2.5 mm
5.5 mm
2.5 mm
Actuator control signal
0-10V
0-10V
0-10V
Mechanical pre-setting
Not available
Available
Available
Parameter
Cooling PICV
(Types 1, 5)
Cooling PICV
(Types 2, 3, 6, 7)
Cooling PICV
(Types 4, 8)
Maximum flow rate
1330 l/h
3609 l/h
4001 l/h
Start up ∆P
25 kPa
25 kPa
25 kPa
Max ∆P
400 kPa
400 kPa
400 kPa
Valve size
DN15
DN25
DN32
Thread
G 3/4”
G 1 1/4”
G 1 1/2”
Actuator Stroke
5 mm
5.5 mm
5.5 mm
Actuator control signal
0-10V
0-10V
0-10V
Mechanical pre-setting
Available
Available
Available
Pre-set Flow (l/h) Pre-set
Flow (l/h)
0.5
2.2
324
0.6
100
2.4
351
0.8
128
2.6
379
1.0
156
2.8
407
1.2
184
3.0
445
1.4
212
3.2
463
1.6
240
3.4
491
1.8
268
3.6
519
2.0
296
3.8
547
2.2
324
4.0
575