Instruction manual for POWERLINE 33 series UPS
2010/06/22
www.ever.eu
45
TECHNICAL DATA
POWERLINE 33
PARAMETERS/MODEL
Model 10k
Model 20k
Model 30k
Model 40k
Model 50k
Output power
1)
10 kVA
10 kW
20 kVA
16 kW
30 kVA
24 kW
40 kVA
32 kW
50 kVA
35 kW
GENERAL DATA
Topology
VFI-SS-111
Sprawno
ść
całk. dla Pmax (dla VFI)
> 94%
Total efficiency for Pmax (for ECO)
> 98%
Cooling
Forced, internal fans
Protection level
IP20
Work environment
Separate rooms with low contamination levels
Operating temperature
2)
10 ÷ 40°C
Storage temperature
0 ÷ 40°C
Relative humidity when working
< 95%
Relative humidity during storage
< 95%
Height above sea level
3)
<1,000 m
RECTIFIER
Input voltage
~173 ÷ 485 Vrms ± 2%
Input voltage frequency
45 ÷ 55 Hz ± 1 Hz
Power factor (PF)
> 0.95
Safeguard (F3, F4)
Overcurrent switches for base and BYPASS lines 3 c 63 A (ch.B)
INVERTER
Output voltage (RMS)
~400 Vrms ± 2%
Output voltage waveform
Sine
Output voltage frequency
Synchronous/ 50Hz ± 0.2 Hz
Static voltage regulation
< 1%
Output voltage distortion THDu
< 1,2% for Pmax (line)
< 5% (PN-EN 62040-3)
Crest factor CF
5:1
Protection
Inverter modes
–
short circuit and overload electronic protection
BYPASS line operation – input overvoltage protection
BATTERIES
Maximum number of internal batteries
2 x 32
Internal batteries
VRLA 12 V / 7Ah or VRLA 12 V / 9Ah
Permitted total capacity of batteries
2 x 200 Ah
Maximum charge current
10A
Backup time
Depends on the type and number of batteries
Maximum battery charge time
Depends on the type and number of batteries
Internal batteries (F1)
2x 63 A/440 VDC cylindrical 22x58 GLB
Protection
External batteries (F5)
2x 63 A/440 VDC cylindrical 22x58 GLB (optional)
MECHANICAL PARAMETERS
Dimensions (width x depth x height)
405 x 840 x 1,040 mm
UPS weight
4)
270 kg
FITTINGS
Terminals
screw terminals; max. 35 mm
2
(wire)
Signals
sound and LED, LCD display
Communication interface
RS 232, USB, network management card SNMP/HTTP -optional
EPO
yes (NC)
Manual BYPASS switch
yes
Note: The manufacturer reserves the right to modify the above parameters without prior notice.
Notes:
1)
For standard operation, the load that is applied to the output must not exceed 80% of the value in the table. The power
margin is necessary to ensure the continuous work of the connected devices in the case of instantaneous surges of the
load.
2)
Constant exposure of the battery module to temperatures of +25°C reduces the battery life.
3)
The permitted maximum load of the power supply unit decreases with the height above the sea level above the limit
specified above.
4)
Weight for the typical battery set-up 1x 2x 32x VRLA 12V /7Ah. Weight depends on the type and number of batteries.