Instruction manual for POWERLINE 33 series UPS
2010/06/22
www.ever.eu
32
TURN OFF AND DISCONNECT
Proceed as follows to fully disconnect the power supply unit:
1)
Turn the unit off by using the interface (KONTROLA 1/4; UPS) on the logical
level.
2)
When uninstalling, disconnect the safeguards of the main line and BYPASS in
the room/building switching station.
3)
Set safeguards F3 and F4 to OFF.
4)
Disconnect safeguards F1, F2, and F5 by opening them and removing the fuse
links.
5)
If the battery packs are connected, repeat step 4 for safeguards F1 and F2 for
the battery packs.
6)
Unscrew protective caps from the connecting elements (rear panel of the power
supply unit and potential modules).
7)
Disconnect the cables fed from the switchboard, power supply unit, and
modules (between modules, as well). It is forbidden to leave loose end cables
unconnected.
8)
Put the protective caps on.
9)
Close mounts F1, F2, and F5 in the power supply unit, and F1 and F2 in the
modules, if the fuse links have been removed. The fuse links must not be stored
in the power supply unit, unless it is installed.
OPERATION MODES
Figure 3: Operation mode scheme