Flushing Primary Circuit
Before filling ModuSat® heat interface unit. The primary
system should be cleaned and flushed in accordance to
BG29/2012
To open the by-pass:
Ensure both isolation valves are closed as shown in the
picture.
Use a suitable screwdriver or other tool to twist the
screw on the H-shape by-pass valve into the open
position.
Close the bypass after flushing is complete.
Provide isolation valves and a strainer.
If Evinox valve kit is not used, it must be ensured that other isolation valves provided.
Strainer on the primary inlet protects internal components from debris and sediments.
Tighten the connections.
When connecting the ModuSat® heat interface unit, ensure that all the connections are
tightened to avoid any leaks.
First fill of the HIU
Clean and flush the system before connecting the unit.
Filling the system should be performed only after the system has been fully
flushed and cleaned. Poor water quality may cause failure of the operation of the
unit.
Water quality.
It is recommended that the flushing and cleaning of the primary circuits, domestic
water circuit, secondary cooling and heating circuits is performed by a qualified
person in accordance with current standards, regulations and BSRIA guidelines.
In the case of a water leak.
Take caution of hot water
Slowly close the isolation valves at the top or bottom of the unit
Contact Evinox Energy
The ModuSat® pump should not be used for flushing.
The pump is integral to the unit and should not be used for flushing and cleaning
the system. Failure to meet this requirement will invalidate the warranty.